16
Installation
(For Qualified Installers Only)
© Travis Industries
4012412
100-01270_000
Installation Example: Interior Vertical Installation
*
Install vent at clearance specified by the vent manufacturer.
Floor Protection
Outside air may be drawn from
a ventilated crawl space.
2” Min.
Vent
Clearance*
24” Minimum
Insulation
must maintain
clearance.
2” Min.
Ceiling Support / Fire Stop Spacer
Roof Flashing
Storm Collar
Vertical Cap
Vent must
maintain
clearance to
combustibles.
“L” Vent
Seal each vent
section (including
adapters, elbows,
etc...) by injecting a
liberal amount of
500° F. RTV
silicone into the gap
between sections.
500° F. RTV
Silicone
Vent
Clearance*
Floor Protection
6” Minimum
6” Minimum
2”
Minimum
“Tee”
Vent
Clearance*
7-1/4”
Each manufacturer’s
“T” section varies in
height. Make sure to
measure the “T” prior
to installation to verify
it fits.