Installation
(qualified installers only)
15
© Travis Industries, Inc.
4/11/22 - 1538
Outdoor Linear Burners
Enclosure Ventilation Requirements
The linear burner enclosure must be ventilated to properly cool the fire pit (see illustration below for details).
WARNING
The chase must be ventilated in accordance with the requirements listed below to allow the appliance to
cool. Failure to provide this ventilation will create a severe fire risk. The ventilation grilles must be
installed within 24” of the appliance.
Enclosure Ventilation Overview
The linear burner enclosure must have at least (2) vents. The vents must be on opposite sides of the
enclosure from each other (either on the ends (a) or along the sides (b). Each vent must provide a minimum
of
9 square inches
of free area.
Example: If (w) = 4" and (h) = 2"
4" x 2" = 8 square inches
8"
< 9" (the minimum)
NOT LARGE ENOUGH
Example: If (w) = 12" and (h) = 2"
2" x 12" = 24 square inches
24"
> 9" (the minimum)
LARGE ENOUGH