Installation
(qualified installers only)
15
© Travis Industries, Inc.
5/21/20 - 1534
Tempest Lantern 24v
Direct-Run Wire Length Chart
This type of wire configuration allows for long distances between the transformer and
Lantern (see illustration below). Use the charts below to determine the correct wire
gauge and length.
24
Volt
Lead
26
Volt
Lead*
28
Volt
Lead*
Wire
Wire
Wire
14
G
min
0'
14
G
min
79'
14
G
min
234'
max
242'
max
384'
max
499'
12
G
min
0'
12
G
min
120'
12
G
min
356'
max
369'
max
584'
max
760'
10
G
min
0'
10
G
min
184'
10
G
min
548'
max
566'
max
897'
max
1168'
* Not available on some transformers.
Wiring Examples:
Daisy-Chain Installations:
When using 3 Lanterns on one branch, 14 G wire, and 150’ of wire, use the 28V Lead.
When using 4 Lanterns on one branch, 10 G wire, and 100’ of wire, use the 24V Lead.
Direct Run Installations:
When using a Lantern on a 200’ run, 14 G wire, use the 24V Lead.
When using 6 Lanterns, each on a 200’ run, 14 G wire, use the 24V Lead.
How to Determine Wire Gauge
: When purchasing your wire, it should include wire gauge (the larger the
number, the smaller the diameter wire). The wire will also be printed with a gauge number (e.g. AWG#14
= 14 gauge, 10AWG = 10 gauge, etc.). Do not use wires of dissimilar gauges (do not use 14 gauge & 10
gauge wire on the same transformer).