RS-WMB, RD-WMB Installation Instructions TG201349 Issue 4, 26-Aug-2015. Applies to 1.02.2.

RS-WMB, RD-WMB 

Installation Instructions

8

Configure Controller Strategy 

(not pre-configured controllers)

9

Replace Front Panel

3 InStAllAtIon 

(continued)

Use with IQ4

The IQ4 can be configured either by using the SET strategy 

block (recommended), or by manual configuration.

Using the SEt strategy block (recommended):

 

Add  the  SET  Strategy  Block  to  the  strategy.  The 

strategy  blocks  are  located  in  the  ‘Standard  Block’ 

section  of  the  Strategy  Library  in  the  ‘WMB  Room 

Modules’ section. There is a separate section for RS 

and RD, each section has 4 blocks, one block for each 

product version (-T, -TC, -TH, -THC).

 

Set  the  Wallbus  Interface  module’s  ‘Address’ 

parameter to the RS-WMB, RD-WMB’s address on 

the Wallbus (default is 2.)

 

Ensure that the Wallbus Interface module’s inputs and 

outputs are linked to the required modules.

Important: 

When  using  the  strategy  block  (as  explained 

above)  some  PVs  write  their  value  to  the  RD-WMB  and  will 

overwrite changes to that PV made in the RD-WMB’s Settings 

Menu. If this is not required, remove the PV from the Wallbus 

Interface module’s inputs. See RS-WMB, RD-WMB Data 

Sheet (TA201348).

Adding the strategy block will automatically add the Wallbus 

Network  module,  and  create  an  instance  of  the  Wallbus 

Interface module. 

The  strategy  block  configures  the  inputs  and  outputs  of  the 

Wallbus  Interface  module  -  see  RS-WMB,  RD-WMB  Data 

Sheet  (TA201348).  This  configuration  should  be  suitable  for 

most  applications.  If  different  functionality  is  required  the 

strategy will need to be modified after the strategy block has 

been added.

Manual configuration:

 

Add  the  Wallbus  Network  module  to  the  strategy 

(default values will be suitable).

 

Add a Wallbus Interface module to the strategy.

 

SET  the  Wallbus  Interface  module’s  ‘Address’ 

parameter to the RS-WMB, RD-WMB’s address on 

the Wallbus.

 

Set  up  the  Wallbus  Interface  module’s  input  and 

output connections to specify the PV (PV Index) in the 

RS-WMB, RD-WMB that they are to be linked to as well 

as their other parameters. The RS-WMB, RD-WMB’s 

PVs  are  described  in  the  RS-WMB,  RD-WMB  Data 

Sheet (TA201348). 

 

Link the Wallbus Interface module’s inputs and outputs 

to the required modules in the strategy.

For  details  of  the  Wallbus  Network  and  Wallbus  Interface 

modules see the IQ4 Configuration Manual (TE201263). 

The controller strategy must be configured using SET v7.0 or greater. For details of using SET - see the SET Manual 

(TE200147).

For IQeco

I/Omodule  2  must  be  set  up  with  WMB  display  type.  Its 

channels are connected to external sensors with scaling type 

‘112, WMB pre-scaled’ as follows:

Channel 1: Temperature

Channel 2: Humidity*

Channel 3: Dew point*

*Humidity and Dew point on -H, CO

2

 on -C versions only

The fan can operate in one of seven modes, this is set in I/O 

module 2, Fan Configuration parameter (f). It is set up in the 

RD by the controller on power up.

Mode Description

0

no fan

1

2 position fan (OFF, ON)

2

3 position fan (OFF, ON, AUTO)

3

4 position fan (Off, 1, 2, 3)

4

5 position fan (Off, 1, 2, 3, AUTO)

5

4 position blind

6

5 position blind.

The strategy must comply with the following module mappings 

between strategy and RS-WMB, RD-WMB .

Setpoint

K44 Input to/output from RD

Occupation Override

W1 Input to/output from RD

Occupation Status

S10 Input to RD

Fan Speed

K45 Input to/output from RD

Room Temperature

S31 Input to RS-WMB, RD-WMB 

Humidity Display

S32 Input to RD

CO

2

 Concentration 

Display

S34 Input to RD

Outside Temperature 

Display

S30 Input to RD

Note:  RS-WMB  needs  S31  only  (to  define  temperature 

units,°C or °F)

Summary of Contents for RD-WMB

Page 1: ...K FI ES FR IT NL NO RU PL SE 1 Dimensions 2 Mounting Requirements 3 InStAllAtIon 1 BoX ContEntS 2 StoRInG ContEntS 1 Box contents 1 2 Storing 1 3 Installation 1 4 Disposal 8 5 Security 8 RS WMB RD WMB...

Page 2: ...e Main Module 2 Mounting Requirements continued 45 C 113 F 10 C 14 F operating Altitude 2000 m 6562 maximum accuracy 0 to 40 C 32 to 104 F H O 2 0 RH 90 RH Use No 6 screws Use 3 5 mm screws Main modul...

Page 3: ...allbus RS WMB T TH 9 10 RS WMB TC THC 18 2 5 RD WMB T TH 12 8 7 RD WMB TC THC 20 8 4 Maximum number with all RS WMB RD WMBs of same type with 50 mA full current available from controller 3 Installatio...

Page 4: ...odule to the strategy default values will be suitable Add a Wallbus Interface module to the strategy SET the Wallbus Interface module s Address parameter to the RS WMB RD WMB s address on the Wallbus...

Page 5: ...controller Or RD WMB KOSF THC 200 XXX XXX FIRMWARE REV WMB ADDRESS 2 23 3 ERR 5s Home display Communication error RD WMB THC WALL MODULE SOFTWARE VERSION 1434 e g Default PIN 1434 RD WMB THC WALL MOD...

Page 6: ...be if more than one device on wallbus SETPOINT TYPE Can be set to the following NUMERICAL GRAPHICAL Icon Description Scroll down next value Scroll up previous value Edit selected value Exit setting m...

Page 7: ...priate Depending on the configuration some displays may not be visible Note The available displays can be seen in the More menu regardless of the configuration of the Home display Check correct value...

Page 8: ...tre Do not dispose of with normal household waste Do not burn 5 SECURITY RS WMB RD WMB must have its security correctly configured to reduce the risk of unauthorised access The advice described in the...

Reviews: