T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 5, 28/08/09

3

Installation Instructions

T/PC

INSTALLATION 

(continued)

Wire to Controller

8

Insert Cable

7

either use M20 flexible conduit

or use M16 cable gland

IQ1xx, IQ2xx

polarity independent

Sensor

24 Vdc
IN

Terminate screen at IQ end only

Analogue input
channel linked
for current (

I

)

I

IQ system TP/I/22/HF/200 (Belden
8761) cable recommended.
Terminal size 0.5 to 2.5 mm

2

 (20 to

14 AWG)

IQ3

Sensor

0 (0 V)
N (in)

Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V),
instead connect to AUX+ (+24V).

+ (24 V)

Replace Connector

9

Replace Lid

10

a

b

Note that IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with
cable or conduit connection fully tightened.