T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 5, 28/08/09
3
Installation Instructions
T/PC
INSTALLATION
(continued)
Wire to Controller
8
Insert Cable
7
either use M20 flexible conduit
or use M16 cable gland
IQ1xx, IQ2xx
polarity independent
Sensor
24 Vdc
IN
Terminate screen at IQ end only
Analogue input
channel linked
for current (
I
)
I
IQ system TP/I/22/HF/200 (Belden
8761) cable recommended.
Terminal size 0.5 to 2.5 mm
2
(20 to
14 AWG)
IQ3
Sensor
0 (0 V)
N (in)
Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V),
instead connect to AUX+ (+24V).
+ (24 V)
Replace Connector
9
Replace Lid
10
a
b
Note that IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with
cable or conduit connection fully tightened.
N