24
0xA0, 0xA1
I2Cconfig0
Bit flags
N/A
Defines I2C sensor 0 address, and operating modes
0xA2, 0xA3
I2CSetPoint0
0.1K *
0 to 6553.5 I2C Sensor 0 low temp alarm setting
0xA4, 0xA5
I2CHiLoAlarm0
0.1K *
0 to 6553.5 I2C Sensor 0 high temp alarm setting
0xA6, 0xA7
I2Cconfig1
Bit flags
N/A
Defines I2C sensor 1 address, and operating modes
0xA8, 0xA9
I2CSetPoint1
0.1K *
0 to 6553.5 I2C Sensor 1 low temp alarm setting
0xAA, 0xAB
I2CHiLoAlarm1
0.1K *
0 to 6553.5 I2C Sensor 1 high temp alarm setting
0xAC, 0xAD
I2Cconfig2
Bit flags
N/A
Defines I2C sensor 2 address, and operating modes
0xAE, 0xAF
I2CSetPoint2
0.1K *
0 to 6553.5 I2C Sensor 2 low temp alarm setting
0xB0, 0xB1
I2CHiLoAlarm2
0.1K *
0 to 6553.5 I2C Sensor 2 high temp alarm setting
0XB2, 0xB3
I2Cconfig3
Bit flags
N/A
Defines I2C sensor 3 address, and operating modes
0XB4, 0xB5
I2CSetPoint3
0.1K *
0 to 6553.5 I2C Sensor 3 low temp alarm setting
0XB6, 0xB7
I2CHiLoAlarm3
0.1K *
0 to 6553.5 I2C Sensor 3 high temp alarm setting
0XB8, 0xB9
I2Cconfig4
Bit flags
N/A
Defines I2C sensor 4 address, and operating modes
0xBA, 0xBB
I2CSetPoint4
0.1K *
0 to 6553.5 I2C Sensor 4 low temp alarm setting
0xBC, 0xBD
I2CHiLoAlarm4
0.1K *
0 to 6553.5 I2C Sensor 4 high temp alarm setting
0xBE, 0xBF
I2Cconfig5
Bit flags
N/A
Defines I2C sensor 5 address, and operating modes
0xC0, 0xC1
I2CSetPoint5
0.1K *
0 to 6553.5 I2C Sensor 5 low temp alarm setting
0xC2, 0xC3
I2CHiLoAlarm5
0.1K *
0 to 6553.5 I2C Sensor 5 high temp alarm setting
0XC4, 0xC5
I2Cconfig6
Bit flags
N/A
Defines I2C sensor 6 address, and operating modes
0xC6, 0xD7
I2CSetPoint6
0.1K *
0 to 6553.5 I2C Sensor 6 low temp alarm setting
0xC8, 0xD9
I2CHiLoAlarm6
0.1K *
0 to 6553.5 I2C Sensor 6 high temp alarm setting
0xCA, 0xDB
I2Cconfig7
Bit flags
N/A
Defines I2C sensor 7 address, and operating modes
0xCC, 0xCD
I2CSetPoint7
0.1K *
0 to 6553.5 I2C Sensor 7 low temp alarm setting
0xCE, 0xCF
I2CHiLoAlarm7
0.1K *
0 to 6553.5 I2C Sensor 7 high temp alarm setting
0xD0 Word
PWRSDdebDef
Sec
0 to 65535
Debounce interval for main power loss
0xD2 Word
PWRSUdebDef
Sec
0 to 65535
Debounce interval for main power applied
0xD4 Word
PWRSDDef
Sec
0 to 65535
Shut-Down delay for main power loss
0xD6 Word
PWRSUDef
Sec
0 to 65535
Start-Up delay for main power applied
0xD8 Word
IGNSDdebDef
Sec
0 to 65535
Debounce interval for IGN input turned off
0xDA Word
IGNSUdebDef
Sec
0 to 65535
Debounce interval for IGN input turned on
0xDC Word
IGNSDDef
Sec
0 to 65535
Shut-Down delay for IGN input turned off
0XDE Word
IGNSUDef
Sec
0 to 65535
Start-Up delay for IGN input turned on
0xE0 Word
PBSDDef
Sec
0 to 65535
Shut-Down delay for Pushbutton off
0XE2 Word
PBSUDef
Sec
0 to 65535
Start-Up delay for Pushbutton on
0xE4 Word
BATTSDDef
Sec
0 to 65535
Shut-Down delay for low battery voltage or capacity
0xE6 Word
Cmd98SDDef
Sec
0 to 65535
Shut-Down delay for command PowerSupplyStatusCmd
0xE8 Word
Cmd98SUDef
Sec
0 to 65535
Start-Up delay for command PowerSupplyStatusCmd
0xEA to 0xFD
Future
0xFE
Word BattTime2Recharge
Min
0 to 65535 Minutes from charge termination to start of recharge battery