BattTempMaxDef - EEprom Locations 8C:
Description:
When BattTempMaxEn is enabled, the HESC-SER will terminate charging a standard battery pack when the battery
temperature rises above BattTempMaxDef degrees.
Purpose:
Prevent damage to batteries that can occur from being over charged or charged at high ambient temperatures.
22.
BattVminDef - EEprom Locations 0x8E:
Description:
When BattVminEn is enabled, the HESC-SER will not charge or terminate charging a standard battery pack when the
battery voltage is below BattVminDef mV.
Purpose:
To prevent damage to batteries that can occur from being charged when in an excessively low charge condition, or to
prevent normal charging if one or more cells are faulty.
23. PWRSDdebDef (0xD0), PWRSUdebDef (0xD2), IGNSDdebDef (0xD8), IGNSUdebDef (0xDA)
Description:
Defines the interval for debouncing signal. Range is 0 to 65535 seconds.
Purpose:
To prevent unnecessary start-up or shut-down of the Host CPU.
24. PWRSDDef (0xD4), IGNSDDef (0xDC), PBSDDef (0xE0), BATTSDDef (0xE4), Cmd98SDDef (0xE6)
Description:
Defines the timer interval for Shut-Down. Range is 0 to 65535 seconds. Setting value equal zero disables timer.
Purpose:
Shut-Down timers allows time to close files, and properly stop the operating system.
25. PWRSUDef (0xD6), IGNSUDef (0xDE), PBSUDef (0xE2), Cmd98SUDef (0xE8)
Description:
Defines the timer interval for Start-Up. Range is 0 to 65535 seconds. Setting value equal zero disables timer.
Purpose:
Start-up timers allow the delayed start of the Host CPU to conserve energy.