Table 13, SLA Two Stage Charging Set-up
EEprom Enable
Values
EEprom Variable
Values
Stage Description
BattTempMaxEn = 1
BattTempMax = 3182*
1
Terminates charging if battery temperature above
BattTempMax.
Set for 45C
BattVmaxEn = 1
BattVmax = 14700
1
Terminates charging if battery voltage above BattVmaxDef.
Set for 13.9V
BattTempCompEn = 1 BattTempComp = 18
1
Compensates the BattVDef voltage for the ambient
temperature. Compensation is in mV starting at 298.2K
(25C).
N/A
BattVDef = 15700
1
"Float" voltage set-up. Set for 13.7 volts
N/A
BattIDef = 2500
1
Maximum charge current. Set for 2500mA
BattTempMaxEn = 0
N/A
2
Terminates charging if battery temperature above
BattTempMax.
Set for 45C
BattVmaxEn = 0
N/A
2
Terminates charging if battery voltage above BattVmaxDef.
Set for 13.9V
BattTempCompEn = 1 BattTempComp = 18
2
Compensates the BattVDef voltage for the ambient
temperature. Compensation is in mV starting at 298.2K
(25C).
N/A
BattVDef = 13700
2
"Float" voltage set-up. Set for 13.7 volts
N/A
BattIDef = 2500
2
Maximum charge current. Set for 2500mA
CHCycleMax = 2
Set for two stage charging
BattAutoStartEn = 1
Charging auto starts when the HESC is reset (main power is
removed then re-applied), or when a new battery is inserted
TermEn = 1
Charge termination is enabled
BattIsolateEn = 1
HESC de-activates the battery enable line (BE) after the
power supply enters the shutdown mode.
Then = 1
Thermistor monitoring enabled