Observe the following points: 

• The laws, standards and directives in force. 
• Best practice at the time of installation 
• The device operating manual. 
• An operating manual can only give general instructions. They must be interpreted in the context of 
a specific installation. 
  
The device is intended solely for use conforming to its purpose. Any repairs or modifications by the 
user  are  forbidden!  Do  not  use  with  other  devices  the  operation  of  which  could  endanger  people, 
animals or property. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note:

 

The signal strength between the transmitter and the receiver decreases as the distance 

increases. Where there is a line of sight connection, the range is approximately 30 m in corridors 
and 100 m in large workshops or halls. The range can be increased with an 

0

2

LINE

 repeater.

 

 
 

General characteristics

 

Transmission frequency

 

868.3 MHz

 

Transmission power

 

10 mW max.

 

 2. Safety 

 3. Technical characteristics 

EnOcean Equipment Profile

 

A5-02-13

 

Measurement range

 

from -30°C to +50°C 

 

Measurement resolution

 

0.314°C

 

Storage temperature

 

From -20°C to +60°C

 

Illumination 

 

>100 lux on average per day

 

Degree of protection

 

IP 54, on its base

 

Range in buildings

 

Masonry

 

20m, through 3 walls at most

 

Reinforced concrete

 

10m, through 1 wall/ceiling at most

 

Plasterboard / wood

 

30m, through 5 walls at most

 

Installation altitude

 

2000m max.

 

Measurement accuracy

 

+/- 1°C from -5°C to +35°C  
+/- 1.5°C from -30°C to +50°C 

Summary of Contents for 02LINE 10020076

Page 1: ...ws without prejudicing the rights of the end customer that arise from the sales contract with his reseller If the event of exercising of a legitimate and regular right TRI02SYS may at its sole discretion rectify the device fault or supply a fault free device Any claim beyond this and all claims for consequential damages are excluded A legitimate fault exists if the device cannot be used at the tim...

Page 2: ...tance increases Where there is a line of sight connection the range is approximately 30 m in corridors and 100 m in large workshops or halls The range can be increased with an 02LINE repeater General characteristics Transmission frequency 868 3 MHz Transmission power 10 mW max 2 Safety 3 Technical characteristics EnOcean Equipment Profile A5 02 13 Measurement range from 30 C to 50 C Measurement re...

Page 3: ...e that averaged across the day the mean illuminance is 100 lux d The sensor s operating power reserve when fully charged in conditions of total darkness is 4 days Note The device is designed for external use To clean use a damp cloth 10020076 sensors transmit the measured temperatures using the frame described in the EnOcean Equipment Profiles EEP2 1 document A5 02 13 consultable under www enocean...

Page 4: ...e to metallic objects or close to materials containing metallic elements Observe a distance of at least 10 cm Humidity in the materials Devices emitting high frequency signals such as audio and video systems computers electronic ballasts or fluorescent tubes Observe a distance of at least 0 5 m 6 3 Contacts E mail contact trio2sys fr This product can be sold and operated in the countries of the Eu...

Reviews: