background image

10

Steel Tanks

Steel tanks should comply with the requirements BS 799,

Pt. 5: 1987 and mounted on brick or block piers with a

waterproof membrane between the piers and tank.

The tank should be fitted with fill and vent connections

(weather protected), a drain-off cock, shut-off valve and

an oil level indicator.

Plastic Tanks

Polyethylene tanks are now widely used because of their

advantages over traditional steel tanks:

(a)  They do not need pier supports and can be mounted

directly on any flat surface giving uniform support for

the tank base.

(b) They do not corrode and therefore never need

painting.

(c)  They are easier to handle because of their lower

weight.

(d)  They have a 10 year manufacturer’s guarantee.

Plastic tanks should be fitted with similar components to

those used with steel tanks.

Fire Protection

To comply with building regulation 

Section J5:

1

Where a storage tank is close to a dwelling, fire

cladding must be provided to the eaves, if less than

1.8m from the top of the tank.

2

The cladding must extend 300mm beyond the tank.

3

The tank must be sited on a non-combustible base.

Pollution Protection

To comply with building regulation 

section J6

, the tank

must be ‘bunded’ (i.e. double walled) if:

1

The tank is less than 10m from a stream.

2

The tank is less than 50m from a well, spring, or drinking

water.

3

The tank cannot be viewed from the delivery point.

4

In the event of a leak, there is a risk of oil reaching a

manhole cover or drain.

The tank capacity exceeds 2500 Litres.

Oil supply line

A long life flexible oil hose is supplied with the boiler. 

A filter and shut-off valve are also required.  These should

be fitted as shown if Figs. 4 and 5.

The oil shut-off valve should be fitted as close to the

burner as practicable to enable the burner to be

disconnected without undue loss of oil.  The filter must be

connected in the oil supply pipe and positioned as close

to the oil tank as possible.

Fire Valve

A fire-valve must be fitted in the oil line outside the

building with its sensing phial positioned within the boiler

casing below the control panel.  A clip is provided for

retaining the phial.

All oil line joints must be completely sealed and the total

pipe run thoroughly flushed out before connecting to the

burner.  No soldered joints are permitted in the oil line.

The oil line can be fed into the back of the boiler base tray

or through the holes at the side.

Single pipe oil supply (Fig. 4 )

When, the bottom of the oil supply tank is above the

burner, a single pipe gravity system can be used.  The oil

supply pipe must be connected to the suction port on the

burner pump via the flexible hose.

Two pipe oil supply (Fig. 5)

Where, the bottom of the oil storage tank is below the

burner, a two pipe  suction lift system is necessary.  

When using a two pipe system, it is important that the

by-pass screw is fitted, on the BFP II pump remove the

end cover and filter, then remove the ‘U’ washer by

unscrewing the bottom screw, then replace the screw

ensuring it is fully inserted. An additional flexible hose is

also required.

A spring loaded non- return valve must be fitted in the

suction line to stop the oil running back to the tank. 

A filter, shut-off valve and fire valve must also be fitted in

the line.

No valves are permitted in the return line which must

remain unobstructed at all times.

Notes:

(1)  The pump suction should not exceed 0.4  bar, other

wise dissolved gas will be released from the oil to

affect combustion.

(2)  The return pipe must end at the same level as the

suction outlet to prevent loss of prime.

(3) The outlet from the tank should be approximately

75mm (3 in) above the bottom to prevent sediment

and water being drawn into the supply pipe.

Oil De-aerator -
Single pipe supply (Fig. 6)

Where a two pipe suction lift system is required, but the

return pipe is too long, or impractical to run, an Oil De-

aerator can be used.  The burner is piped as for a two

pipe system up to the Oil De-aerator but only a single

pipe is required to be run back to the oil storage tank.  A

none-return valve is not required with this system but the

bypass plug must be fitted in the pump as for a two pipe

system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for EuroStar 50-90

Page 1: ...der USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS FS External Models EuroStar 50 90 EuroStar 95 115 FLOOR STANDING OIL FIRED CENTRAL HEATING BOILERS FOR EXTERNAL INSTALLATION ONLY TRIANCO BED...

Page 2: ...disposable gloves face masks and eye protection After handling wash hands and other exposed parts When disposing reduce dust with water spray ensure parts are securely wrapped GLUES SEALANTS PAINT Glu...

Page 3: ...8 Heating and domestic hot water system 8 Electrical supply 9 Thermostats 9 Frost Protection 9 5 OIL SUPPLY 10 Oil storage tank Steel and Plastic 10 Oil supply line 10 Single pipe oil supply 10 11 Two...

Page 4: ...elect the temperature of the water leaving the boiler It is calibrated between High and Low in five intermediate settings corresponding to a temperature range of 82 C high to 55 C low Set the temperat...

Page 5: ...do not wait until the tank is nearly empty before refilling otherwise sludge and water could be sucked into the oil pipe to affect the burner s operation and reduce pump life After a delivery of oil...

Page 6: ...tallation and servicing instructions or The breakdown occurs immediately following an annual service visit In this instance your appointed Service Agent must check all his work PRIOR to requesting Tri...

Page 7: ...m the front of the boiler The front mounted flue cover permits easy access for the removal of the flue baffles and cleaning of heating surfaces The boiler is fully automatic in operation and incorpora...

Page 8: ...1 1 4 MODEL X Y Z 50 90 195 503 255 95 115 195 559 255 NOTE ALL DIMENSIONS IN MM FLOW RETURN SOCKET SIZES L W W L Y X X Z Y FLOW RETURN PIPE ACCESS POINTS 88 88 47 SIDE VIEW FRONT VIEW REAR VIEW ELECT...

Page 9: ...ontent litre 22 30 Flow return sockets in 4 x 1 BSP 4 x 1 1 4 BSP Max operating pressure bar 3 3 psi 43 5 43 5 Test Pressure bar 4 5 4 5 psi 65 3 65 3 Water side resistance 10 diff mbar 25 0 25 4 20 d...

Page 10: ...FIG 2 WIRING DIAGRAM EXTERNAL MODEL 7 REMOVE LINK WHEN FITTING EXTERNAL CONTROLS...

Page 11: ...rt L The Control of Pollution Oil Regulations Current I E E Regulations Local Water Undertakings By laws OFTEC Installation Requirements for Oil Fired Boilers and Oil Storage Tanks Health and Safety a...

Page 12: ...is fitted with a variable setting control thermostat and a pre set limit thermostat Should the boiler thermostat malfunction the limit thermostat will take over control and shut down the boiler Frost...

Page 13: ...il line outside the building with its sensing phial positioned within the boiler casing below the control panel A clip is provided for retaining the phial All oil line joints must be completely sealed...

Page 14: ...ANCO EUROSTAR BOILER FIRE VALVE SENSOR FIRE VALVE SENSOR BURNER BURNER SHUT OFF VALVE SHUT OFF VALVE H NONE RETURN VALVE FITTED IN VERTICAL PIPE RUN 50mm 2 DIA AIR VENT 50mm 2 DIA AIR VENT SAW CUT PIP...

Page 15: ...T LEVEL GAUGE LEVEL GAUGE VALVE ISOLATING VALVE DRAIN COCK SHUT OFF VALVE BURNER OIL FILTER FIRE VALVE SENSOR TRIANCO EUROSTAR BOILER TERMINAL GUARD OIL DE AERATOR OUTSIDE BUILDING REMOTE OPERATED FIR...

Page 16: ...d to avoid products of combustion entering the building 13 Note 1 The terminal should be positioned so as to avoid products of combustion entering the building Note 2 The terminal must be protected by...

Page 17: ...item 1 in position and secure with the 9xM5 screws provided 3 Place the second gasket item 4 up to the back panel 4 Fit the terminal box item 5 with the discharge pointing downwards and secure with t...

Page 18: ...s until the flame cuts off sharply this indicates any remaining air has been dispersed 8 All the burner to run for about 15 minutes then take a CO2 reading through the sampling hole in flue cover Comp...

Page 19: ...readings with those given under Burner Settings and make any air or oil pressure adjustments necessary Servicing the Boiler Burner removed 1 Remove flue cover and lift out flue baffles See Fig 9 2 Br...

Page 20: ...not seeing flame Clean photo cell and ensure it is fully plugged in Air trapped in pump Bleed off air through pressure gauge tapping Solenoid valve faulty Check coil for continuity and replace if fau...

Page 21: ...on from tank Dirt in solenoid valve Clean or replace valve Pump shut off piston sticking Replace pump MORNING START LOCK OUT Faulty non return valve or air leak Replace non return valve and cure leak...

Page 22: ...0808 210784 Boiler Control Thermostat 1 206896 206896 Limit Thermostat 1 206892 206892 Gasket 1 210846 210846 Baffle W U Top 1 208838 Baffle Plate Top 2 208865 Baffle W U Bottom 3 208834 Baffle W U 6...

Page 23: ...opyright in this brochure and the drawings or illustrations contained in it is vested in Trianco Limited and neither the brochure or any part thereof may be reproduced without prior written consent Tr...

Reviews: