Instinct
Display Module Replacement
5
Table 1: Controls Settings
HEATING SETTING
FACTORY DEFAULT
MINIMUM SETTING
MAXIMUM SETTING
EXISTING SETTING
Heating Operation
Enabled
Demand Type
Thermostat & Outd.
Curve
Absolute Max CH Setpoint
185°F [85°C]
68°F [20°C]
188°F [87°C]
CH1 Maximum Setpoint
180°F [82°C]
68°F [20°C]
188°F [87°C]
CH1 Minimum Setpoint
80°F [27°C]
60°F [15°C]
188°F [87°C]
Outdoor Curve Coldest Day
10°F [-12°C]
-30°F [-34°C]
50°F [10°C]
Outdoor Curve Warmest Day
64°F [18°C]
60°F [15°C]
78°F [25°C]
CH2 Circuit
Enabled
CH2 Maximum Setpoint
140°F [60°C]
68°F [20°C]
194°F [90°C]
CH2 Minimum Setpoint
80°F [27°C]
60°F [15°C]
190°F [88°C]
Warm Weather Shutdown
Off
Off
78°F [25°C]
Circulation Pump
Permanent
Disabled
CH Post Pump Time
5 Minutes
Off
20 Minutes
Freeze Protection
Enabled
Frost Protection Setpoint
-22°F [-30°C]
-22°F [-30°C]
50°F [10°C]
Parallel Shift Value
0°F [0°C]
0°F [0°C]
144°F [80°C]
CH Call Blocking
2 Minutes
0 Minutes
30 Minutes
DOMESTIC SETTING
SOLO
FACTORY
DEFAULT
COMBI
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EXISTING
SETTING
DHW Operation
Enabled
Enabled
Demand Type
Thermostat
N/A
DHW Boiler Setpoint
168°F [76°C]
168°F [76°C]
96°F [35°C]
188°F [87°C]
DHW Setpoint
140°F [60°C]
140°F [60°C]
68°F [20°C]
168F [75°C]
DHW Warmstart Setpoint
N/A
125°F [52°C]
86°F [30°C]
140°F [60°C]
DHW Warmstart Hysteresis
N/A
30°F [17K]
9K
36K
DHW On Differential
6°F [3°C]
N/A
4°F [2°C]
18°F [10°C]
DHW Storage Adder
27°F [15°C]
18°F [10°C]
10°F [5°C]
54°F [30°C]
DHW Post Pump Time
2 Minutes
2 Minutes
Off
30 Minutes
DHW Priority Timeout
Off
Off
Off
120 Minutes
DHW Priority
Enabled
Enabled
DHW Call Blocking
1 Minute
1 Minute
0 Minute
30 Minutes
DHW to CH Call Blocking
1 Minute
1 Minute
0 Minute
30 Minutes
Antilegionella Function
Disabled
Enabled