background image

The control panel will display a H followed

by  the  current  boiler  temperature  when

placed into high fire test mode.

2. If  the  combustion  levels  during  high  fire  are

outside  the  recommended  combustion  settings

adjust the THROTTLE SCREW (see Fig. 5) as

follows:

Counter-clockwise  adjustment  of  the  THROT-

TLE SCREW at High Fire:

O2 decreases and C02 increases

Clockwise  adjustment  of  the  THROTTLE

SCREW at High Fire:

O2 increases and CO2 decreases

3. Once  the  combustion  level  is  set  at  high  fire,

manually place the boiler into low fire mode by

pressing  the  MODE  button  with  “-”  button

simultaneously on the control display while in

the standby (STBY) mode.

The control panel will display a L followed

by  the  current  boiler  temperature  when

placed into low fire test mode.

4. If the CO

combustion level  at low fire is not

/- 0.2 of the combustion level measured

at high fire, remove the offset cover screw and

adjust the plastic 

OFFSET SCREW

using a T-

40 Torx wrench (see Fig. 5) as follows:

Counter-clockwise  adjustment  of  OFFSET

SCREW  at Low Fire:

O2 increases and CO2 decreases

Clockwise adjustment  of OFFSET SCREW at

Low Fire:

O2 decreases and CO2 increases

5. Press the “+” and “-” buttons simultaneously to

shutdown the burner.

TriMax Instructions

1. Press the round INSTALLER button. See Fig. 6.

2. Enter the installer access code “054” by using

the 

LEFT

and 

RIGHT

buttons to select a digit

and the 

UP

and 

DOWN

buttons to change the

digit.  Press the 

OK

button to enter the access

code.

3. Press  the 

RIGHT

button  to  highlight  the

Manual Operation icon

then press the 

OK

button.

4. Press  the 

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and

power the CH circulator.

An adequate CH load must be present to dissi-

pate the heat generated during the combustion

test.  If an adequate CH load is not available, an

indirect water heater can be used to dissipate the

heat by creating a DHW call which will enable

the DHW circulator.

NOTICE

NOTICE

NOTICE

Prestige SOLO 399

Burner Mounting Plate Kit

5

Installer
Button

Fig. 6: TriMax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH

CH1

FAN

DHW

SYS

CH2

Summary of Contents for PSRKIT39

Page 1: ...rdous situation which if ignored can result in serious injury or substantial property damage For your safety turn off electrical power supply at service panel and allow unit to cool before proceeding...

Page 2: ...ors from the blower and remove the blower retaining nuts Remove the blower with venturi and gas valve from the unit 11 Remove the 10 mm nuts and remove the burn er mounting plate assembly from the hea...

Page 3: ...g nuts are in place use a wrench to tighten using an alternating pattern until the gasket is slightly compressed See Table 2 page 7 for torque specifications 21 Re assemble the blower onto the burner...

Page 4: ...is operating at optimum conditions The combustion testing and adjustments must be performed by a qualified installer service agency or the gas supplier All com bustion measurements must be perform wit...

Page 5: ...wrench see Fig 5 as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire O2 increases and CO2 decreases Clockwise adjustment of OFFSET SCREW at Low Fire O2 decreases and CO2 increases 5 P...

Page 6: ...mbustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire 8 If the CO2 combustion level at low fire is not wi...

Page 7: ...for latest recommendations 2 Wear long sleeved loose fitting clothing gloves and eyes protection 3 Assure adequate ventilation 4 Wash with soap and water after contact 5 Wash potentially contaminated...

Reviews: