5. Press the 

RIGHT

button to adjust the firing rate

to 100% (high fire).  Hold down the  

RIGHT

button to rapidly increase the firing rate.

6. If  the  combustion  levels  during  high  fire  are

outside  the  recommended  combustion  settings

adjust the THROTTLE SCREW (see Fig. 5) as

follows:

Counter-clockwise  adjustment  of  the  THROT-

TLE SCREW at High Fire (100% firing rate):

O2 decreases and C02 increases

Clockwise  adjustment  of  the  THROTTLE

SCREW at High Fire (100% firing rate):

O2 increases and CO2 decreases

7. Once  the  combustion  level  is  set  at  high  fire,

manually place the boiler into low fire mode by

pressing the 

LEFT

button to adjust firing rate

down to 1% (low fire).

8. If the CO

combustion level at low fire is not

/-0.2 of the combustion level measured

at high fire, remove the offset cover screw and

adjust the plastic OFFSET SCREW (see Fig. 5)

using a T-40 Torx wrench as follows:

Counter-clockwise  adjustment  of  OFFSET

SCREW at Low Fire (1% firing rate):

O2 increases and CO2 decreases

Clockwise adjustment  of OFFSET SCREW at

Low Fire (1% firing rate):

O2 decreases and CO2 increases

9. Press the 

OK

button while the fan icon is high-

lighted to shutdown the burner.

10. Press the 

DOWN

button to highlight the home

screen icon

then press 

OK 

to return to the

home screen.

Summary of Contents for PSRKIT39

Page 1: ...rdous situation which if ignored can result in serious injury or substantial property damage For your safety turn off electrical power supply at service panel and allow unit to cool before proceeding...

Page 2: ...ors from the blower and remove the blower retaining nuts Remove the blower with venturi and gas valve from the unit 11 Remove the 10 mm nuts and remove the burn er mounting plate assembly from the hea...

Page 3: ...g nuts are in place use a wrench to tighten using an alternating pattern until the gasket is slightly compressed See Table 2 page 7 for torque specifications 21 Re assemble the blower onto the burner...

Page 4: ...is operating at optimum conditions The combustion testing and adjustments must be performed by a qualified installer service agency or the gas supplier All com bustion measurements must be perform wit...

Page 5: ...wrench see Fig 5 as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire O2 increases and CO2 decreases Clockwise adjustment of OFFSET SCREW at Low Fire O2 decreases and CO2 increases 5 P...

Page 6: ...mbustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire 8 If the CO2 combustion level at low fire is not wi...

Page 7: ...for latest recommendations 2 Wear long sleeved loose fitting clothing gloves and eyes protection 3 Assure adequate ventilation 4 Wash with soap and water after contact 5 Wash potentially contaminated...

Reviews: