FMS-1655L

Installation Manual

Version: 03.27.17

 Triatek  FMS-1655L

Summary of Contents for FMS-1655L

Page 1: ...FMS 1655L Installation Manual Version 03 27 17 Triatek FMS 1655L ...

Page 2: ...lation Setpoint Pressure Deadband Analog Output Analog Output Range zero based or offset Analog Output Upper Limit 0 100 Analog Output Lower Limit 0 100 Analog Output Action Direct or Reverse PID Constants Proportional Constant 0 5 100 0 Integral Constant 0 0 100 0 Derivative Constant 0 0 100 0 Alarm Limits Positive Isolation High Alarm Setpoint Positive Isolation High Warning Setpoint Positive Is...

Page 3: ...nt Triatek reserves the right to change product specifications without notice 3 CONTROLLER SETTINGS Audible Alert Operating Mode audible or silent Delay Time Base secs or mins Delay Setting 0 60 Engineering Units Inches of Water or Pascals ...

Page 4: ...he right to change product specifications without notice Warning Failure to follow the wiring diagrams could result in damage to your equipment and could void your warranty Under no circumstances should a single transformer be split between an actuator and controller Doing so will damage the actuator the transformer the controller or all units A single 120 24V 30Va transformer is required for the ...

Page 5: ...tal Input to Door Switch 21 Digital Input to Flow Switch 22 Digital Input to Occupancy Sensor 23 Relay Output to Alarm 24 Relay Output to Warning 25 RelayOutput1 26 Power 27 Isolated Power Supply 28 COMMUNICATIONS WIRING 29 30 FMS 1655L PROGRAMMING Introduction 31 Main Display Screen 31 Configuring Isolation Room Controller 32 Configuring Alarm Limits 32 Set Target Setpoints 32 Setting Up the Anal...

Page 6: ...uivalent Touchscreen User Interface LCD Size 3 2 diagonal LCDType Transmissive Resolution 240 x 320 portrait Viewing Area 50 60 mm x 66 80 mm Color Depth 18 bit or 262K colors Backlight Color White Luminous Intensity min 2500 cd m2 Mechanical FMS 1655L Display Module Housing Surface Mount 3 W x 5 H x 1 13 D FMS 1655L Display Module Housing Flush Mount 5 6 W x 8 5 H x 0 75 D FMS 1655L Controller Ho...

Page 7: ...r the LonWorks network The alarm will automatically reset when the unit senses that room pressure has returned to proper limits or the attendant can mute the audible alarm by touching the Alarm Audible button at the bottom of the screen The FMS 1655L provides four relay outputs that can be used for remote alarms or pilot control functions The operation of each relay can be configured to trigger on...

Page 8: ...without notice FMS 1655L 8 FMS 1655L Surface Mount Case Dimensions Triatek reserves the right to change product specifications without notice 3 5 3 4 3 4 PWR LED GND V Right Side View Left Angle Side View Control Unit Adapter Inside Control Unit 1 13 Cable provided terminated at control unit ...

Page 9: ...NG WIRING Triatek reserves the right to change product specifications without notice The FMS 1655L Flush Mount display is mounted flushed to the wall using the supplied retro fit ring or wall box Use the retro fit ring as a template to mark the wall for cutout ...

Page 10: ...out notice 10 MOUNTING WIRING FMS 1655L Surface Mount Display Triatek reserves the right to change product specifications without notice The FMS 1655L display backplate may be mounted directly to a standard single gang wall box using the two slots along the centerline Use the backplate as a template to mark the mounting holes and the cable access hole at the center of the backplate 3 04 5 05 ø 0 1...

Page 11: ...Controller Mounting Hole Patterns FMS 1655L 11 MOUNTING WIRING Triatek reserves the right to change product specifications without notice ...

Page 12: ...ductor cable from the FMS 1655L controller down wall to the opening of the single gang low voltage mounting bracket Connect cable wires to Vin GND and IO at the sensor s 9 pin connector 6 Attach the flow tube to the sensor port then push the tube and sensor module into place and secure to the mounting enclosure with two 6 32 x 3 4 screws supplied 7 Install the louvered cover plate 8 On the opposit...

Page 13: ... Stainless Steel Flow Tube Mounting Plate Gasket Thin Silicone Caulking apply around tube and between stainless steel plate and wall to seal unit Terminal For connection of transmitter to FMS 1655L Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To FMS Controller Wall Section cutaway view Orange wall brac...

Page 14: ...N ROOM CORRIDOR Stainless Steel Mounting Plate Gasket Louvered Cover Plate Stainless Steel Flow Tube Mounting Plate Gasket Thin Silicone Caulking apply around tube and between stainless steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1655L Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as ...

Page 15: ...RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD DI_3 1 2 3 INT SNSR G 5v V DI FLASH_WP SHLD NETWRK IN NT_2 NT_1 Vsel RNG 4 1 2 3 LED Ain Aout JP4 JP5 RNG mA LED4 JP7 Ain JP3 JP2 FLA FLA 1 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor Remote Sensor Transmitter GND Io V...

Page 16: ...access the status and the configuration of the unit Also used by configuration software to configure unit Analog Output Unit has 4 analog outputs which can be configured for 0 5 VDC or 0 10VDC Analog Input Unit has 4 analog inputs which can be configured for 4 20 mA 0 5VDC or 0 10VDC Power The FMS 1655L can be powered by either 24 VAC or 24 VDC A 120 VAC to 24 VAC Step Down Isolation Transformer i...

Page 17: ...SNSR DIGITAL IN RLY1 RLY2 RLY3 RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD DI_3 1 2 3 SELECT INT SNSR G 5v V DI SRVC FLASH_WP 5v GND GND GND SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT Vsel RNG 4 1 2 3 LED Aout JP4 JP5 RNG LED3 LED4 JP7 JP3 1 1 1 Air Control Modulator Optional External Transmitter Power Supply 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 A...

Page 18: ..._WP SHLD NETWRK IN NT_2 Vsel RNG LED1 LED Aout LED2 JP4 JP5 RNG JP7 Ain LED1 JP3 LED2 1 1 4 20mA OUT NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor Remote Pressure Sensor Io Vin GND 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 1...

Page 19: ... GND PH1 PH2 VS SYN IN SASH SNSR DIGITAL IN RLY1 RLY2 RLY3 RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD DI_3 INT SNSR G 5v V DI SRVC 5v GND GND GND SHLD NETWRK IN NT_2 NT_1 AUX PWR OUT Vsel LED 4 LED3 LED4 JP3 1 Remote Pressure Sensor 1 Remote Pressure Sensor 2 GND Io Vin GND Io Vin 4 20mA OUT 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 AI 4 JP7 1 2 3 ...

Page 20: ...D 10v V ANALOG IN 1 2 3 EXT SNSR 5v GND GND GND GND AUX PWR OUTPUT ANALOG OUT RNG 4 1 2 3 Ain 4 Aout JP4 2 JP5 4 RNG 1 mA 3 JP7 Ain JP6 1 1 1 NT_1 NT_2 NETWRK OUT DI_1 DI_2 DI_4 GND GND GND PH1 PH2 VS SYN 24V IN SASH SNSR DIGITAL IN RLY1 RLY2 RLY3 RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD DI_3 EXT SNSR SELECT INT SNSR G 5v V DI SRVC SRVC FLASH_WP 1 SHLD NETWRK IN NT_2 NT_1 PWR Vsel 1 SW1 LED1 JP2 LED LED...

Page 21: ...I_3 G 5v V DI Vsel 1 1 AO_1 AO_2 AO_3 AO_4 AI_1 AI_2 AI_3 AI_4 GND GND 10v V ANALOG IN NT_1 NT_2 NETWRK OUT GND PH1 PH2 VS SYN 24V IN SASH SNSR RLY1 RLY2 RLY3 RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD 1 2 3 EXT SNSR SELECT INT SNSR SRVC EXT SRVC SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT 1 SW1 RNG 4 1 2 3 LED1 JP2 LED Ain 4 Aout LED2 1 JP4 2 JP5 4 RNG 1 Tx m...

Page 22: ... JP3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1JP2 FLA JP2 FLA LED2 1 1 LED3 LED LED LED LED4 LED LED LED 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1...

Page 23: ...JP6 1 1 1 1 AO_1 AO_2 AO_3 AO_4 AI_1 AI_2 AI_3 AI_4 GND GND 10v V ANALOG IN NT_1 NT_2 NETWRK OUT GND PH1 PH2 VS SYN IN SASH SNSR RLY1 RLY2 RLY3 RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD 1 2 3 EXT SNSR SELECT INT SNSR SRVC EXT SNSR 5v GND GND GND GND SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT ANALOG OUT RNG 4 1 2 3 LED Ain Aout 1 JP4 2 JP5 4 1 mA 3 LED3 LED4 JP7 JP6 1 1 1 NC No Connection to Field Wiring Fie...

Page 24: ...1 JP5 RNG LED4 JP7 Ain 1 JP6 JP3 JP2 LED2 1 1 1 1 1 1 AO_1 AO_2 AO_3 AO_4 AI_1 AI_2 GND GND 10v V ANALOG IN NT_1 NT_2 NETWRK OUT DI_1 DI_2 DI_4 GND GND GND PH1 PH2 VS SYN 24V IN SASH SNSR DIGITAL IN SHLD DI_3 1 2 3 EXT SNSR SELECT INT SNSR V DI EXT SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT ANALOG OUT Vsel RNG 4 1 2 Aout LED2 JP4 JP5 RNG LED4 JP7 Ain JP6 JP3 JP2 FLA...

Page 25: ...ut JP4 2 JP5 4 RNG 1 mA 3 LED4 JP7 Ain JP6 JP2 1 1 1 1 AO_1 AO_2 AO_3 AO_4 AI_1 AI_2 AI_3 AI_4 GND GND 10v V ANALOG IN NT_1 NT_2 NETWRK OUT DI_1 DI_2 DI_4 GND GND GND PH1 PH2 VS SYN IN SASH SNSR DIGITAL IN SHLD DI_3 1 2 3 EXT SNSR SELECT INT SNSR 5v V DI EXT SNSR FLASH_WP 5v GND GND GND GND SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT ANALOG OUT Vsel RNG 4 1 2 3 LED Ain Aout JP4 2 JP5 4 RNG 1 mA 3 LED4...

Page 26: ...D Aout LED2 JP4 1 JP5 RNG LED4 JP7 Ain 1 JP6 JP3 LED2 1 1 1 1 1 1 AO_1 AO_2 AO_3 AO_4 AI_1 AI_2 AI_3 AI_4 GND GND 10v V ANALOG IN NT_1 NT_2 NETWRK OUT DI_1 DI_2 DI_4 GND GND GND PH1 PH2 VS SYN 24V IN SASH SNSR DIGITAL IN SHLD DI_3 1 2 3 EXT SNSR SELECT INT SNSR 5v V DI EXT SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT ANALOG OUT Vsel RNG 4 1 2 3 LED Aout LED2 JP4 JP5 R...

Page 27: ...3 LED4 JP7 Ain 1 JP6 LED1 JP3 LED2 1 1 1 1 LED4 1 1 AO_1 AO_2 AO_3 AO_4 AI_1 AI_2 AI_3 AI_4 GND GND 10v V ANALOG IN NT_1 NT_2 T_2 NETWRK OUT DI_1 DI_2 DI_4 GND GND GND PH1 PH2 VS SYN SASH SNSR DIGITAL IN RLY1 RLY2 RLY3 RLY4 C3 4 C2 C1 RELAY OUTPUTS SHLD HLD DI_3 1 2 3 EXT SNSR SELECT INT SNSR V DI SRVC EXT SNSR 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT ANALOG OUT Vsel 1 RNG 4 1 ...

Page 28: ...60 Hz Black White Stepdown Isolation Transformer provided with FMS Controller Only Class 2 wiring in this compartment Note This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker This circuit breaker should be mounted in an approved electrical enclosure located separately but in close pr...

Page 29: ...CT INT SNSR SRVC EXT SNSR 5v GND GND GND GND AUX PWR OUTPUT ANALOG OUT RNG LED Aout LED2 JP5 RNG LED3 JP7 Ain LED2 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor LON FTT 10 Free Topology Communications Network 18 22AWG Twisted Pair Cable Type Maximum Node ...

Page 30: ...ated communications problems to a minimum 1 Do not splice communications cable or wire at any point between controllers 2 Avoid the stub T tap technique of routing connecting communications cable Conductor discontinuities produced by such connections may generate RFI or other electromagnetic interference on the communications circuit 3 Do not use wire nut devices for connecting communications cabl...

Page 31: ...eutral isolation mode which is represented by a blue screen with a slashed circle The information that is displayed on the main screen includes the following from top to bottom see Figure 1 Isolation room name in the upper window up to 25 characters Current differential pressure default units in wc Current isolation mode and status Status icon centrally located Current relative humidity in the low...

Page 32: ...then this is the only required step to set up the FMS 1655L Configuring Alarm Limits To determine the limits at which the unit status changes from normal to warning and from warning to alarm the alarm limits must be configured To access the alarm limit settings select the Unit Setup option from the Main Setup Menu At the Unit Setup menu select the Alarm Limits option The high and low alarm limits ...

Page 33: ...dding up to 10 multi level passwords to the system The Password Setup option on the System Setup menu allows the user to manage the security passwords Options on the Password Setup menu include those for adding editing and deleting entries from the system as shown in Figure 7 To add a new password entry select the Add Password option from the Password Setup menu which prompts the user to enter a m...

Page 34: ...ually overridden by selecting the Overrides option from the Diagnostics menu the Analog Outputs option and then selecting the specific analog output to be overridden The user can then in real time dynamically move the damper actuator to a specific position using the slider on the override screen While in override mode the selected analog output is disconnected from its PID control loop if configur...

Page 35: ...ch S1 internal use only 1 Graphics Chip Mode Selection OFF Programming Mode ON Run Mode 2 Touch Screen Calibration Mode OFF Force calibration ON Auto calibration 3 Reserved 4 Reserved Options Dipswitch S2 Product Configuration 1 Sensor Mode OFF Single ON Dual 2 Test Mode OFF Disabled ON Enabled 3 Product Type OFF FMS 1655L ON HMS 1655L 4 Operational Mode OFF Demo Mode ON Run Mode Pushbutton Switch...

Page 36: ...Module Settings 36 Triatek reserves the right to change product specifications without notice MODULE SETTINGS FMS 1655L Triatek reserves the right to change product specifications without notice ...

Page 37: ...acetone tolulene xylene propyl or isopropyl alcohol or kerosene Touching the current name text brings up an alphanumeric keyboard to quickly change the name of the monitored room Touching anywhere else on the screen enters the Main Setup Menu if no password is stored Otherwise a password must be entered before the Main Setup Menu can be accessed Touching the units brings up Engineering Units selec...

Page 38: ... to change product specifications without notice 38 FLOW DIAGRAMS Complete Flow Diagram Due to continuous improvement Triatek reserves the right to change product specifications without notice Triatek reserves the right to change product specifications without notice ...

Page 39: ...FMS 1655L 39 FLOW DIAGRAMS Setup Menu ...

Page 40: ...FMS 1655L Due to continuous improvement Triatek reserves the right to change product specifications without notice 40 Setup Menu FLOW DIAGRAMS ...

Page 41: ...rollers fume hood controllers monitors sensors actuators and more all designed to seamlessly integrate into a facility s building automation system Triatek s customer service is unparalleled Our product support system includes on site installations phone support repairs calibrations and in depth training sessions From our knowledgable engineers and sales team to our talented field technicians Tria...