![background image](http://html.mh-extra.com/html/triatek/hms-1650/hms-1650_installation-manual_1160741007.webp)
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Mechanical
HMS-1650 Display Housing …………………………………………………………………………………………………………… 3”W x 5”H x .75”D
HMS-1650 Controller Housing …………………………………………………………………………………………………… 4.1”W x 6”H x 1.85”D
Environmental
Operating Temperature ………………………………………………………………………………………………………… 32° to 125° F Operating
Operating Humidity …………………………………………………………………………………………………… 10% - 95% RH, Non-condensing
HMS Air Flow Sensor
Type of Sensor ……………………………………………………………………………………………………………… Thru-the-hood ultra sensitive
Face Velocity Accuracy …………………………………………………………………………………………………………… 0-200 FPM ± 2 FPM*
Dimensions …………………………………………………………………………………………………………………… 25/32”H x 43/4”W x 35/16”D
NIST Traceable / Individual certification available as option
*@72°F ± 5°F
Venturi Valve (Order Separately)
Diameter …………………………………………………………………………………………………………………………… 6”, 8”, 10”, 12”, 14” & 16”O.D.
CFM Range ……………………………………………………………………………………………………………………………………………… 30-2400
Materials ………………………………………………………………………………………………………… Aluminum, Stainless Steel, Heresite Coating
Sound Insulation ………………………………………………………………………………………………………………………………………… Optional
Actuation ………………………………………………………………………………………………………………………………… Electronic or Pneumatic
Part Number Guide
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Triatek reserves the right to change product specifications without notice.
-
7
-
HMS-1650
Triatek reserves the right to change product specifications without notice.
GENERAL
Specifications
*Accuracy is ± 5FPM when velocity drops below 60FPM or exceeds 140 FPM
HMS1650
-
1
-
1
Sensor
Type
Sash
Sensor
1 = single smart sidewall sensor
blank = sash sensor not included
2 = dual smart sidewall sensor S = sash position sensor included
A = single Honeywell sidewall sensor
B = dual Honeywell sidewall sensor