background image

HMS-1655 

Installation Manual

Version: 03.15.17

 Triatek  HMS-1655 

Fume Hood Controller

Summary of Contents for HMS-1655

Page 1: ...HMS 1655 Installation Manual Version 03 15 17 Triatek HMS 1655 Fume Hood Controller ...

Page 2: ...point Decommissioned Mode Setpoint Face Velocity Deadband Analog Output Operating Mode Direct or PID Analog Output Range zero based or offset Analog Output Upper Limit 0 100 Analog Output Lower Limit 0 100 Analog Output Input Channel AI 1 thru AI 4 TI 1 or TI 2 Analog Output Action Direct or Reverse Analog Output Range zero based or offset Sash Switch Operating Mode normally open or normally close...

Page 3: ...Setpoint Occupied Mode Low Warning Setpoint Occupied Mode Low Alarm Setpoint Unoccupied Mode High Alarm Setpoint Unoccupied Mode High Warning Setpoint Unoccupied Mode Low Warning Setpoint Unoccupied Mode Low Alarm Setpoint Audible Alert Enabled Input Channels AI 1 thru AI 4 TI 1 TI 2 Operating Mode audible or silent Delay Time Base secs or mins Delay Setting 0 60 Alarm Quiet Period Starting Hour 0...

Page 4: ...roduct specifications without notice Warning Failure to follow the wiring diagrams could result in damage to your equipment and could void your warranty Wiring diagrams can also be found at www triatek com Under no circumstances should a single transformer be split between actuator and controller Doing so will damage the actuator the transformer the controller or all units A single 120 24V 30Va tr...

Page 5: ...ancy Sensor 21 Power 22 Isolated Power Supply 23 COMMUNICATIONS BACnet MS TP 24 Metasys N2 Open 25 BASIC PROGRAMMING Introduction 26 Main Display Screen 26 Configuring Fume Hood Monitor 26 Calibrating Face Velocity Sensor 27 Configuring Sash Position Sensor 27 Calibrating Sash Position Sensor 27 Configuring Sash Settings 27 Selecting Sash Control Mode 28 Calibrating the Sash Control Feature 28 Con...

Page 6: ...DC Control Signal Wire Size 18 22 AWG minimum Power Supply Class 2 24Vac 10 30VA universal 120 240 to 24 Vac 60 50 Hz step down isolation transformer provided Communications BACnet MS TP network Two wire Twisted Pair RS 485 signaling Metasys N2 network Two wire Twisted Pair RS 485 signaling Recommended Cable Type Belden 3107A Touchscreen User Interface LCD Size 3 2 diagonal LCD Type Transmissive R...

Page 7: ...rtification available as option 72 F 5 F Venturi Valve Order Separately Diameter 8 10 12 14 O D CFMRange 35 2100 Materials Aluminum Stainless Steel Heresite Coating Insulation Optional Actuation Electronic or Pneumatic Part Number Guide 7 HMS 1655 Triatek reserves the right to change product specifications without notice GENERAL Specifications Accuracy is 5FPM when velocity drops below 60FPM or ex...

Page 8: ...ut may be dimmed or even disabled completely The HMS 1655 is equipped with a 3 2 diagonal full color touchscreen display in portrait orientation 240 x 320 The password protected menu tree is very intuitive and simplifies the setup and configuration of the unit The menus incorporate touch based interfaces such as sliders radio buttons and dialog popups to facilitate the ease of use of the HMS 1655 ...

Page 9: ...to eight digits may be programmed with each having one of four associated access levels Administrators and Facility Management personnel may have unrestricted access while general staff may be assigned restricted access passwords which limit the functionality of the user menus Fume hood operating mode selection of occupied unoccupied or decommissioned may be protected using limited access password...

Page 10: ...o mounting the assembly to its mounting surface Be careful to avoid getting sealant in the sensor port 4 See page 12 for mounting details for the HMS 1655 display unit The preferred location is eye level usually on one of the side bezel panels Please note that the display unit is cable connected to the control unit and provision must be made to route the cable without interference with the fume ho...

Page 11: ...OUNTING WIRING HMS 1655 11 Right Side View Left Angle Side View Case Dimensions Triatek reserves the right to change product specifications without notice 1 13 Cable provided terminated at control unit Control Unit ...

Page 12: ...5 Triatek reserves the right to change product specifications without notice 12 The HMS 1655 display backplate may be mounted directly to a standard single gang wall box using the two slots along the centerline Use the backplate as a template to mark the mounting holes and the cable access hole at the center of the backplate 3 04 5 05 ø 0 143 ø 0 143 ø 0 750 ...

Page 13: ...MOUNTING WIRING Controller Mounting Hole Pattern HMS 1655 Triatek reserves the right to change product specifications without notice 13 ...

Page 14: ...ut notice 14 Sensor Placement Non By Pass Type 6 00 6 00 Ø 0 50 The P1 Port must be referenced to the laboratory air for proper operation and should be a located away from air turbulence such as supply or exhaust diffusers Bottom edge of sash in uppermost position not operating height Sensor If the hood is bypassed or in close proximity to items like baffles deflectors etc contact the factory 3 1 ...

Page 15: ...nterior of Fume Hood Flexible Tubing 3 ft Supplied This port must be referenced to laboratory air for proper orientation and should be located away from turbulence Exterior of Fume Hood FIGURE 1 Preferred Sensor Mounting Interior of Fume Hood Flexible Tubing 3 ft Supplied This port must be referenced to laboratory air for proper orientation and should be located away from turbulence Exterior of Fu...

Page 16: ...product specifications without notice MOUNTING WIRING Analog Output to Pneumatic Actuator HMS 1655 Triatek reserves the right to change product specifications without notice 16 110 24 Controller Configuration Dipswitch Settings S1 1 OFF S1 5 OFF AI 1 set as 0 5V Input ...

Page 17: ...IRING Analog Output to Electric Actuator HMS 1655 Triatek reserves the right to change product specifications without notice 17 Controller Configuration Dipswitch Settings S1 1 OFF S1 5 OFF AI 1 set as 0 5V Input ...

Page 18: ...655 Due to continuous improvement Triatek reserves the right to change product specifications without notice 18 MOUNTING WIRING Analog Input Single Flow Sensor Triatek reserves the right to change product specifications without notice Controller Configuration Dipswitch Settings S1 1 OFF S1 5 OFF AI 1 set as 0 5V Input ...

Page 19: ... G The terminal should be connected to 10V IN should be connected to AI_1 and G should be connected to AGND at the HMS 1655 backplane Triatek reserves the right to change product specifications without notice Controller Configuration Dipswitch Settings S1 1 OFF S1 5 OFF AI 1 set as 0 5V Input S1 2 OFF S1 6 OFF AI 2 set as 0 5V Input ...

Page 20: ... reserves the right to change product specifications without notice 20 MOUNTING WIRING Analog Input Sash Position Sensor Triatek reserves the right to change product specifications without notice Default input for sash sensor is AI 2 but may also be terminated at AI 3 or AI 4 Controller Configuration Dipswitch Settings S1 2 OFF S1 6 ON AI 3 set as 0 10V Input ...

Page 21: ...cy Sensor Triatek reserves the right to change product specifications without notice Controller Configuration Slideswitch Settings S5 Left Active Low Digital Input Default input for occupancy sensor is DI 14 but also may be terminated at DI 2 or DI 3 ...

Page 22: ... continuous improvement Triatek reserves the right to change product specifications without notice MOUNTING WIRING HMS 1655 Power 22 Triatek reserves the right to change product specifications without notice ...

Page 23: ...r provided with HMS 1655 Only Class 2 wiring in this compartment Note This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker This circuit breaker should be mounted in an approved electrical enclosure located separately but in close proximity to this product 240 VAC 50 60 Hz Blue Slow Bl...

Page 24: ...ACnet MS TP Wiring HMS 1655 24 Controller Configuration Dipswitch Settings S3 7 ON S3 8 ON BACnet MS TP protocol selected Triatek reserves the right to change product specifications without notice NOTE For optimum network communications the reference signal REF must be connected to the NETWK REF terminals at the backplane ...

Page 25: ...ight to change product specifications without notice NOTE For optimum network communications the reference signal REF must be connected to the NETWK REF terminals at the backplane Controller Configuration Dipswitch Settings S3 7 ON S3 8 OFF Metasys N2 Open protocol selected ...

Page 26: ... and date display are the audible toggle button and the emergency purge button if it has been enabled The emergency purge button may be used to instantaneously force the exhaust damper to the maximum open position in the event of a chemical spill or other unsafe condition at the fume hood work space While in decommissioned operating mode the background is blue However while in either occupied or u...

Page 27: ...s application requires monitoring only and does not include controlling the exhaust valve of the fume hood then proceed to Selecting Sash Control Mode Section below To begin configuring the sash position sensor input enter the Main Setup Menu by touching the touchscreen display anywhere other than one of the hotspot locations From the Main Setup Menu select System Setup Analog Inputs and select th...

Page 28: ... this closed loop control mode select Sidewall Sash on the Sash Control Mode popup configuration screen and tap the Next button Follow the instructions on the next four screens to calibrate the sash position sensor for sash control operation Calibrating the Sash Control Feature The HMS 1655 features a comprehensive closed loop control scheme using both sash control and sidewall sensing The sash co...

Page 29: ...etup Menu select Unit Setup Controller Setup Analog Output and the user is prompted to select an operating mode direct control or PID control and an operating range Most applications will take advantage of the PID proportional integral derivative control mode where the control output can be customized by varying the control loop constants The operating range can either include an offset from zero ...

Page 30: ... controlling an exhaust valve that is equipped with a universal valve module UVM 1000L the real time exhaust air flow may be displayed in the lower window next to the real time sash height To display the exhaust air flow select Exhaust Flow on the Set Display Options popup configuration screen The air flow output from the UVM must be brought into analog input 4 AI 4 at the HMS 1655 and this input ...

Page 31: ...bration ON Auto calibration 3 Reserved 4 Reserved Options Dipswitch S2 mode configuration 1 1 Product Type OFF FMS HMS ON CMS 1655 2 EMERGENCY PURGE Button OFF Disabled ON Enabled 3 Mode Select OFF FMS 1655 CMS 1650 ON HMS 1655 4 Operational Mode OFF Demo Mode ON Run Mode Pushbutton Switch SW1 Reset Button Pushbutton Switch SW2 Reserved Triatek reserves the right to change product specifications w...

Page 32: ...S 1655 for sidewall velocity sensor set dipswitch positions 1 and 5 to OFF To configure HMS 1655 for sash position sensor at AI 3 default set dipswitch position 3 to OFF and dipswitch position 7 to ON For other inputs see Table 1 Analog Output Configuration Dipswitch S3 1 AO 1 Mode Selection OFF current output ON voltage output 2 AO 2 Mode Selection OFF current output ON voltage output 3 AO 3 Mode...

Page 33: ...FF ON BACnet MS TP default ON ON Controller Configuration Dipswitch S4 1 AO 1 Voltage Range Selection OFF 0 10Vdc ON 0 5Vdc 2 AO 2 Voltage Range Selection OFF 0 10Vdc ON 0 5Vdc 3 AO 3 Voltage Range Selection OFF 0 10Vdc ON 0 5 Vdc 4 AO 4 Voltage Range Selection OFF 0 10Vdc ON 0 5 Vdc Controller Configuration Slideswitch S2 Controller Configuration Slideswitch S5 LEFT Analog Outputs powered by remo...

Page 34: ...e relay output Read Only BO 4 Relay Output 4 spare relay output Read Only Binary Values BV 1 Occupancy Status Read Write BV 2 Emergency Purge MAX FLOW Read Write Triatek reserves the right to change product specifications without notice Analog Values AV 1 AI 1 Setpoint Fume Hood Face Velocity Setpoint Read Write AV 2 AI 2 Setpoint Read Write AV 3 AI 3 Setpoint Read Write AV 4 AI 4 Setpoint Read Wr...

Page 35: ...ange 0 4 194 000 Read Write AV 49 Duct Air Flow based on AI 1 flow input Read Only AV 50 Duct Air Flow based on AI 2 flow input Read Only AV 51 Duct Air Flow based on AI 3 flow input Supply Flow Read Only AV 52 Duct Air Flow based on AI 4 flow input Exhaust Flow Read Only AV 53 Volumetric Offset Supply Flow Exhaust Flow Read Only AV 54 Volumetric Offset Setpoint Read Write AV 55 AO 1 Override Leve...

Page 36: ... Write Triatek reserves the right to change product specifications without notice ADF 4 Secondary Alarm Relay High Setpoint Read Write ADF 5 Secondary Alarm Relay Low Setpoint Read Write ADF 8 AI 1 Low Alarm Setpoint Low Face Velocity Alarm Read Write ADF 9 AI 1 Low Warning Setpoint Low Face Velocity Warning Read Write ADF 10 AI 1 High Warning Setpoint High Face Velocity Warning Read Write ADF 11 ...

Page 37: ...Flow Input at AI 3 default Supply Flow Read Only ADF 51 Air Flow based on Flow Input at AI 4 default Exhaust Read Only ADF 52 Volumetric Offset Supply Flow Exhaust Flow Read Only ADF 53 Volumetric Offset Setpoint Read Write ADF 54 AO 1 Override Level Read Write ADF 55 AO 2 Override Level Read Write ADF 56 AO 3 Override Level Read Write ADF 57 AO 4 Override Level Read Write ADF 58 AI 1 Deadband Set...

Page 38: ...umeric keyboard to quickly change the name of the monitored fume hood Touching anywhere else on the screen enters the Main Setup Menu if no password is stored Otherwise a password must be entered before the Main Setup Menu can be accessed Touching DATE brings up the Date Entry popup to quickly change the current displayed date Touching the engineering units selection brings up a popup to quickly c...

Page 39: ...COMPREHENSIVE WIRING DIAGRAM HMS 1655 39 Triatek reserves the right to change product specifications without notice ...

Page 40: ...tinuous improvement Triatek reserves the right to change product specifications without notice FLOW DIAGRAMS Unit Setup Tree HMS 1655 40 Triatek reserves the right to change product specifications without notice ...

Page 41: ...FLOW DIAGRAMS Unit Setup Tree HMS 1655 41 Triatek reserves the right to change product specifications without notice ...

Page 42: ...inuous improvement Triatek reserves the right to change product specifications without notice FLOW DIAGRAMS System Setup Tree HMS 1655 42 Triatek reserves the right to change product specifications without notice ...

Page 43: ...FLOW DIAGRAMS System Setup Tree HMS 1655 43 Triatek reserves the right to change product specifications without notice ...

Page 44: ...inuous improvement Triatek reserves the right to change product specifications without notice FLOW DIAGRAMS System Setup Tree HMS 1655 44 Triatek reserves the right to change product specifications without notice ...

Page 45: ...FLOW DIAGRAMS Display Setup Tree HMS 1655 45 Triatek reserves the right to change product specifications without notice ...

Page 46: ...uous improvement Triatek reserves the right to change product specifications without notice FLOW DIAGRAMS Diagnostics Setup Tree HMS 1655 46 Triatek reserves the right to change product specifications without notice ...

Page 47: ...FLOW DIAGRAMS Notes HMS 1655 47 Triatek reserves the right to change product specifications without notice ...

Page 48: ...ers fume hood controllers monitors sensors actuators and more all designed to seamlessly integrate into a facility s building automation system Triatek s customer service is unparalleled Our product support system includes on site installations phone support repairs calibrations and in depth training sessions From our knowledgable engineers and sales team to our talented field technicians Triatek ...