background image

 

23 

 

10

 

 Troubleshooting 

10.1

 

Plant Operation 

Symptom 

Possible causes 

Solution 

Pump won’t start or 

run 

Fuse blown (if applicable). 

Replace with fuse of suitable size. 

Tripped breaker. 

Reset breaker. 

Low line voltage and wet 

electrics. 

An electrician should check the power 

supply to the plant. 

Defective pump. 

Pump must be checked by a qualified 

person. 

Pump operates but 

delivers no water 

Low line voltage or wired 

incorrectly. 

An electrician should check the power 

supply to the plant. 

Something caught in 

impellers.   

Clean out impellers or replace pump.  

WARNING: Ensure pump is disconnected 

from the mains before you attempt to 

unclog it. 

Delivery hose blocked. 

Find blockage and remove or replace 

damaged hose. 

Other pump malfunction. 

Pump must be checked by a qualified 

person. 

Plant fills above 

working water level 

Pump not working. 

Check pump is functioning properly as 

above. 

Float from the pump stuck. 

Ensure the float on the pump is set correct 

and can move freely. 

Storm water flooding. 

Redirect storm water drains. Storm water 

must never enter the plant. 

Discharge hose/pipe 

blocked. 

Find blockage and remove or replace 

damaged hose/pipe. 

Pump runs 

intermittently 

Thermal overload tripped. 

Check for clogged impeller. 

WARNING: Ensure pump is disconnected 

from the mains before you attempt to 

unclog it. 

The pump has run dry so add water. 

Damaged float. 

Pump must be checked by a qualified 

person. 

Alarm is lighting but 

the pump and is 

working 

High level float is snagged 

or caught on the side of the 

tank. 

Free the high-level alarm float; unsnag it 

from the side of the tank. 

Electrical fault. 

Get a qualified person to check that the 

alarm is installed correctly. 

The electrical panel is wet. 

Get a qualified person to check that the 

alarm is installed correctly. 

Build-up of grease 

and fat particularly on 

the float switches and 

pumps. 

Build-up of grease and fat 

may happen over a long or 

short period of time 

depending on type of 

material entering the tank. 

The float and pump may need to be 

withdrawn for hosing down.  Once the 

pump and float has been cleaned, they 

will operate in a more efficient manner. 

 

Summary of Contents for 11P Puraflo Secondary

Page 1: ...1 125 Rev 4 Jan 2019 Tricel Puraflo 1 50 Wastewater Treatment Plants Engineering a green future...

Page 2: ...eatment 11 3 Tricel Puraflo Range 12 3 1 System Specifications 12 3 2 System Components 12 3 2 1 Tricel Puraflo Module 12 3 2 2 Effluent Filter secondary treatment only 13 3 2 3 Pump 13 3 2 4 Pipework...

Page 3: ...Conditions 21 10 Troubleshooting 23 10 1 Plant Operation 23 10 2 Odours 24 11 Certification 25 11 1 Declaration of Performance Tricel Puraflo with Tricel Fortis 25 11 2 Declaration of Performance Tric...

Page 4: ...4...

Page 5: ...5...

Page 6: ...e wastewater treatment system must be appropriately trained Suitable protective clothing including waterproof abrasion resistantgloves overalls safety footwear eye ear and respiratory protection goggl...

Page 7: ...hende sludgingand thereforethisshallneverbe donealone A wastewater treatment system that fails to fully treat sewage due to poor maintenance or overloading may allow excess nutrients phosphorus and ni...

Page 8: ...using little to no energy The Tricel Puraflo system works in conjunction with your septic tank or wastewater treatment plant The wastewater is distributed evenly over the top of the peat filter using...

Page 9: ...evenly onto the peat filter via a distribution grid at the top of each Puraflo module Stage 3 Liquid effluent undergoes treatment as it filters through the bio fibrous peat in the Puraflo modules Stag...

Page 10: ...er of modules depend on loadings 7 Sampling Chamber 8 DistributionBox Flowing topercolationarea pumpchambertodischarge treated liquid Some septic tanks may only have one manhole cover 2 2 2 Plan view...

Page 11: ...tank a pumping chamber with control alarm kiosk as well as the Puraflo modules with a sampling chamber 2 3 2 Tertiary Treatment Environmentally sensitive sites or sites that are restricted in terms o...

Page 12: ...2 7 9 1 3 3 10 11 1 4 4 12 15 3 2 6 16 21 4 2 8 22 24 3 3 9 25 27 5 2 10 28 33 6 2 12 34 42 5 3 15 43 45 4 4 16 46 50 6 3 18 3 2 System Components 3 2 1 Tricel Puraflo Module Dimension Unit Value A m...

Page 13: ...hose over the septic tank 3 2 3 Pump The submersible pump and float switch is fitted with a thermal overload protection Effluent from the septic tank or waste water treatment is pumped via a 1 5inch p...

Page 14: ...ted wastewater from the Puraflo modules and the pipeworkusedforthedispersion of wastewater on top of the peat inside the Puraflo modules is in accordancewithBS3505 1986 Specification for unplasticized...

Page 15: ...15 Important If you required drawings for larger Tricel Puraflo systems from 12 to 50PE please visit http ie tricel eu downloads...

Page 16: ...re ropes in contact with the modules Care is needed to control the lift to ensure the modules are not damaged The modules are designed for a single lift when placing them in position Always lift modul...

Page 17: ...result in reduced effectiveness and increased maintenance and orreplacementcostsinthelong term 8 1 Regular Maintenance 8 1 1 Septic Tank If applicable Theseptictankshouldbede sludgedwhenrequired Inacc...

Page 18: ...lter over the septic tank ensuring that all solids fall back into the septic tank Insert the filter cartridge back into the housing ensuring that the filter is properly aligned and inserted correctly...

Page 19: ...relation to the pump o Intheeventofanelectricalstormorpowerfailure thecircuit breakerswitchesoff theelectrical linesfeedingthepump The pump alarmshouldbecheckedtoseeif they tripped to the off positio...

Page 20: ...the septic tank primary storage chamber is measured The system is inspected for any obvious non wastewater infiltration into any compartment at the time of inspection The effluent filter in the septi...

Page 21: ...e done as soon as possible An electrical connection to the plant must be maintained for it to function correctly This ensures that theplanthasacontinuousairsupplyandwherenecessarythedischargepumpwill...

Page 22: ...meticandcleaningwipes Sanitarytowels Tampons Kitchenpaper Nappies Medication Servicepersonnelmustbeaccommodatedwithclearaccesstothesystem If others size the system we will supply to these specificatio...

Page 23: ...move freely Storm water flooding Redirect storm water drains Storm water must never enter the plant Discharge hose pipe blocked Find blockage and remove or replace damaged hose pipe Pump runs intermi...

Page 24: ...in the drains are fitted and the joints sealed Air vent on pipe work not installed correctly Ensure all effluent pipes are vented correctly Vents are normally fitted to all pipes and they should be h...

Page 25: ...RP Technology Septic tank with bio fibrous peat filter Components Septic tank Pump chamber bio fibrous peat modules alarm 4 Intended for Use To treat domestic wastewater for up to 50 population equiva...

Page 26: ...ad of 0 33kg d and hydraulic daily load of 0 9m 3 d Determined at temperatures 12 0 Material Performance Essential Characteristics Method Performance Harmonised Technical Specification Water Tightness...

Page 27: ...r finstitut f r Abwassertechnik GmbH Hergenrather Weg 30 52074 Aachen Number NB 1739 Treatment design capacity Nominal organic daily load BOD5 Nominal Hydraulic daily flow QN As Set Out in Table CE fo...

Page 28: ...s peat modules alarm 4 Intended for Use To treat domestic wastewater for up to 50 population equivalent 5 Name Address and Contact Information of Manufacturer Tricel Killarney Unlimited Company tradin...

Page 29: ...s obtained at average organic daily load of 0 33kg d and hydraulic daily load of 0 9m 3 d Determined at temperatures 12 0 Material Performance Essential Characteristics Method Performance Harmonised T...

Page 30: ...rance Number NB 1164 Puraflo Notified Body Pr finstitut f r Abwassertechnik GmbH PIA Hergenrather Weg 30 52074 Aachen Germany Number NB 1739 Treatment design capacity Nominal organic daily load BOD5 N...

Page 31: ...31...

Page 32: ...Puraflo Tertiary 221361 1 62 4050 33P Puraflo Secondary 221349 1 98 4950 33P Puraflo Tertiary 221362 1 98 4950 42P Puraflo Secondary 221350 2 52 6300 42P Puraflo Tertiary 221363 2 52 6300 45P Puraflo...

Reviews: