18
•
Ensure the air blower is working by listening for a gentle hum when standing beside the plant.
•
The inlet and outlet should be inspected and rodded to remove any blockages if necessary.
•
Ensure that no storm or surface water enters the system.
•
The wastewater treatment plant should be serviced once a year or as per the manufacturer’s
instructions.
8.1.3
Effluent Filter (If applicable)
•
The filter should be inspected and cleaned bi-annually.
•
Do not use plumbing when cleaning filter.
•
Pull the filter out of the housing when cleaning.
•
Hose off the filter over the septic tank, ensuring that all solids fall back into the septic tank.
•
Insert the filter cartridge back into the housing ensuring that the filter is properly aligned and
inserted correctly.
8.1.4
Pump Chamber (If applicable)
•
The pump chamber should be inspected annually and the following checks and procedures should
be followed.
•
Remove the manhole cover and de-sludge tank if necessary.
•
Turn up the high-level alarm float switch and check that the alarm light flashes in the control
panel.
•
Clean the high-level alarm float switch if necessary.
•
Ensure that the high-level alarm float switch is positioned correctly to ensure correct operation.
•
Check the position of the pump to ensure that the control float has free movement within the
pump chamber.