18
5.10.3
Proximity to rolling & static loads
Minimum separation distances from:
•
Rolling Loads (e.g. vehicle traffic): 4 metres
•
Static Loads (e.g. dwelling house, shed): 3 metres
If the tank is installed in an area where traffic or other superimposed loadings can be applied, consult a
structural engineer for the design of a reinforced concrete slab to prevent the load being transmitted to
the tank (or its concrete surround). If this slab is constructed immediately above the tank, it should be
separated from the concrete surrounding the tank by a compressible material.
5.11
Electrical Requirements
Important:
•
Please ensure the electrical installation complies with all national regulations and
requirements.
•
Electrical installations must be carried out by a qualified and certified electrician
.
•
A wiring label is located on the inside of the alarm box.
The customers’ minimum responsibility shall consist
in the provision of:
•
The type and size of the power supply cable must comply with all national regulations and
requirements. The specification of the cable is the responsibility of a qualified electrician.
Note:
In typical domestic installations, a single run of 1.5mm² 3 core (two conductors plus earth
conductor) steel wire armoured (SWA) cable from the
customer’s
distribution cabinet to
the tank unit socket box is required.
•
The system should have its own circuit with cable protection via 10-amp MCB protected by (RCD),
rated 230V, 30mA.
•
The cable must be properly bonded to the main earth in line with current wiring regulations.
•
Never disconnect the power to the pump. It is imperative that it is running 24 hours a day, every day.