background image

Trident Emergency Products, LLC
2940 Turnpike Drive | Suite #9 | Hatboro, PA 19040 USA

16

AirPrime

™ Fire Pump Priming System

Annual Primer Testing

The AirPrime™ primer is designed to meet the NFPA requirements of: 

Dry Vacuum

 (

TEST #1

)

 and 

Priming Time

 (

TEST #2

)

. These tests 

should be performed on an annual basis, or whenever major repairs or modifications have been made to the fire pump, plumbing or primer.

TEST #1

 

Dry Vacuum Test

: Checks the primer’s ability to produce 22 inches (Hg) 

[�745 Bar]

 of vacuum, and the pump and plumbing’s 

ability to hold that vacuum. The fire pump does not have to be engaged. If you have an Automatic AirPrime, use the lower 

PRIME

 position 

on the rocker switch. If you have a Manual AirPrime, use the 

Push Button

 control. Never run a dry pump at engine speeds above 1200 

RPM. There is no time requirement for the vacuum to reach 22 inches. If the compressor has a capacity of 13.2 CFM 

[374 Cubic Centimeter 

Displacement]

, it can take several minutes to reach 22 inches 

[�75 Bar]

. This time can be shortened by engaging the pump and increasing 

the engine speed to 1200 RPM. The test process is as follows:
1.  Drain all water from pump and plumbing.
2. Close all valves and drains. Cap all suction openings and the outlet off of the suction side relief valve (if so equipped).
3. Connect a vacuum test gauge to the intake test gauge connection on the pump panel.
4. Operate the AirPrime with the air system at over 100 PSIG 

[7�0 Bar]

 pressure, air tanks filled to capacity, and at 1000 RPM engine speed; 

until the vacuum gauge indicates 22 inches (Hg) 

[�75 Bar] 

or more of vacuum. For a 

Manual

 AirPrime, depress the valve on the pump 

panel. If the primer is an 

Automatic

 AirPrime, depress the rocker switch to the 

PRIME

 (lower position) to activate the primer.

5.  Watch the gauge, if the vacuum falls more than 10 inches in 5 minutes the test has failed and is a certain indication of an air leak(s). 

Vacuum leaks may be detected by ear, with the engine turned off. Correct leaks immediately and test the priming system again.

TEST #2

 

Priming Time Test

: This test is to prove that the fire pump and primer have the capability of attaining a prime and creating 

discharge water pressure in a set period of time. This test is also conducted by the apparatus builder prior to delivery. The fire pump shall 
be engaged and primer actuated. This test is part of an annual pump performance test and is performed as follows:
1.  Set up the apparatus in accordance with the pump test outlined in the NFPA 1901 Standards.
2. Engage the pump, and increase the throttle to a maximum engine speed of 1000 RPM.
3. Operate the AirPrime with the air system over 100 PSIG 

[7�0 Bar]

 pressure, air tanks filled to capacity, and at 1000 RPM engine speed.

•  For the 

Manuallly

 controlled primer, release the push button when a discharge pressure over 20 PSIG 

[1�4 Bar]

 is obtained.

•  For the 

Automatic

 primer, place the switch in the 

AUTO PRIME

 (upper position), the primer will turn off automatically when prime is 

achieved.

4. The priming time should not exceed 30 seconds for 1250 GPM 

[4700 LPM]

 and smaller pumps. The priming time should not exceed 45 

seconds for 1500 GPM 

[5600 LPM]

 and larger pumps. An additional 15 seconds is allowed for pumps with auxiliary suctions using 4" or 

larger piping.

Higher lifts and operating at higher elevations will slow down the priming time. The air compressor rating should be a minimum of 18 
CFM 

[410 Cubic Centimeter Displacement]

 for elevations over 4000 feet 

[1200 m]

 and lifts in excess of 15 feet 

[4�5 m]

. Operation at these 

extremes may require the primer to be operated at engine speeds in excess of 1000 RPM without engaging the pump, until water reaches 
the impeller. Never run a dry pump at engine speeds above 1200 RPM.

IN-SERVICE OPERATIONAL RAMP TEST

The integrity and operation of the primer can be quickly checked (on a daily or weekly basis) as outlined below, without fire pump 
engagement:
1.  Drain all water from pump and plumbing.
2. Close all valves and drains. Cap all suction openings.

•  Operate the AirPrime with the air brake system pressure over 100 PSIG 

[7�0 Bar]

, air tanks filled to capacity, and the engine running at 

1000 RPM (with an 

Auto AirPrime

 electrically controlled model, depress the switch in the lower 

PRIME

 mode position).

3. Stop running the primer.
Time to reach 15 inches HG 

[�50 Bar]

 or 17 feet 

[5�0 m]

 on lift gauge should be within the times listed below for the volume of the pump 

being tested.

Small Body Pump (

Up To 1250

 GPM): Vacuum Time

10 inches HG 

[�33 Bar]

 (11 Feet) 

6 Seconds

15 inches HG 

[�50 Bar]

 (17 Feet) 

15 Seconds

Large Body Pump (

Over 1250

 GPM): Vacuum Time

10 inches HG

 [�33 Bar

] (11 Feet) 

8 Seconds

15 inches HG 

[�50 Bar]

 (17 Feet) 

20 Seconds

Note

: Vacuum Times listed in the table at left are for operations up 

to 2,000 feet 

[609 m]

 of elevation above sea level.  

When performing this 

In-Service Operational Ramp Test

 at higher 

elevations, the vacuum should be reduced by 1 inch (1.13 Feet) for 
each 1,000 feet 

[304 m]

 of elevation above 2,000 feet 

[609 m]

.

Summary of Contents for AirPrime SC 1906 Wildland Unit

Page 1: ...nd Operation Guide All AirPrime Models Automatic Controls Manual Controls t Lift Gauge Option Standard Control q Lift Gauge Option u q Standard Control AIRPOWER SC 1906 Self Contained Priming System AirPrime Pressure Regulator For use with high pressure SCBA cylinders ...

Page 2: ... for small trucks without air brakes See Page 5 for additional information 7 Industrial AirPrime units are available for large fire pumps Contents Available Models 2 AirPrime Overview 2 AirPrime How Does It Work 3 Installer Responsibilities 4 Air Schematic PPV Air Hose and Connections 5 Automatic Single Location AirPrime System 6 Automatic Single Location AirPrime System with Optional Vacuum Gauge...

Page 3: ...ns and safety Auto Prime Depress switch into the upper position The Green LED light will illuminate while priming occurs The primer will only activate when the OK TO PUMP light is ON and the Pump Pressure is below 20 PSIG AirPrime Primers can be used for both New and Retro Fit installations In Retro Fit scenarios an AirPrime replacement installation requires minimal tools and time Automatic AirPri...

Page 4: ... sparingly while applying sealant to avoid blockage of the internal mesh filter See Page 5 Figure 5 Remote Primer Mounting 1 A fabricated primer bracket to secure the primer within the pump enclosure The mounting height for all priming components must be ABOVE the highest priming point on the pump suction side or above the highest remote priming valve for multiple location systems to permit air re...

Page 5: ...f any kinks or bends and must not be run near exhaust components or rotating shafts Stay 6 150 mm away from any exhaust or hot components Use rubber grommets to protect the tubing from sharp metal edges at all hole locations When the installed length of the air brake tubing exceeds 20 feet 6 1 m a minimum size of 1 2 OD air brake tubing should be used Pressure Protection Valve PPV A Pressure Prote...

Page 6: ...rPrime rocker switch in AUTO PRIME mode If drafting connect all suction hoses strainer and tighten accordingly Utilize wheel chocks In Cab Apply parking brake Engage pump per manufacturers recommendations AirPrime will start priming automatically when the pump is engaged NOTE Never run a fire pump dry for more than 45 seconds Pump Panel Verify that the green OK TO PUMP light is ON and then increas...

Page 7: ... constant 12 24 volt vehicle power source Connect Black to chassis ground on the vehicle Wires 1 foot long wiring and 1 amp fuse by installer Plug the Male Deutsch connector into the Female Deutsch connector on the AirPrime solenoid 5 feet of cable 1 8 m Connect to the Male Deutsch connector on the pump discharge pressure switch 5 feet of cable 1 8 m See Figure 6 on Page 6 6 Connect a 1 4 OD 6 35 ...

Page 8: ...2 Circled Letters Used To Identify Wire Descriptions PLUG IN TO AirPrime Solenoid Black Positive and White Negative Red Wire to 12 24V Power Source Black Wire to Chassis Ground White Wire To Positive Side of OK TO PUMP Light Circuit Automatic AirPrime Assembly 1 2 6 5 1 3 5 6 3 Automatic AirPrime Panel Switch A C B D E 2 LETTER A B C D E Discharge Pressure Switch Male Deutsch Connector Female Deut...

Page 9: ...ol Manual AirPrime Second Control Point In Cab Valve Depress to Activate 3 4 Tubing Minimum PlumbTo DrainValve Strainer 3 8 Tubing Minimum 3 8 Tubing Minimum 3 8 Tubing Minimum Closed Compressed AirIn PumpPanel Valve FirePump Open 3 8 Tubing Minimum Color Key Air Supply Lines Vacuum Priming Lines InCab Valve FirePump From FirePump PrimingPoint ...

Page 10: ... button will operate the primer regardless of whether the fire pump is engaged or not Depressing the Push To Prime button directs air to the primer inlet An internal valve to the fire pump is opened with air pressure from the chassis air brake system when the button is depressed Vacuum for drafting is created by air flowing through multi stage internal venturi nozzles The Primer Control Valve has ...

Page 11: ...for LEFT RIGHT FRONT and REAR remote priming locations as shown in Photo 6 8 See Photos 3 and 4 to note that the cast in arrows on the RPVs and Check Valves are in the proper flow direction Operating Instructions for Multi Location Automatic Priming System 1 See operating instructions for the Auto Priming System on Page 6 for the initial fire pump priming procedures 2 Be sure the AirPrime switch i...

Page 12: ... Min 3 8 Tubing Min Drawing Denotes Two 2 Additional Multi location Priming Points Check Valve Panel Rocker Switch Auto AirPrime Color Key Electric Lines Air Supply Lines Vacuum Priming Lines Multi Location Wiring Harness 3 4 Tubing Min See photo inset lower left corner Open Position Out Figure 16 Color Key 3 4 ID External Flex Line 3 4 ID External Flex Line 3 4 ID External Flex Tubing Merge All H...

Page 13: ...ocation Color Key 3 4 ID External Flex Line to Low Point Drain 1 2 ID Internal Flex Line 3 4 ID External Flex Lines 1 2 or 5 8 ID External Flex Line 1 2 ID Internal Flexible Tubing Priming Line Drain Valve 1 2 or 5 8 ID External Flexible Tubing 3 4 Weld Coupling 3 4 ID External Flex Tubing Merge All High Point Pickups At The Valve Location Higher Than The High Points Fittings In Kit From Outside O...

Page 14: ...an or replace Part 21 002 0 b Automatic AirPrime Remove air supply piping remove air solenoid assembly remove fine mesh filter clean or replace Part 21 002 0 Slight air leak in discharge or intake valves in fire pump plumbing c Hydrostatic test the plumbing system to the NFPA 1901 standard with wet fire pump closed valves 250 PSIG 17 2 Bar for 10 minutes without pressure loss Check the interior ch...

Page 15: ... suction intakes a Remove the MIV and cap intake b Install a cap on the discharge side of the relief valve c Cap the Storz or NH intake Check the AirPrime internal priming valve a The priming valve is not seating in the shut off position remove primer disassemble and check the priming valve spring seat and operation b The priming valve is stuck Check for damaged O Ring or check to see that the pis...

Page 16: ... is performed as follows 1 Set up the apparatus in accordance with the pump test outlined in the NFPA 1901 Standards 2 Engage the pump and increase the throttle to a maximum engine speed of 1000 RPM 3 Operate the AirPrime with the air system over 100 PSIG 7 0 Bar pressure air tanks filled to capacity and at 1000 RPM engine speed For the Manuallly controlled primer release the push button when a di...

Page 17: ...r damage shall in no case exceed the price paid for the product or any part thereof which give rise to claim As always TRIDENT technical assistance and support is available for your convenience 5 Year Warranty For five years after the date of purchase Trident Emergency Products LLC warrants its products to be free from defects in materials and workmanship when properly installed operated and maint...

Page 18: ...Trident Emergency Products LLC 2940 Turnpike Drive Suite 9 Hatboro PA 19040 USA 18 AirPrime Fire Pump Priming System Installation Operation Notes Vehicle Number ...

Page 19: ... 215 293 0700 7 215 293 0701 sales tridentdirect com 19 Installation and Operation Guide Proven Priming Performance Installation Operation Notes Primer Testing Notes ...

Page 20: ...iming Valve RPV 30 035 1 23 1 4 NPT Air Check Valve 30 012 0 24a Remote Priming Valve with 12 Volt Solenoid 30 035 10 24b Remote Priming Valve with 24 Volt Solenoid 30 035 11 25 Multi Location Push Button w Mounting Plate 27 003 9 26a Label Only PRIMER FRONT INTAKE 02 006 5 26b Label Only PRIMER REAR INTAKE 02 006 6 26c Label Only PRIMER LEFT SIDE 02 006 7 26d Label Only PRIMER RIGHT SIDE 02 006 8...

Reviews: