4.3 Behaviour at net recovery
x-touchBOX/PANEL
4 Basic settings
4.3
Behaviour at net recovery
In the
Configuration
menu you can define how the system will behave after a power failure.
–
The
System
tab is open in the
Configuration
menu.
1. Press the
Action at net recovery
button.
= The dialog box
Action at net recovery
is displayed.
2. Activate the desired check box and confirm with
OK
.
4.4
Determining the display name and program version
–
The
Main Menu
is displayed.
1. Press the
Configuration
button.
2. Press the
System
tab.
= The display name and
Program version
are displayed.
3. Press the display name to change it.
= The dialog box
Keyboard
is displayed.
4. Enter the new name and confirm with the
Enter
key.
5. Press the
Esc
button to abort the process.
Function
Action at net recovery
No action
No commands are transmitted.
Broadcast OFF
All operating devices are switched off.
Broadcast MAX
All operating devices are set to maximum luminous intensity. Somfy
components are started.
Broadcast MIN
All dimmed operating devices are set to the stored dimming value and all
other devices are set to maximum luminous intensity. Somfy components
are shut down.
Scheduler start
The Scheduler is started. A sequence is restarted, schedule and schedule
list are continued.
Hint
If an Ethernet connection is established you can use the keyboard of your PC or laptop.