background image

TR-B200S-WH, TR-B200S-IV 

Intelligent Sounder Base 

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING

Read System Sensor’s Applications Guide for System Smoke Detectors 
(SPAG91), which provides detailed information on sensor spacing, placement, 
zoning, wiring, and special applications. This manual is available online at 
www.systemsensor.com. NFPA 72 and NEMA guidelines should be observed.

NOTE: Triga series sounder bases are not compatible with remote test capable 
Triga series detectors.

NOTICE: 

This manual should be left with the owner/user of this equipment.

IMPORTANT: 

The detector used with this base must be tested and maintained 

regularly following NFPA 72 requirements. The detector should be cleaned at 
least once a year.

GENERAL DESCRIPTION

The TR-B200S-WH and TR-B200S-IV sounder bases are used with addressable 
detector heads. Refer to the appropriate manual for more information on sen-
sors.

The TR-B200S-WH and TR-B200S-IV sounder bases were designed specifically 
to meet the needs of dwelling unit applications. They offer maximum flex-
ibility in configuration and operation to meet or exceed the requirements of 
UL268 and UL464.

The sounder base is capable of producing a variety of tone patterns, includ-
ing the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm 
signal now required by NFPA 72 for commercial and residential applications.

The TR-B200S-WH/TR-B200S-IV can be commanded by the Fire Alarm Con-
trol Panel to adopt the address of the attached sensor head, but as a unique 
device type on the loop. By using the address, the fire alarm control panel can 
command an individual sounder base to activate, or a group of sounders in 
a suite or other multi-room configuration. The command set from the panel 
can be tailored to the specific event, allowing selection of volume, tone, and 
group. The device offers two volume levels: 75 dBA and 85 dBA. The available 
tones are Continuous, ANSI Temporal 3, ANSI Temporal 4, and March Time. 
In addition, some fire alarm panels will offer the ability to command a custom 
tone pattern. Refer to the appropriate fire alarm control panel manual for more 
information.

In addition, the TR-B200S-WH/TR-B200S-IV is equipped with the circuitry to 
recognize the System Sensor synchronization protocol, enabling the sounder 
base to be used as a component of the general evacuation signal – producing 
an NFPA 72 compliant Temporal 3 pattern in synchronization with other listed 
compatible notification devices. This requires connection to a power supply 
capable of generating the System Sensor synchronization pulses, a FACP NAC 
output configured to System Sensor synchronization protocol, or a separate 
synchronization module. 

SPECIFICATIONS

Base Diameter: 

6.875" (17.46 cm)

Base Height (less sensor): 

2.0" (5.08 cm)

Weight: 

0.50 lb. (227 gm)

Operating Temperature Range:  Refer to the applicable sensor’s operating temperature range provided in the sensor’s installation manual. 
Operating Humidity Range: 

10% to 93% relative humidity (non-condensing)

External Supply Electrical Ratings

External Supply Voltage: 

16 to 33 VDC (VFWR)

Standby Current: 

500 μA maximum

Alarm Current: 

35 mA maximum (at high volume setting); 15 mA maximum (at low volume setting)

SLC Electrical Ratings

SLC Operating Voltage: 

15 to 32 VDC

SLC Standby Current: 

300 μA maximum

Sound Output 

High Volume: 

Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet (3.1m), 24 Volts (in continuous tone)

Low Volume: 

Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet (3.1m), 24 Volts (in continuous tone)

The sounder base is intended for use with intelligent systems. In addition to 
being connected to the SLC, the sounder base requires a connection to either 
24 VDC constant power or a NAC circuit, depending on the FACP and intended 
use. The connections for 24V constant/NAC power and the communication 
loop are isolated to prevent electrical interaction between them. 
When connected to a NAC, power is supervised via the NAC circuit supervi-
sion while in standby mode (EOL resistor required for Class B operation). 
When activated, the TR-B200S-WH/TR-B200S-IV provides supervision of NAC 
power. (See Figure 5.) 
When using a FACP equipped with a “sounder base standby power monitor-
ing” mode and constant 24 V power, power supervision EOL devices (super-
vision relays and resistors) should not be used. (See Figure 4.) In this case, 
the TR-B200S-WH/TR-B200S-IV will provide supervision in both standby and 
alarm/active mode. Refer to FACP installation documentation to determine if 
this mode is available. If your FACP does not support this mode or you choose 
not to use it, power supervision relays and EOL resistors are required to pro-
vide supervision in standby mode.

NOTE: 

If the FACP’s “sounder base standby power monitoring” mode is en-

abled, connecting TR-B200S-WH/TR-B200S-IV sounder bases to the NAC 
will result in power supervision failure when in standby. Only connect 
TR-B200S-WH/TR-B200S-IV sounder bases to constant 24 V power in this 
case. Refer to the panel manual for maximum allowable number of units per 
loop.

NOTE: 

For NFPA 72 Installations, the Temporal 3 tone at high volume should 

be used for public mode evacuation. The use of other tone styles and low 
volume level will be at the discretion of the local Authority Having Jurisdic-
tion (AHJ).

NOTE: 

When not used as a supplementary evacuation system, the external 

24 VDC supply shall be treated as a component of the main power supply 
system and shall fall under the requirements of the main power supply system 
per NFPA 72.

WIRING GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction and must not be of such length or wire 
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and 
accessory devices should be color coded to reduce the likelihood of wiring 
errors. Improper connections can prevent a system from responding properly 
in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm2) may be used with the base. The sounder 
base will be shipped with the screw terminals set for 14 AWG wiring. If 
12 AWG wire is to be used, back out the screws to allow the wire to fit beneath 

I56-3387TRG-009

This model is compatible with Sytem Sensor Models MDL, MDL3R, MDLW, MDL3W and SYNC-1

TRIGA Life Safety Systems, LLC

7600 Olde Eight Rd.

Hudson, Ohio 4426-1057

Tel: +1 330-577-5199. Email: info@trigaglobal.com 

  

I56-3387TRG-009 

 

 4/22/2021

Summary of Contents for TR-B200S-WH

Page 1: ...gh volume setting 15 mA maximum at low volume setting SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum Sound Output High Volume Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone Low Volume Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone The s...

Page 2: ... the base without the use of a tool To activate this feature break the tab from the detector base as shown in Figure 7A Then install the detector To remove the detector from the base once the tamper resist feature has been activated insert a small bladed screwdriver into the slot from the top and press down on the lever see Figure 7B This allows the detector to be rotated counterclockwise for remo...

Page 3: ...C NAC OPTIONAL REMOTE ANNUNCIATOR MODEL RA400Z 100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTI...

Page 4: ...l wiring configurations see your sync module manual FACP 1 EOL 1 HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF NAC 1 B B NAC 2 B B NAC 3 B B TO NEXT DEVICE OR EOL 1 TO NEXT DEVICE OR EOL 1 2 STYLE Y ZONES CLASS B MASTER SOUNDER BASE SOUNDER BASE OPTIONAL FIGURE 7B REMOVING THE DETECTOR HEAD FROM THE BASE SLOT SLOT C1082 00 Triga is a trademark...

Reviews: