FIGURE 4.  WIRING DIAGRAM  

(CONNECTED TO 24V POWER USING COMPATIBLE FACP WITH “SOUNDER BASE STANDBY POWER MONITORING” ENABLED)

FIGURE 5. WIRING DIAGRAM (CONNECTED TO NAC OR 24V POWER; OPTIONAL EOL DEVICES FOR CONSTANT SUPERVISION)

(+) SLC

(–) SLC

(–) CONSTANT POWER

(–) NAC

(+) CONSTANT POWER

(+) NAC

U

.L.

 LISTED COMP

ATIBLE

CONTR

OL P

ANEL

OPTIONAL REMOTE

ANNUNCIATOR MODEL

RA400Z/100Z

CLASS A OPTIONAL WIRING

FIRST

SOUNDER

BASE

SECOND

SOUNDER

BASE

LAST

SOUNDER

BASE

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

(+)

(+)

(+)

(–)

(–)

(–)

EOL

A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE
THE SYNCHRONIZATION PULSES  (SEE FIGURE 6)

/

/

HORN

HORN

HORN/STROBE

FIRST

SOUNDER

BASE

SECOND

SOUNDER

BASE

LAST

SOUNDER

BASE

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

(+) SLC

(–) SLC

(–) NAC OR CONSTANT POWER*

(+) NAC OR CONSTANT POWER*

(+) NAC

(–) NAC

OPTIONAL REMOTE

ANNUNCIATOR MODEL

RA400Z/100Z

(+)

(+)

(+)

EOL

A SEPARATE SYNCHRONIZATION MODULE MAY BE 
USED TO PROVIDE THE SYNCHRONIZATION PULSES

HORN

HORN/STROBE

UL LISTED COMP

ATIBLE

CONTR

OL P

ANEL

UL LISTED 24V  PO

WER  SUPPL

*WHEN USING 24V CONSTANT POWER 
(AUX POWER), ADDITIONAL POWER 
SUPERVISION RELAYS AND MODULES WILL
BE REQUIRED FOR PROVIDING SUPERVISION 
WHEN THE SOUNDER BASES ARE INACTIVE.

CLASS A OPTIONAL WIRING

(–)

(–)

(–)

/

/

EOL

/

/

HORN

C0474-24

C0474-25

NOTE: Only use this wiring diagram when connecting to 24VDC power using a FACP listed in the table on page 1. Please consult your FACP manufacturer for 
panel-specific wiring configurations and special cases.

Additional Audible Visible devices may be connected to the same power supply or the the NAC output of the Fire Alarm Control Panel (FACP) to provide a syn-
chronized communication of the alarm signal.

(SEE FIGURE 6)

NOTE: Only use this wiring diagram when connecting to a NAC or a 24V power supply that does not support “sounder base standby power monitoring”  
(see page 1). 

  

I56-3387TRG-009 

 

 4/22/2021

Summary of Contents for TR-B200S-WH

Page 1: ...gh volume setting 15 mA maximum at low volume setting SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum Sound Output High Volume Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone Low Volume Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone The s...

Page 2: ... the base without the use of a tool To activate this feature break the tab from the detector base as shown in Figure 7A Then install the detector To remove the detector from the base once the tamper resist feature has been activated insert a small bladed screwdriver into the slot from the top and press down on the lever see Figure 7B This allows the detector to be rotated counterclockwise for remo...

Page 3: ...C NAC OPTIONAL REMOTE ANNUNCIATOR MODEL RA400Z 100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTI...

Page 4: ...l wiring configurations see your sync module manual FACP 1 EOL 1 HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF NAC 1 B B NAC 2 B B NAC 3 B B TO NEXT DEVICE OR EOL 1 TO NEXT DEVICE OR EOL 1 2 STYLE Y ZONES CLASS B MASTER SOUNDER BASE SOUNDER BASE OPTIONAL FIGURE 7B REMOVING THE DETECTOR HEAD FROM THE BASE SLOT SLOT C1082 00 Triga is a trademark...

Reviews: