23
January, 2021
Cellular communicator G16T_LTE-M
“Module” tab
s
After adding the expander to the communicator as described above, in the
RS485 modules
window a new tab will appear with
this module
’s
settings. The tab will be given a number. Below we describe the settings for
iO-8
expanders, for the WiFi module
W485
, for „Ethernet”
module
E485
.
iO-8 expander settings window
Expander
iO-8
has 8 universal (input/output) terminal contacts. Up to four
iO-8
expanders can be connected.
•
Input Count
–
select what number of terminal contacts should be set to input (IN) mode. The rest of the terminal contacts
will become outputs (OUT).
Outputs are configured directly in
Protegus
app.
In the table inputs can be assigned Contact ID event and restore codes. After an input is triggered, the communicator will send
an event with the set event code to the monitoring station receiver and to
Protegus
app.
Contact ID event code:
•
Enable
–
allow message transmission, when the input is triggered.
•
E/R
–
choose what type of event will be sent when input is triggered
–
Event
or
Restore
.
•
CID
–
assign a Contact ID event code to the input.
•
SIA
- assign a SIA event code to the input.
•
4+2
- assign a 4+2 event code to the input.
•
Part.
–
assign a partition (area) to the input. It is set automatically: if the module no. is 1, then the area is 91; if the module
no. is 4, then the area is 94.
•
Zone
–
set the zone number for the input.
Contact ID restore code
:
•
Enable
–
allow message transmission when the input is restored.
•
E/R
–
choose what type of event will be sent when input is restored
–
Restore
or
Event
.
•
CID
–
assign a Contact ID restore code to the input.
•
SIA
- assign a SIA event code to the input.
•
4+2
- assign a 4+2 event code to the input.
•
Part.
–
assign a partition (area) to the input. It is set automatically: if the module no. is 1, then the area is 91; if the module
no. is 4, then the area is 94.
•
Zone
–
set the zone number for the input.
•
Input type
–
select the type of the input (NO or NC).