Option 2 (if no CAN keypad is connected to network)
1. Remove power from door module.
2. Open up door module enclosure.
3. Move DIP switches 4-6 to the “ON” position.
4. Connect door module to CAN network.
5. Connect power to door module.
6. Wait 5 seconds. The LED will come on solid and then continue to
flash.
7. Press lock button of the first FOB for 2 seconds until LED pattern
changes (fast flash), then release. This synchs the first FOB
transmitter.
8. Press lock FOB button of 2nd FOB for 1 second, until fast LED
flash. This synchs the 2nd FOB transmitter.
9. Repeat step 8 until all FOBs are synched (up to 4 FOBs).
10. Remove power and CAN from door module.
11. Move DIP switches 4-6 to original position and verify DIP switches
1-3 are in proper position.
12. Reassemble enclosure.
13. Reconnect power and CAN to module.
14. Verify that FOBs are synched to the door module and that range
of RF transmission is acceptable.
e-ASK CAN DIP Switch Configurations
DIP Switches 1-3:
The settings of DIP switches 1-3 define the CAN address of the
module. Each door module must have a unique address.
5
Dipswitch
Driver Door
Rear Left
Rear Right
1 Off
Off Off
2 Off
On On
3 Off
Off On
Front Right
Off
Off
On