background image

ComfortDry CD55 & CD90

I n s t a l l a t i o n ,   O p e r a t i o n ,   a n d   M a i n t e n a n c e   M a n u a l

www.trioniaq.com

5

Step 1: Placement of the Dehumidifier Unit

IMPORTANT: If the dehumidifier unit is handled in 

such a manner that the compressor did not remain 

in the upright position, it is necessary to place on 

a level surface and wait a minimum of two hours 

before turning the unit on.

Additionally,  ComfortDry  dehumidifiers  cannot  sit 

directly on the floor unless the unit condensate drain 

output is feeding directly into a sump pump next to it.

When placing, the dehumidifier units are equipped 

with adjustable feet that can be used along with a 

leveling tool to make sure the dehumidifier rests in 

a completely “level” final state as needed for proper 

operation.

Step 2: Set Up Drain Line

The condensate drain line should be routed to a 

suitable drain to carry the condensate water to the 

outside.  The drain line must flow down without any 

loops, dips, or valleys to the final drain hole.

Recommended Dehumidifier Drain Configuration 

Including a Transition to PVC Pipe

1.  Cut a piece of ¾” OD PVC that is 6” minimum.

2.  Insert PVC into a ¾” elbow, then attach a ¾” OD 

length of PVC to drain.  Keep the length of the 

PVC drain pipe to a minimum and make sure it 

flows down.

3. 

Insert  the  open  end  of  the  dehumidifier 

condensate tubing into the ¾” pipe so that it does 

not extend into the elbow fitting.  For proper flow, 

a minimum downward slope of 1” per 10’ run is 

required.  NOTE: If a proper downward angle is 

not possible, then it is recommended to use an 

external condensate pump configuration.  This 

will require expert installation.

4.  Support the PVC tubing so that it maintains a 

smooth downward flow to drain.

5.  Always test the drain before leaving the 

installation area.

Step 3: Electrical Power Connections

The  dehumidifiers  are  equipped  with  a  3-prong, 

standard 120VAC electrical plug.  Given operation in 

damp and wet environments, and to put safety first, 

the required electrical outlet to be used to connect 

the dehumidifiers should have:

1.  Ground Fault Circuit Interrupter (GFCI)

2.  15 Amp minimum circuit that cannot be shared 

with any other significant load

120VAC may cause serious injury from electric 

shock.  To ensure safety:

1.  Disconnect electrical power before servicing.

2.  Only plug unit into grounded electrical circuit.

3. 

Do not use extension cord.

4.  Do not use a plug adapter.

Step 4: General Ducting Points and Requirements

In all cases, sound duct design practices must be 

followed, such as those provided in ACCA manual “D” 

of ASHRAE’s 

Fundamentals of Air System Design

.

For supply side air ducting (output from the 

dehumidifier), both the ComfortDry CD55 and CD90 

have 6” round ducts.

For  return  side  ducting,  the  dehumidifiers  are 

equipped as follows:

•  A 12” round collar for the CD90.

•  The CD55 does not include a return duct, as it is 

preferred for standalone operation, which may 

not require ducting.  However, an 8” round collar 

can be ordered separately from TRION and 

requires easy mounting.

For ducting material to use between existing ducts 

or new ducts with the ComfortDry dehumidifiers, it is 

advisable to select an acoustical flex duct material 

WARNING

In all cases, local codes precede over installation 

and wiring recommendations.  Do not plug the 

dehumidifiers into the outlet until all the control 

circuitry is properly connected.

Figure 3. 

Drain Tube Drawing

Summary of Contents for ComfortDry CD55

Page 1: ...T R I O N w w w t r i o n i a q c o m ComfortDry CD55 CD90 Whole House Central Dehumidifiers READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...ce 10 Warranty 11 PLEASE COMPLETE THE FOLLOWING ON DAY OF INSTALLATION HOMEOWNER TO RETAIN FOR FUTURE INFORMATIONAL PURPOSES Unit Model Number _________________________________________________________...

Page 3: ...ually work harder and longer to cool the air when the air is moist Only by using a whole house dehumidifier to reduce the humidity in the entire home s air can a balance between humidity levels temper...

Page 4: ...application the CD55 and CD90 are capable of operating in a complete standalone mode in a ductless configuration that does not require any extra ducting or control system hook ups In SUD mode the CD5...

Page 5: ...condary drain pan MUST be placed under the unit if installed above a living area or above an area where water leakage could cause damage see local codes for other requirements 6 DO NOT position the Co...

Page 6: ...ation This will require expert installation 4 Support the PVC tubing so that it maintains a smooth downward flow to drain 5 Always test the drain before leaving the installation area Step 3 Electrical...

Page 7: ...e CD55 will require the duct accessory kit Return Ducting for Whole House Separate Room The return duct length is not overly critical and it is acceptable to provide more than a single return path to...

Page 8: ...r terminals HVAC blower upon a call for dehumidification When ehumidifier will act to turn off the HVAC blower cooling present At that time the HVAC will be controlling the HVAC blower JUMPER WIRE DEH...

Page 9: ...minate red If in Unit Standalone mode press the button a second time and you will hear one beep as the machine shuts down Specially note that there is a one minute fan delay from button push to shutdo...

Page 10: ...t illustrates the unit is configured for Whole House Configuration and not Standalone Mode While in Whole House Configuration the dehumidifier is to be controlled by a separate humidistat Configuratio...

Page 11: ...until the Whole House light turns on which indicates the unit is configured for Whole House Mode of operation After a very brief delay the dehumidifier will switch into the Whole House Mode Step 4 Aft...

Page 12: ...free of material defects in workmanship or materials for a period of five years following the date of initial purchase of such Product by a Customer from TRION or an authorized TRION reseller Limitati...

Page 13: ...rranty period Warranty service must be performed by TRION or a servicer authorized by TRION In order to obtain warranty service the Customer should call TRION at 1 800 884 0002 and ask for the TRION P...

Page 14: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2016 All Rights Reserved Form No 268513 001 Rev 10 16...

Reviews: