Grease Viper

6

I n s t a l l a t i o n ,   O p e r a t i o n ,   a n d   S e r v i c e   M a n u a l

Unless  otherwise  specified,  the  water  wash  supply 

should be hot 

(140°F recommended - WATER 

HEATER NOT SUPPLIED BY TRION

®

)

 at the volume 

specified for the given unit, and at a full flow pressure 

between 40 and 50 psig measured at header.

Although not required, a pressure gage and a manual 

service valve are recommended as shown in the 

plumbing schematic (separate from this manual). The 

components should be located within the system to 

provide for service access.

7.   Mount Control Panel

The control panel should be mounted indoors (unless 

supplied with a weatherproof enclosure), at eye 

level, and located as close to the ESP as practical. 

Allow  sufficient  space  in  front  of  the  access  door(s) 

for service. Refer to appropriate control panel outline 

drawing for mounting hole layout and dimensions.

8.   Complete Wiring

a.   

Primary Wiring

: The control panel is the main 

distribution point for all primary wiring. The various 

electrical components involved are connected to 

and powered from the control panel.

b.   

Grounding

: An earth ground must be provided 

to the Grease Viper cabinet and control panel. All 

ground connections must be in contact with bare 

metal and securely affixed. Ground conductor size 

and connection means will be in accordance with 

all applicable electrical code standards.

WARNING

Precautions should be taken in the event the water 

supply, detergent piping, and drains are subjected to 

freezing temperatures: 1) All plumbing components 

– backflow preventer, ‘Y’ strainer, pressure gauge, 

solenoid valve(s), detergent system, drain valve, 

and  air  gap  fitting  -  must  be  installed  indoors  or 

in a heated mechanical room in accordance with 

the plumbing schematic to prevent freezing. 2) All 

piping exposed to cold climate outdoor conditions 

should be heat traced and insulated to prevent 

freezing. 3) An air gap fitting should be installed on 

the drain line to facilitate gravity draining of wash 

water from the internal headers and manifolds. 

4) The water supply line should be pitched back 

toward the heated space.

9.   Check Out for System Start-up

When the installation has been completed, assure 

that the equipment is ready for start-up by checking 

the following:

•  All construction debris has been removed from the 

ionizing-collecting cells, drain basin and ductwork.

•  The inside of the control panel and detergent tank 

are clear of any foreign materials.

•  The drain lines from the Grease Viper drain basins 

are clear and completely connected to their point 

of termination.

•  All piping is completed to the manifold headers 

and wash water is available.

•  Supply line power is available and electrical wiring 

is completed to the following components:

a.   Control Panel

b.   Solenoid Valve(s)

c.   Detergent Pump Motor

d.   Electrical Interlocks

e.   Power Supplies for Ionizing-Collecting Cells

f.    Exhaust Fan

FOR THE MAINTENANCE ENGINEER

1.   Introduction and Principle of Operation

The TRION

®

 electronic air cleaner is technically known 

as an Electrostatic Precipitator (ESP). In this type of 

equipment, all airborne particles, even of microscopic 

size, are electrically charged (positively) as they 

pass through a high voltage ionizer. These charged 

NOTE

Do not add the initial supply of detergent into the 

detergent tank - this is to be done after volume 

settings are adjusted at start-up.

Operation & Service

WARNING

RISK OF ELECTRIC SHOCK

These servicing instructions are for use by 

qualified  personnel  only.  To  reduce  the  risk  of 

electric shock, do not perform any servicing other 

than that contained in the operating instructions 

unless you are qualified to do so.

Summary of Contents for Grease Viper Series

Page 1: ...T R I O N w w w t r i o n i a q c o m Grease Viper Series Electrostatic Precipitators Commercial Industrial Applications READ AND SAVE THESE INSTRUCTIONS ...

Page 2: ...or 1 Unpack and Inspect 4 2 Position Air Cleaner Cabinet 5 3 Connect Adjoining Ductwork 5 4 MountDetergentSystem 5 5 Connect Drain 5 6 Connect Water Wash Supply 5 7 MountControlPanel 6 8 Complete Wiring a Primary Wiring 6 b Grounding 6 9 Checkout for System Start up 6 Section 3 Operation Service For the Maintenance Engineer 1 Introduction and Principle of Operation 6 2 General Description 7 3 Init...

Page 3: ...reactivated carbon Gasketed access doors located on one side of the cabinet 90 degrees to the direction of the airflow provide entry for removal of the cells and filters The location of the access doors may be specified as right hand or left hand access determined by facing the inlet of the ESP dirty airflow at your back The solid state high voltage power supplies are factory installed and wired w...

Page 4: ...nit and detergent system Where applicable all water lines must be protected from freezing SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of operating personnel Any additional access that may be provided in the system where there is access to high voltage must be equipped with such interlocks Interlocks are readil...

Page 5: ... pan supply through the floor The recommended drain line trap to seal off the cabinet from the drain against the system pressure and the drain dump valve should be located in the heated interior If not installed in this manner heat trace or other means should be employed to prevent freezing Clean outs are recommended to be installed in all drain lines Wash Water Supply Line The length of the wash ...

Page 6: ...emperatures must be considered see detailed Warning on Page 6 cabinet then re install the ionizing collecting cells and all other filters When the ionizing collecting cells are reinstalled the directional arrows on the cell end plates must concur with airflow direction through the cabinet Impinger prefilters are to be installed within the inlet plenum section on the air entering side of the unit 4...

Page 7: ...n accordance with the plumbing schematic to prevent freezing 2 All piping exposed to cold climate outdoor conditions should be heat traced and insulated to prevent freezing 3 An air gap fitting should be installed on the drain line to facilitate gravity draining of wash water from the internal headers and manifolds 4 The water supply line should be pitched back toward the heated space 9 Check Out ...

Page 8: ...s On multi cell units all of the electrical connections between cells in a given tier are automatically made through spring plunger connectors Install cells into the cabinet in accordance with the directional arrows on the cell end plates The side of the cell containing the spiked ionizer blades must always be located on the air entering side The spring plunger connectors located on one end of eac...

Page 9: ...in the drain basin for any restrictions The ducting where secured to the cabinet collars should be sealed water tight either with gasketing or caulking 2 Inspect the ionizing collecting cells to see that all of the ionizing blades are intact that no large pieces of foreign material are lodged between the plates and that the cells are properly installed in the cabinet with the spiked ionizing blade...

Page 10: ...ion is only effective when timer is running in AUTO mode Temporary Override Condition 1 When timer s output status is ON press MANUAL key to move indicator from AUTO to OFF Timer output shall turn to OFF status programs overrided Press MANUAL again to switch timer status to AUTO Timer s output shall continue maintaining OFF Timer shall resume its automatic operation when next program event calls f...

Page 11: ...he inside of the tank should be kept clean free from dirt and foreign objects The detergent as supplied by TRION is formulated specifically for electronic air cleaners If substitutes are used they must be approved by TRION so as to not void the warranty They should be safe for use in ventilation systems and non caustic as 95 of the ionizing collecting cells are constructed of aluminum special high...

Page 12: ... or cleaning shall be maintained on the premises WARNING RISK OF ELECTRIC SHOCK These servicing instructions are for use by qualified personnel only To reduce the risk of electric shock do not perform any servicing other than that contained in the operating instructions unless you are qualified to do so NOTE All repairs to the fire suppression system if supplied must be completed by the authorized...

Page 13: ...h voltage power supply s is 12 000 VDC and up to 8 MA When the power supply s is de energized there is a 20 second delay for the voltage to decay Always short from ground to a point of high voltage with a well insulated jumper wire or an insulated handled screwdriver to bleed off any remaining residual charge NOTE It will be necessary to close the access door electrical interlock switch operated b...

Page 14: ... indicating light Replace light d Malfunctions other than short or open circuits refer to the Troubleshooting Reference Chart below Problem Symptom Probable Cause Location Reason Correction Indicating Light Not Glowing Short Circuit Ionizing Section of Cell 1 Dirty Insulator s Clean 2 Defective Insulator s Replace 3 Foreign Object between Spiked Ionizer and Ground Electrode Remove Collecting Secti...

Page 15: ...on and Buyer s sole and exclusive remedy for any breach of this warranty repair or replace reperform the Goods which gave rise to the breach or at Seller option refund the amounts paid by Buyer for the Goods which gave rise to the breach Any repair replacement or reperformance by Seller hereunder shall not extend the applicable Warranty Period The parties shall mutually agree on the specifications...

Page 16: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2017 All Rights Reserved Form No 266206 001 Rev 09 17 ...

Reviews: