7. UPS Operation
7.3 Maintenance Bypass Operation
Follow the below steps to transfer to maintenance bypass for power stage maintenance and UPS protection.
7.3.1 Transfer Critical Load from Line Mode to Maintenance Bypass
Confirm Bypass Mode is enabled via the LCD display menu prior to performing the Maintenance Bypass procedure.
Step 1
Remove the mechanical locking plate securing the Q4 Maintenance Bypass breaker (all models).
Step 2
Confirm the UPS is operating in Bypass Mode.
Step 3
Turn ON the Q4 Maintenance Bypass breaker (all models).
Q4
Maintenance Bypass
Q4
Maintenance Bypass
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/120 kVA) Models
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
Q4
Maintenance Bypass
ON
OFF
Q4
Maintenance Bypass
ON
OFF
2018/01/01
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/120 kVA) Models