DIP SWITCH GROUP B

(Available on Select Models)

LOAD SHARING/EQUALIZE BATTERY CHARGE

Using a small tool, set the “Load Sharing” Configuration DIP Switches, #1 and #2 of Group B
(located on the front panel of your APS; see Diagram 1, p. 36). DIP Switch #3, Group B should
be kept in the “UP” position when you are not equalizing your batteries' charges. DIP Switch #4,
Group B has no function.

• Load Sharing 

(DIP Switches #1, Group B & #2, Group B)

Your APS features a high-output battery charger that can draw a significant amount of power
from your line power source when charging at its maximum rate. If an APS is supplying its
full AC power rating to its connected load at the same time as it is charging, it could trip its
line source circuit breaker. Tripping this breaker will cut off AC power to your load and stop
battery charging.

To reduce the chance of tripping this breaker, select APS models may be set to automatically
limit their charger output to keep the sum of their AC load and charger power within their circuit
breakers’ rating.

This charger limiting function has four settings, allowing you to choose less charger limiting
for APS configurations with higher rated breakers. The figures below show how to set your
DIP Switches to select how heavy a load can be placed on your APS before charger limiting begins.

Configuration

continued

4

3

2

1

4

3

2

1

4

3

2

1

4

3

2

1

Battery Charger Limiting Points

MOST LIMITING (#1 & #2 Up*):

Charger limiting takes effect the

moment any load is applied; charger output falls gradually from full
output at no load to no output at full load. 

LESS LIMITING (#1 Down & #2 Up):

Charger limiting begins

when the APS’s load reaches 33% of the APS’s load rating. Charger
output falls gradually from full output at 33% of the APS’s load rating
to about 40% of full output at full load

LEAST LIMITING

(

#1 Up & #2 Down):

Charger limiting begins at

when the APS’s load reaches 66% of the APS’s load rating. Charger
output falls gradually from full output at 66% of the APS’s load rating
to about 40% of full output at full load.

NO LIMITING (#1 & #2 Down):

No charger limiting occurs at any

load size. 

* Factory default setting.

200106010 230V APS Owners Manual.qxd  1/3/02  5:18 PM  Page 6

Summary of Contents for 93-2007 (200106010)

Page 1: ...Instructions 4 Configuration Connection 5 Features 11 Maintenance and Service 14 PowerVerter is a registered trademark of Tripp Lite All rights reserved APS PowerVerter Alternative Power Sources 230V...

Page 2: ...attery charge decreases Automatic Overload Protection If you overload your APS it will automatically protect itself and your valuable batteries from damage Fast Load Switching Your APS provides an uni...

Page 3: ...osting or cutting the voltage to keep your equipment running through brownouts and overvoltages without draining battery power Load Sharing Select models only Select APS models can be set to limit the...

Page 4: ...al battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC input terminals Do not short or bridge these terminals together Serious injur...

Page 5: ...To Battery Point DIP Switch 2 Group A Voltage Switch Position 264V Up 259V Down Select Low AC Voltage Switch To Battery Point DIP Switches 4 Group A 3 Group A Voltage Switch Postion 201V 4 Up 3 Up 182...

Page 6: ...heir AC load and charger power within their circuit breakers rating This charger limiting function has four settings allowing you to choose less charger limiting for APS configurations with higher rat...

Page 7: ...mit Battery Charger DIP Switch 4 Group B APSINT1524 only To prevent overheating smaller batteries the charger on this UPS system is initially set to deliver only a fraction of its maximum power rating...

Page 8: ...Hour ratings of batteries are usually given for a 20 hour discharge rate Actual Amp Hour capacities are less when batteries are discharged at faster rates batteries discharged in 55 minutes provide o...

Page 9: ...You must tighten your battery terminals to approximately 4 Newton meters of torque to create an efficient connection and prevent excessive heating Insufficiently tightening terminals could void your P...

Page 10: ...ad your wires through strain reliefs and through the knockouts 3 Connect all input and output ground wires to the input output ground tie point 4 Connect the incoming hot wire to the input hot brown t...

Page 11: ...has shut down due to overload or overheating See Diagrams 9a and 9b p 39 and 40 to locate the following switches indicator lights and other features 1 Operating Mode Switch All models This switch sele...

Page 12: ...a severe overload or overheating If this happens turn Operating Mode Switch OFF Remove the overload and let the unit cool You may then turn the APS ON after it cools 7 CUT BOOST VRI models only These...

Page 13: ...ove some of the load on the APS to prevent overload then wait 1 minute to allow components to cool before resetting the circuit breaker 14 Remote Module Connector All models The front panel of all mod...

Page 14: ...Tripp Lite service center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not...

Page 15: ...e cabling APS charger failure Turn APS OFF Wait 1 minute and switch to AUTO REMOTE If automatic shutdown occurs call Tripp Lite Customer Service All APS Indicator Lights are This is normal if the APS...

Page 16: ...gth 2 ft Acceptance Volts VDC Selectable 14 4 V 14 2 V Wet Gel Float Volts VDC w gel 13 3 V 13 6 V Input Voltage AC 230 V Input Current AC 3 3 A LINE VAC OPERATION Minimum Input AC Volts Selectable 14...

Page 17: ...WIRED MODELS Cont APSINT2424 APSVRI3636 Weight 18 5 Kg 25 6 Kg INVERTER Continuous power 20 C 2400 W 3600 W Surge power 5 seconds 4800 W 7200 W Efficiency Full Load 89 88 Minimum DC Fuse Rating 220A 1...

Page 18: ...ls 3 3 is the output neutral white 3 4 is the output hot black 3 5 is the input output ground tie point 3 6 is the input neutral blue and 3 7 is the input hot brown Refi rase a la secci n Conexiones E...

Page 19: ...Inverter s Nominal Input Voltage See specs Refi rase a la secci n Conexi n de Bater as p gina 26 5 1 representa el fusible X El Voltaje Nominal de Entrada del Inversor del APS Vea las especificaciones...

Page 20: ...Advanced 12VDC Vehicular Battery Connection See Pg 9 8 1 is the alternator 8 2 is a battery isolator 8 3 is the vehicle battery ground 8 4 is an auxiliary vehicle battery 8 5 is the vehicle battery 8...

Page 21: ...Interruptores DIP Todos los modelos 3 Grupo B de Interruptores DIP Modelos selectos nicamente 4 LINE L nea Todos los modelos 5 INV Inversor Todos los modelos 6 LOAD Carga Conectada 8 BATTERY HI MED L...

Page 22: ...Todos los modelos 2 Grupo A de Interruptores DIP Todos los modelos 3 Grupo B de Interruptores DIP Modelos selectos nicamente 4 LINE L nea Todos los modelos 5 INV Inversor Todos los modelos 6 LOAD Car...

Reviews: