14
Features
Outlets:
During normal operation, the outlets
distribute AC power to connected equipment.
Outlet Status LED:
Once the unit is powered on, each outlet individually
ramps up and each Outlet Status LED will illuminate when the associated
outlet is ready to distribute live AC power.
C13
C19
Circuit Breaker (Select Models):
There are 3 Load Banks, each
protected by a circuit breaker. If the connected equipment load exceeds
the Maximum Load Rating for those banks of the PDU, the circuit breaker
will trip. Disconnect excess load and reset the breaker.
Note:
Each breaker comes equipped with a
push-to-reset guard
to prevent
accidental breaker tripping. To turn off the breaker, insert a flathead screwdriver into
the reset slot.
Mounting Brackets:
Use these brackets as an alternate PDU mounting
method.
Mounting Buttons:
Located on the back side of the PDU, the pre-
installed buttons are used for toolless mounting.
Note:
Four additional mounting buttons are included for alternate rack styles.
Push-to-Reset Guard
PDUMVROTATEBRKT Mounting Accessory:
Use these L-shaped
brackets to mount the PDU with its outlets facing the rear of the rack.
LED Configuration
LED Color
Outlet Status
Description
Standard
1
Off
Off
Outlet power is absent
Green
On
Circuit breaker is on – Outlet power is present
Yellow
On
Outlet’s current has exceeded 80% of the outlet current
rating – Outlet power is present
Red
Off
Outlet’s voltage is below the Low Voltage threshold – Outlet
power is absent
Red Flashing
Off
Circuit breaker has tripped – Outlet power is absent
Alternate
Off
Off
Outlet power is absent
Red
On
Circuit breaker is on – Outlet power is present
Red Flashing
On
Outlet’s current has exceeded 80% of the outlet current
rating – Outlet power is present
Green
Off
Outlet is disabled – Outlet power is absent
Green Flashing
Off
Circuit breaker has tripped – Outlet power is absent
1
This is the default configuration.