22
6 Operation
UPS Operating
Voltage
Selectable Options:
100: Inverter voltage setting to 100V
120: Inverter voltage setting to 120V (Default)
127: Inverter voltage setting to 127V
Bypass High Range
Selectable Options:
5: Bypass range setting to 5%
10: Bypass range setting to 10% (Default)
15: Bypass range setting to 15%
20: Bypass range setting to 20%
Bypass Low Range
Selectable Options:
5: Bypass range setting to 5%
10: Bypass range setting to 10%
15: Bypass range setting to 15% (Default)
20: Bypass range setting to 20%
Off Mode Setting
Selectable Options:
On: Off Mode setting to bypass output (Default)
Off: Off Mode setting to no output
For setup procedures, refer to the following:
1. Press the scrolling buttons
for more than 3 seconds to enter Setup Mode.
2. Press the scrolling button
or
for 0.1 second to change the parameter.
3. Press the confirmation button for 0.1 second to confirm the parameter. The LCD will go to the next setup item.
4. In Setup Mode, press the scrolling button
for more than 3 seconds. The LCD will return to the original display.
5. In Setup Mode, if no buttons are pressed for more than 2 minutes, the LCD will exit Setup Mode and return to the original
display.
Buzzer setup can be performed in all operation modes. Other setup actions can only be configured when the UPS is running in
Off Mode.
Note:
Only qualified service personnel can perform setup actions.