8 Internal Battery Replacement
WARNING:
1. Turn off the UPS and cut off the AC source before performing battery/battery pack replacement.
2. A battery can present a risk of electrical shock and high short-circuit current.
3. Servicing of batteries and battery packs should be performed or supervised by qualified service personnel
knowledgeable in batteries, battery packs and all required precautions.
4. Only use the same type of batteries from the same supplier. Never mix old and new batteries or batteries of
different amperages.
5. Keep unauthorized personnel away from batteries and battery packs.
6. The following precautions should be observed before replacement of batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery terminals.
7. Thoroughly read
Battery Precautions
in section
1 Important Safety Instructions
before replacing batteries.
The 1.44kVA and 2kVA UPS contain eight internal batteries.
Model
SU1500LCD1U
SU2000LCD1U
Replacement Battery Number
RBC487-1U
RBC489-1U
1
2
3
1
Remove the four front bezel screws and slowly pull
bezel away from housing to prevent damage to LCD
ribbon cable.
Note:
Do not put your fingers in the gap between the front
plastic panel and the housing.
2
Disconnect the battery cables and remove cover.
3
Pull out the tab to remove the internal batteries.
PULL