9
2 Introduction
2.5 Operation Panel
2.5.1 LED Indicators
LED
Description
Indicates the output status.
1. ON (Green; On or Flashing): UPS AC output receptacles are ON.
A. Green LED ON = Connected equipment is PROTECTED from power failures.
B. Green LED Flashing = Connected equipment is NOT PROTECTED from power failures (To enable protection,
turn the UPS ON).
2. OFF: UPS AC output receptacles are OFF.
Indicates the warning status.
1. ON (Red): The UPS is in failure mode.
2. Flashing (Red): The UPS system’s working conditions are abnormal.
2.5.2 Multi-Function Buttons
Multi-Function Button
Description
The ON button has two functions.
1. Turn On
(Enable Protection / Cold Start):
A. Enable UPS Protection - In Off Mode, press and hold this button for 3 seconds. Release as
you hear one beep. The UPS will turn on in the user-configured protected operating mode
(Auto-Adaptive On-line, ECO, Frequency Conversion/Regulation) and the green output LED
will turn on.
B. Cold Start - As the UPS is completely OFF and unpowered, press and hold this button for
3 seconds. The UPS will turn on in Battery Mode and provide inverter-derived AC output.
2. Battery Test:
• A battery test can only be performed when the UPS is operating in “qUA” (Max-Quality/Online)
or “ECO” (Max-Efficiency) mode.
• For a manual battery test, press and hold the button for 3 seconds. Release it after you hear
one beep. The UPS will transfer to run in Battery Mode and perform a 10-second battery test.
If the test result is okay, the 7-segment display will show ‘PAS’ and the UPS will return to its
original mode of operation. If the test result is abnormal, the 7-segment display will show ‘FAL’,
the no-battery/battery replacement icon (
) will flash and the UPS will return to the same
protected operating mode that preceded the battery test. If the test is canceled or interrupted,
the LCD will display “Abo” and the UPS will return to its original mode of operation.
LED Indicators
LCD Panel
(Including a 7-Segment Display)
Multi-Function
Buttons
Summary of Contents for AG-03A7
Page 94: ...94 ...
Page 95: ...95 ...
Page 96: ...96 1111 W 35th Street Chicago IL 60609 USA tripplite com support 21 06 205 9339C4_RevC ...