SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation
and storage of this product. Failure to heed these warnings may affect the warranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight.
• Operating Temperature: 0°C to 40°C
• Storage Temperature: -15°C to 45°C
• Humidity: 0% to 90% R.H.
• Operating Altitude: 0 m to 2,000 m
• Storage Altitude: 0 m to 3,000 m
• Pollution: PD2
• Overvoltage Category: II for normal mode, I for stored energy mode
• Leave adequate space around all sides of the UPS for proper ventilation.
• Only set the UPS upright on a sturdy flat surface. Do not block fans or ventilation holes, as this will seriously inhibit the unit's
internal cooling and cause product damage not covered under warranty.
UPS Connection Warnings
• Connect your UPS directly to a properly grounded AC power outlet. Do not plug the UPS into itself; this will damage the UPS.
• Do not modify the UPS’s plug, and do not use an adapter that would eliminate the UPS’s ground connection.
• Do not use extension cords to connect the UPS to an AC outlet.
• If the UPS receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade
output.
• The mains socket outlet that supplies the UPS should be easily accessible and located near the UPS.
• For use on a TN power distribution system of input power supply. The UPS stored energy output device provides a TN power
system.
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the
failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this
equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
• Do not connect surge suppressors or extension cords to the output of your UPS. This might damage the UPS and may affect
the surge suppressor and UPS warranties.
• Connect the UPS to an outlet that is adequately protected against excess currents, short circuits and earth faults as part of
the building installation.
Model Number
Agency Series
Number
Dimensions
(H x W x D)
Weight
AC Fuse/Breaker
Output Short-
Circuit Current
SMX1500LCDTA
AG-04F3
205 x 146 x 397 mm
11.2 kg
Fuse: T10AL, 250VAC Approx. 73A Peak
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference,
in which case, the user may be required to take additional measures.
Important Safety Instructions