background image

1

Owner’s Manual

SmartOnline

®

 S3MX 

3-Phase UPS Systems

Models: S3M100KX, S3M120KX, S3M160KX, S3M200KX

Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 3Ø 4-Wire + PE

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

Copyright © 2018 Tripp Lite. All rights reserved.

Summary of Contents for AG-6100

Page 1: ...MX 3 Phase UPS Systems Models S3M100KX S3M120KX S3M160KX S3M200KX Input 220 230 240V Ph N 380 400 415V Ph Ph 3Ø 4 Wire PE 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2018 Tripp Lite All rights reserved ...

Page 2: ...Measurement Screen 24 4 2 5 Setup Screen 26 4 2 6 Information Screen 36 4 2 7 Event Screen 38 4 3 Alarm List 40 4 4 History Record 41 5 Interface and Communication 42 5 1 X1 Temperature Detection Port for 42 External Battery Pack 5 2 X2 Remote EPO Input Port 43 5 3 Other Communication Interfaces 43 6 Operation Principles 44 6 1 UPS Block Diagram 44 6 2 Operation Modes 45 6 2 1 Standby Mode 45 6 2 ...

Page 3: ...models High efficiency performance in AC On line and Battery Standby modes to minimise energy consumption Market leading small size and footprint ECO Mode allows the UPS to operate on bypass in stable utility conditions and immediately transfers to inverter to support the load when the utility input drops below tolerance High output power factor more actual power allows more equipment to be suppor...

Page 4: ...ould access the interior of the UPS after disconnecting utility and DC power Batteries present a risk of electrical shock and burns from high short circuit current Battery connection or replacement should be performed by only qualified service personnel observing proper precautions Turn off the UPS before connecting or disconnecting internal batteries Use tools with insulated handles Do not open t...

Page 5: ...talled by qualified service personnel An appropriate disconnect device such as short circuit backup protection must be provided in the building wiring installation An integral single emergency switching device should be included in the building wiring installation Connect the earth ground before connecting to the building wiring terminal Installation and wiring must be performed in accordance with...

Page 6: ...or cable on the UPS or the building wiring terminals at any time as this will cancel the protective earth of the UPS system In order to fully disconnect the UPS system first press the OFF button then disconnect the mains Ensure no liquid or other foreign objects can enter into the UPS system 2 9 Standards Safety IEC 62040 1 2008 A1 2013 EMI Conducted Emission EN 62040 2 2006 Category C3 Radiated E...

Page 7: ...transportation Notify the carrier and dealer immediately if there is any damage or missing parts Please keep the original packaging in a safe place for future use 1 Use a forklift to move the product to the installed area Make sure the bearing capacity of forklift is sufficient Refer to Figure 3 1 2 Follow the unpacking order in Figure 3 2 to remove carton 1 2 and foams 3 3 Remove two fixing plate...

Page 8: ...8 3 Installation and Setup S3M160KX and S3M200KX Models Figure 3 1B Figure 3 4B Figure 3 5B Figure 3 2B Figure 3 3B 1125 mm 1610 mm 705 mm 1 2 3 4 4 3 1 2 3 ...

Page 9: ...e is any damage or missing parts and accessories Keep the original packaging for future use It is recommended you keep each equipment and battery set in their original packaging as it is designed to provide maximum protection during transportation and storage 3 2 Open Front Panel View Each UPS comes equipped with a front door key The key can be found attached to the front door with a cable tie Upo...

Page 10: ...ription 1 Fan Air enters the power stage through the front grills and is exhausted through the rear of the module Do not block the ventilation vent 2 Stage Address DIP Switches There are three DIP switches for Power Stage address setting In the same cabinet each Power Stage ID MUST be exclusive Refer to Table 3 1 Power Stage ID for more information 3 Battery Start Button When AC input is not avail...

Page 11: ... a second AC input Q2 are also available However the pictures below only reflect single AC Q1 input models The breakers shown are Q1 input Q3 output and Q4 maintenance bypass Output 100KVA 120KVA 160KVA 200KVA Maintenance Bypass Q4 Maintenance Bypass Q4 Maintenance Bypass Q1 Input Q1 Input Q1 Input Q3 Output Q3 Output ...

Page 12: ...tion 1 Output Block Connects to the critical loads Includes R S T and Neutral terminals 2 Main Input Block Connects to main AC source Includes R S T and Neutral terminals 3 Ground Connection For UPS grounding Includes one grounding terminal 4 Battery Input Block Connects to an external battery cabinet Includes Positive Negative and Neutral N terminals 100KVA 120KVA 160KVA 200KVA ...

Page 13: ...wise the receptacle may be shorted and destroyed 2 Switch off the mains in the building before installation 3 Turn off all connected devices before connecting to the UPS 4 Prepare the power cables according to Table 3 2 Refer to Table 3 3 for UPS Input Breaker sizes and Table 3 4 for Battery Cabinet Batteries and Breaker sizes Table 3 2 Power Cables Model Power cable mm2 and AWG Input Ph Output Ph...

Page 14: ...ttery wires according to the function indicated on terminal block Make sure to connect the grounding earth wires first when establishing a wire connection Disconnect the grounding earth wire last when performing wire disconnection Notes Ensure the wires are tightly and securely connected to the terminals This breaker must have leakage current protective function 6 Reattach the terminal block cover...

Page 15: ... the input wires of the other UPS Likewise the length of output wires R S T N must also be in equal length If not it will cause unbalance current on the output load Figure 3 6 Single Input Wiring In Parallel System Maintenance Breaker Output Breaker Input Breaker AC I P 1 Parallel Cable Load Input 2 Input 1 Output Static Switch UPS Module Bat Module Bat Module UPS Module RECT Inv Charger Charger M...

Page 16: ... Breaker Input Breaker AC I P 1 AC I P 2 Parallel Cable Load Input 2 Input 1 Output Static Switch UPS Module Bat Module Bat Module UPS Module RECT Inv Charger Charger Maintenance Breaker Static Switch Output Breaker Input Breaker Input Breaker Input 2 Input 1 Output UPS Module Bat Module Bat Module UPS Module RECT Inv Charger Charger ...

Page 17: ... Installation and Setup 3 6 2 Parallel Board Setting 3 6 2 1 Configure Parallel Board of UPS 1 1 Set SW2 on the parallel board of the UPS 1 to the right side Figure 3 8 SW2 Position on UPS 1 Default Setting ...

Page 18: ...18 3 Installation and Setup 3 6 2 2 Configure Parallel Board of UPS 2 1 Set SW2 on the parallel board of the UPS 2 to the left side Figure 3 9 SW2 Position on UPS 2 ...

Page 19: ...our settings select the Save Setting icon in the General screen of the SETUP page 10 Proceed to set up UPS 2 11 Set up the parallel function through the LCD panel on UPS 2 Enter the PARALLEL menu in the SETUP page refer to section 4 2 5 5 Setup Parallel Screen for more information 12 Enable the UPS Parallel function of UPS 2 ignore the Parallel UPS Cable Loose warning 13 Choose the battery configu...

Page 20: ...1 to 3 6 4 correctly 2 Confirm the input breaker and output breakers of each UPS have been turned ON 3 Turn ON the battery breaker 4 Turn ON the external AC source breaker to apply AC input source to both UPS systems 5 Watch for abnormal event messages on the LCD display refer to section 4 2 7 Event Screen for more information 6 Switch ON the UPS by pressing the power button on the UPS front panel...

Page 21: ...is abnormal Off No input source BYPASS Yellow On Load on Bypass Flashing Input source is abnormal Off Bypass not operating LOAD Green On There is power output for the load Off There is no power output for the load INV Green On Load on inverters Off Inverters not operating unless in ECO Mode BATTERY Red On Load on Battery Flashing Low battery Off Battery converter is normal and battery is charging ...

Page 22: ...tion the main screen will display Figure 4 3 Main Screen The Main Screen is divided into six sections 1 UPS Operation Mode Shows UPS current operation mode and status 2 UPS Flow Chart Shows current flow chart and measurement data 3 Main Menu Touch each icon to enter submenu Refer to Figure 4 4 for menu tree Figure 4 4 Menu Tree 4 UPS Power Rating Shows UPS power rating 5 Date and Time Shows curren...

Page 23: ... Mode or ECO Mode LINE BYPASS and LOAD On UPS operating in Battery Mode or Battery Test Mode BATT INV and LOAD On UPS operating in Fault Mode FAULT On or Flashing Alarm 4 2 3 Control Screen Touch to enter into the submenu as shown in Figures 4 5 and 4 6 Figure 4 5 Control Screen Figure 4 6 Control Menu System Turn On System Turn Off Manual Battery Test Cancel Battery Test Turn to Bypass Shutdown R...

Page 24: ...rm command or to cancel command Figure 4 7 Confirmation Screen 4 2 4 Measurement Screen Touch to enter into the Measurement submenu You may choose input output bypass load or battery to monitor each detailed status Refer to Figures 4 8 and 4 9 Figure 4 8 Measurement Menu Input Output Bypass Load Battery MEASUREMENT ...

Page 25: ...25 4 Control Panel and LCD Operations Figure 4 9 Measurement Screens INPUT OUTPUT BYPASS LOAD and BATTERY ...

Page 26: ... Remain Time Sec Battery remaining runtime Units 1 sec Capacity The percentage of the battery capacity Units 1 Test Result Battery test result Charging Status Battery charging status Temperature 01 C Temperature of external battery pack Units 0 1 C Temperature 02 C Temperature of external battery pack through extra communication card T1 Units 0 1 C Temperature 03 C Temperature of external battery ...

Page 27: ...ay retry Figure 4 11 Enter Password Screens There are two levels of password protection user password and administrator password The default user password is 0000 It may be changed by the user The administrator password is owned by trained service personnel Different password levels can access different settings The setting can be changed in various operation modes Refer to Table 4 5 for details ...

Page 28: ...estart Y Y Y Y Y Y Y Y Y Cold Start Y Y Y Y Y Y Y Y Y Battery Mode Delay Time Y Y Y Y Y Y Y System Shutdown Time Y Y Y Y Y Y Y Y Y System Restore Time Y Y Y Y Y Y Y Y Y Charger Test Y Y Y Y Y Y Battery Battery Capacity in Ah Y Y Y Y Y Y Y Maximum Charging Current Y Y Y Battery Low Shutdown Setting Y Y Y Y Y Y Y Periodic Battery Test Y Y Y Y Y Y Y Y Y Battery Test Interval Y Y Y Y Y Y Y Y Y Stop by...

Page 29: ...tep 2 Each item will show its current value and alternative settings Step 3 Choose to confirm the change or to cancel any modifications Figure 4 12 Setting Procedure 4 2 5 1 Setup General Screen The Setup General screen and setting list options are shown in Figure 4 13 and Table 4 6 Figure 4 13 Setup General Screen ...

Page 30: ... Set battery installed date yyyy mm dd MUST be set after UPS installation Battery Last Maintain Date Set battery latest maintenance date yyyy mm dd MUST be set after UPS installation Baud Rate Set SNMP Port COM Port0 Baud Rate 2400 Default 4800 9600 Set RS 232 Port COM Port1 Baud Rate 2400 Default 4800 9600 Audible Alarm Set Audible Alarm Disable Enable Default Factory Reset Restore to factory def...

Page 31: ... System Output Voltage Y Bypass Voltage Range Y Y Bypass Frequency Range Y Y Converter Mode Y Y ECO Mode Y Y Bypass Mode Y Y Auto Restart Y Y Cold Start Y Battery Mode Delay Time Y Y System Shutdown Time Y Y System Restore Time Y Y Charger Test Battery Battery Capacity in Ah Y Y Maximum Charging Current Y Y Battery Low Shutdown Setting Y Y Periodic Battery Test Y Y Battery Test Interval Y Y Stop b...

Page 32: ...40V AC MUST be reviewed after UPS installation BYPASS SETTING Bypass Voltage Range Set bypass voltage range Upper limit 10 15 Default 20 Lower limit 10 20 Default 30 Bypass Frequency Range Set bypass Frequency range Upper Lower limit 1Hz 2Hz 4Hz Default Converter Mode Set Converter Mode Disable Default Enable ECO Mode Set ECO Mode Disable Default Enable Bypass Mode Set Bypass Mode Disable Enable D...

Page 33: ...s in Battery Mode for the set number of seconds Shutdown Restore System Shutdown Time Set system shutdown time 0 2 99 min 0 2 min Default This delay time will start counting when the CONTROL Shutdown Restore command is executed System Restore Time Set system restore time 0 9999 min 1 min Default This delay time will start counting after shutdown time is elapsed when the CONTROL Shutdown Restore co...

Page 34: ...Test Periodic Battery Test Set periodic battery test disable or enable Disable Default Enable Battery Test Interval Set battery test interval 7 99 Days 30 Days Default Stop by Time Set testing time for battery test 10 1000 Seconds 10 sec Default Stop by Battery Voltage Set stop battery voltage in battery test 11 12V x Battery Number 11V x Battery Number Default Stop by Battery Capacity Set battery...

Page 35: ... Table 4 10 Setup Pre Alarm Setting List Setting Item Sub Item Explanation Line Voltage Range Set line voltage range Upper limit 5 10 15 20 Default Lower limit 5 10 15 20 Default Line Frequency Range Set line frequency range Upper Lower limit 1 Hz 2 Hz 3 Hz 4 Hz Default Load Set UPS overload percentage 40 100 100 Default Set UPS load unbalance percentage 20 100 100 Default 4 Control Panel and LCD ...

Page 36: ...etting Item Sub Item Explanation UPS Parallel Set UPS Parallel Disable Default Enable Independent Battery Set Independent Battery Disable Default Enable 4 2 6 Information Screen Touch to enter the submenu In this screen you can check the UPS configurations There are three submenus Identification System and Battery Figure 4 19 Information Menu Identification System Battery INFORMATION 4 Control Pan...

Page 37: ...Use the UP and DOWN arrows to switch between pages Figure 4 20 Identification Screen Page 4 2 6 2 INFORMATION System Screen When the System submenu is selected information such as the system power nominal voltage nominal frequency etc will display Use the UP and DOWN arrows to switch between pages Figure 4 21 INFORMATION System Screen Page 1 Figure 4 22 INFORMATION System Screen Page 2 ...

Page 38: ...rging current etc will display Figure 4 23 INFORMATION Battery Screen Page 4 2 7 Event Screen When an event occurs will flash on the main screen You also can touch to check the latest events and history Refer to Figure 4 25 for the menu tree Figure 4 24 Alarm Warning Screen Figure 4 25 Events Menu Current Events History Events Reset All Events EVENTS ...

Page 39: ...nts Detailed event information is saved in HISTORY EVENT Up to 500 events can be saved When a warning occurs it will display the alarm code alarm time and power stage ID refer to section 3 2 Open Front Panel to identify power stage ID When a fault event occurs it will display the alarm description alarm time and power stage ID refer to Table 4 12 In order to record more historical information abou...

Page 40: ...ttery Fault Batteries reversed Fault Over Temperature Make sure adequate space is allowed for air ventilation and that the fan is working Fault CAN Fault CAN communication fault Fault TRIG0 Fault Synchronised trigger signal fault Fault Relay Fault Inverter relay fault Fault Line SCR Fail Line SCR short circuit fault Fault EEPROM Fault EEPROM operation error Fault Parallel Cable Loose Fault As stat...

Page 41: ...Bypass Mode 19 Setup Audible Alarm 20 Setup Auto Restart 21 Setup Factory Reset 22 Setup Cold Start 23 Setup EEPROM Reset 24 Setup Battery Mode Delay Time 25 Setup EPO Function 26 Setup Shutdown Restore Time 27 Setup Save Setting 28 Setup Redundancy 29 Setup Power Rating Setting 30 Setup Charger Test 31 Setup Nominal Battery Voltage 32 Setup Battery Capacity in Ah 33 Setup Maximum Charging Current...

Page 42: ... a battery temperature detection function The UPS can receive a battery temperature signal through the temperature detection thermostat board Communication between the UPS and battery temperature detection thermostat board is via I2C communication protocol X1 is the battery temperature detection port The port is shown in Figure 5 2 and described in Table 5 1 Figure 5 2 Battery Temperature Detectio...

Page 43: ... of X2 are closed Notes 1 EPO function shuts down the rectifiers chargers inverters and static transfer switch but it does not internally disconnect the input power supply 2 The default setting of the EPO function logic is Normal Closed N C 3 A user supplied REPO button must be latching type and in a normally closed position 5 3 Other Communication Interface 5 3 1 RS 232 Port The RS 232 port is lo...

Page 44: ...d on a Different S3MX UPS Model Maintenance Breaker Output Breaker Input Breaker Input 1 Input 2 Output Static Switch UPS Module UPS Module Bat Module Bat Module RECT Inv Charger Charger Maintenance Breaker Output Breaker Input Breaker Input Breaker Input 1 Input 2 Output Static Switch UPS Module UPS Module Bat Module Bat Module RECT Inv Charger Charger ...

Page 45: ...enter Standby Mode if BYPASS is disabled until the UPS is turned on When the UPS is powered on in Standby Mode the charger function will be active when the battery is connected The load is not powered under this mode Standby Mode Diagrams Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output Break...

Page 46: ...onverts it into pure stable AC power to power the load Line Mode Diagrams Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output Breaker Rectifier Rectifier Battery Breaker Battery Breaker Inverter Inverter STS STS Load Load Main Main Bypass Single Input Dual Inputs 6 Operation Principles ...

Page 47: ...er The inverter filters the DC power and converts it into pure and stable AC power to power the load Battery Mode Diagrams Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output Breaker Rectifier Rectifier Battery Breaker Battery Breaker Inverter Inverter STS STS Load Load Main Main Bypass Single I...

Page 48: ...y can be set as 50 Hz or 60 Hz After the output frequency is set up the system will automatically disable the bypass function Once the inverter shuts down there is no bypass output During converter mode the NORMAL LED indicator NORMAL illuminates green Frequency Conversion Mode Diagram Rectifier Batteries Inverter MAINS LOAD ...

Page 49: ...nsfer the load from the inverter to the bypass source with no interruption If the transference was caused by a recoverable reason the UPS will return to Line Mode once the situation has been resolved Bypass Mode Diagrams 6 Operation Principles Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output ...

Page 50: ...fer the power source from bypass to inverter In order to shorten the transfer time the rectifier and inverter will be operating when the UPS is in ECO Mode ECO Mode Diagrams Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output Breaker Rectifier Rectifier Battery Breaker Battery Breaker Inverter I...

Page 51: ...PS will also enter into a Shutdown Mode When the UPS enters this mode it will shut off the control power of the UPS and rectifier and shut down the charger and inverter Shutdown Mode Diagrams Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output Breaker Rectifier Rectifier Battery Breaker Battery ...

Page 52: ...fore entering the Maintenance Bypass Mode make sure the bypass power source is available Maintenance Bypass Mode Diagrams Q4 Maintenance Breaker Q4 Maintenance Breaker Q1 Input Breaker Q1 Input Breaker Q2 Bypass Breaker Inverter Relay Inverter Relay Q3 Output Breaker Q3 Output Breaker Rectifier Rectifier Battery Breaker Battery Breaker Inverter Inverter STS STS Load Load Main Main Bypass Single In...

Page 53: ...sure all breakers are switched OFF 7 1 AC Startup Use the following procedures when turning on the UPS from a fully powered down state Step 1 Apply utility power to the UPS Step 2 Turn ON the battery breaker external battery cabinet Step 3 Turn ON the Input breaker Q1 Step 4 Wait one minute The LCD panel is displayed as shown below The UPS will enter Bypass Mode if the setting of Bypass Mode is en...

Page 54: ...rning or fault event please refer to 8 Troubleshooting to resolve the issue Step 6 Turn ON the Output breaker Q3 Step 7 Press the Power ON OFF button for two seconds until a beep is heard then release to start the inverter Step 8 The UPS is now in Line Mode AC startup is now complete Power On Off button ...

Page 55: ... stages to start up the control power Step 3 After pressing the Battery Start button the UPS will display the initialization screen Step 4 While the UPS is displaying the Online screen immediately press the Power On Off button for 2 seconds until a beep is heard then release to start the inverter Power On Off button Battery Start Button ...

Page 56: ... will enter Battery Mode Step 6 Switch ON the output breaker Q3 The cold start startup procedure is complete Step 7 Turn on the Input Breaker Q1 when utility power is restored and verified OK 7 UPS Operation 2018 01 01 ...

Page 57: ...e securing the switch S3M100KX model or Q4 Maintenance Bypass breaker S3M120KX S3M160KX and S3M300KX models Step 2 Confirm the UPS is operating in Bypass Mode Step 3 Rotate switch to BYPASS S3M100KX model or Turn ON the Q4 Maintenance Bypass breaker S3M120KX S3M160KX and S3M300KX models Step 4 Turn OFF the Q3 Output breaker Q4 Maintenance Bypass Q4 Maintenance Bypass S3M100KX 100 kVA S3M120KX 120 ...

Page 58: ...reaker Step 6 The UPS will enter Shutdown Mode and will slowly de energize After the UPS powers off turn OFF the battery breaker ex ternal battery cabinet Step 7 The critical load is now supported in Maintenance Bypass Mode 7 UPS Operation Q1 Input 1 Q1 Input 1 Q3 Output Q2 Input 2 Q2 Input 2 S3M160KX S3M300KX 160 kVA 200 kVA Models S3M100KX S3M120KX 100 kVA 200 kVA Models Q1 Input 1 Q1 Input 1 S3...

Page 59: ...reaker 160KVA 200KVA Step 3 Go to the LCD INFORMATION Menu Choose SYSTEM to ensure that Bypass Mode is enabled Power By Bypass If Bypass Mode is disabled set it to enabled through the SETUP menu and confirm the UPS is operating in Bypass Mode before proceeding Step 4 Proceed to Step 5 Turn ON the Q3 Output breaker S3M160KX S3M300KX 160 kVA 200 kVA Models S3M100KX S3M120KX 100 kVA 200 kVA Models S3...

Page 60: ...X S3M160KX and S3M300KX models Step 7 Press Power ON OFF button for 2 seconds until a beep is heard then release to start the inverter Step 8 The critical load is now supported in Line Mode 7 UPS Operation ON OFF ON OFF Q4 Maintenance Bypass Q4 Maintenance Bypass Q4 Maintenance Bypass Q4 Maintenance Bypass S3M160KX S3M300KX 160 kVA 200 kVA S3M160KX S3M300KX 160 kVA 200 kVA S3M100KX 100 kVA S3M100K...

Page 61: ...ing in Line Mode Step 1 Press the Power On Off button for 2 seconds until a beep is heard to turn off the UPS or use the Menu Control System Turn Off to turn off the UPS After turning off the UPS the UPS will tranfer to Standby Mode or Bypass Mode depending on the Bypass Mode setting 7 UPS Operation Power On Off button ...

Page 62: ...abled Step 1 Turn off the Output Breaker Q3 Bypass Mode Setting is Enabled Step 2 Turn off the Input Breaker Q1 UPS enters Shutdown Mode Step 3 The UPS will enter Shutdown Mode and slowly de energize Wait until the LCD is OFF Step 4 After the UPS powers off switch OFF the external power switch to disconnect the AC power to the UPS Step 5 If the UPS will remain disconnected from the AC power for an...

Page 63: ...re when the UPS is operating in Battery Mode Step 1 Press the Power On Off button for 2 seconds to turn off the UPS or use the Menu Control System Turn Off to turn off the UPS After turning off the UPS the UPS will transfer to Standby Mode 7 UPS Operation Power On Off button ...

Page 64: ...some load Fault Battery Fault Battery reverse Check the polarity of battery connection and contact service personnel Fault Over Temperature Make sure adequate space is allowed for air vents and the fan is working Check if the ambient temperature is over specification or contact service personnel Fault CAN Fault CAN communication fault Contact service personnel Fault TRIG0 Fault Synchronised trigge...

Page 65: ...stem is correct Warning Parallel Sys Config Wrong Parallel System Configure error Contact service personnel Warning Maintenance Bypass Enter maintenance Check if the connector is loose when it acts abnormally Warning Battery Age Alert Battery Life expiration Check if the battery has been used over its service age or contact service personnel Warning Parallel UPS Cable Loosen As stated Check if the...

Page 66: ...rdous voltages may occur between the battery terminals and the ground Batteries may cause electric shock and have a high short circuit current Remove all wristwatches rings and other metal personal objects before maintenance or repair and only use tools with insulated grips and handles for maintenance or repair When replacing the batteries install the same number and same type of batteries Do not ...

Page 67: ...n 150 200 ms Overload Battery Mode Up to 110 1 hr Up to 125 10 min Up to 150 1 min 150 200 ms Current Crest Ratio 3 1 Maximum Harmonic Distortion 100 Load 2 THD Linear Load 4 THD Non Linear Load Transfer Time Line Battery 0 ms Transfer Time Inverter Bypass Synchronous 0 ms Asynchronous 1 cycle Transfer Time Inverter ECO 20 ms BYPASS INPUT Nominal Voltage Ph Ph 380V 400V 415V Phase 3 Phase with Neu...

Page 68: ...re and diagnose the UPS from the display Contact Closure Interface Requires Optional RELAYCARDSV Programmable Relay I O Card Remote Emergency Power Off REPO Feature Included Default Normally Closed RS 232 Included Service Only STANDARDS Safety IEC 62040 1 2008 A1 2013 TUV Approval EMC EMI EN 62040 2 2006 Category C3 TUV Approval Ingress Protection Rating IP20 CE Marking Yes RoHS Compliant Yes Qual...

Page 69: ...luded Dimmensions H x W x D mm Description BP480V100 400A 3 Pole 1501 x 826 x 1136 Battery Cabinet with 40 x 100Ah batteries BP480V100 NIB Battery Cabinet without batteries but designed for 40 x 100Ah batteries includes battery cabling and breaker BP480V65 300A 3 Pole Battery Cabinet with 40 x 65Ah batteries BP480V65 NIB Battery Cabinet without batteries but designed for 40 x 65Ah batteries includ...

Page 70: ...N THE WARRANTY EXPRESSLY SET FORTH HEREIN EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW ALL IMPLIED WARRANTIES INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES Some states do not allow limitations on how long an implied warranty lasts and some state...

Page 71: ...71 ...

Page 72: ...72 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 17 11 296 93 37D8_RevA ...

Reviews: