Buttons (Front Panel)

Basic Operation

 

Use the 

POWER

 button to switch your UPS between its four modes of operation.

 OFF: 

No indicator lights are on. The UPS is completely shut down for storage or shipping. If the UPS is connected to AC 

power, it will start up in 

STANDB

Y mode. If the UPS is not connected to AC power and the 

POWER

 button is pressed for two 

seconds, the UPS will “cold start” into

 INVERT

 mode.

 STANDBY: 

The “ ” light is flashing. The UPS is receiving AC power and using it to charge its batteries, but its outlets are not 

active. Pressing the 

POWER

 button while the UPS is in 

STANDBY

 will put the UPS in the ON mode. Unplugging the UPS or 

cutting AC power while the UPS is in 

STANDBY

 will put the UPS in the 

OFF 

mode.

 ON:

 The “ ” light is on. The UPS is receiving AC power, charging its batteries and delivering power to connected equipment. 

If AC power is lost while the UPS is 

ON

 (i.e. a blackout occurs), the UPS will switch into 

INVERT

 mode. Pressing the 

POWER

 

button while the UPS is 

ON 

will put the UPS in 

STANDBY

 mode. 

 INVERT:

 The “

” light is flashing. The UPS is powering connected equipment from battery backup. If AC power is restored, 

the UPS will switch to the 

ON

 mode. Pressing the 

POWER

 button while the UPS is in 

INVERT

 will put the UPS into the 

OFF

 

mode. If the UPS is in 

INVERT

 and its batteries are drained, the UPS will switch to the 

OFF

 mode until AC power is restored, 

then switch to the 

ON

 mode.

 Use  the 

MUTE/TEST

 button to do two things:

SILENCE ALARM:

 Your UPS has three alarms. The first, the 

INVERT

 alarm, emits four short beeps every ten seconds when 

the UPS is in 

INVERT

 mode, to warn you that AC power has failed. The second, the 

OVERLOAD

 alarm, emits short, rapid 

beeps when the UPS is in 

INVERT

 mode if the total power draw of connected equipment exceeds the UPS output capacity, 

to warn you to reduce the load. The third, the Low Battery alarm, emits a constant beep when the UPS is in 

INVERT

 mode 

and its batteries are very nearly depleted, to warn you that connected equipment must shut down. To silence the 

INVERT

 

or 

OVERLOAD

 alarms, press the 

MUTE/TEST

 button. The 

LOW BATTERY

 alarm will only stop when the UPS switches to the 

OFF

 or 

ON

 mode. 

SELF-TEST:

 If your UPS is in the 

ON

 mode and has a load connected, you may test its batteries by pressing the 

MUTE/

TEST

 button for two seconds. The UPS will switch to 

INVERT

 mode for several seconds. Normally, the 

INVERT

 alarm (four 

short beeps) will sound, indicating that the system is working properly. If the 

OVERLOAD 

alarm (short, rapid beeps) sounds, 

reduce the load on the UPS. If the 

LOW BATTERY

 alarm (a constant beep) sounds, your UPS batteries may need replacing, 

your external battery connection may be loose or the batteries may simply be less than fully charged. Check the external 
battery connection, let the UPS charge for 12 hours, then perform a second self-test. If the 

LOW BATTERY

 alarm sounds 

again, contact Tripp Lite for service. Do not unplug your UPS to test its batteries, or you will remove safe electrical grounding 

and may introduce a damaging surge into your network connections.

Indicator Lights (Front Panel)

All Indicator Light descriptions apply when the UPS is plugged into a wall outlet and turned ON.

 POWER:

 Lights green when the UPS is receiving AC power. Illuminates constantly when the UPS is in the 

ON

 mode, 

indicating that batteries are charging and connected equipment is receiving filtered AC power. Flashes while in 

STANDBY 

mode to indicate that batteries are charging but connected equipment is not receiving power.

 

VOLTAGE CORRECTION:

 Lights green whenever your UPS is automatically correcting high or low AC line voltage. The UPS 

will also click gently. These are normal, automatic operations of your UPS, and no action is required on your part.

 BATTERY  CHARGE: 

This multicolored light displays 7 separate UPS battery charge conditions. It will turn from red (low) 

to yellow (medium) to green (full) to show you the level of battery charge. If the light is constant, your UPS is in the 

ON

 or 

STANDBY

 mode, operating from line power, and the battery is charging. If the light is flashing, your UPS is in the 

INVERT 

mode, operating from battery, and the battery is discharging. If the light is flashing red, your UPS is in the 

INVERT

 mode and 

is nearly out of power: you should save files and shut down your equipment immediately.

 OUTPUT  LOAD: 

This multicolored light shows how heavy your UPS load is. Steady green indicates a light load, steady 

yellow a medium load. When the light is red, your UPS is supporting a load above 85% of its capacity. If the red light begins 
flashing, then your UPS is severely overloaded. Immediately remove load from the UPS until the light stops flashing.

Summary of Contents for AGBP4860Y3U

Page 1: ...rt Copyright 2021 Tripp Lite All rights reserved SmartPro is a registered trademark of Tripp Lite WARRANTY REGISTRATION Register your product today and be automatically entered to win an ISOBAR surge...

Page 2: ...rs or extension cords to the output of your UPS This might overload the UPS and will void the surge protector and UPS warranties Battery Warnings Batteries can present a risk of electrical shock and b...

Page 3: ...he mounting rails permanently using the included screws and cup washers C as shown Place 6 screws total at the front and 4 screws total at the back Tighten all screws before proceeding Warning Do not...

Page 4: ...input breaker to the ON position towards the left side of the rear panel 3 Plug your UPS line cord into an electrical outlet Once your UPS is plugged in the UPS will enter STANDBY mode The fan will ac...

Page 5: ...plug is disconnected Connection Optional 1 2 3 2 USB Port Connection Using the USB cable provided connect a USB port from a computer to a USB port on your UPS On the computer install the Tripp Lite p...

Page 6: ...may test its batteries by pressing the MUTE TEST button for two seconds The UPS will switch to INVERT mode for several seconds Normally the INVERT alarm four short beeps will sound indicating that th...

Page 7: ...nect the UPS to a DB9 port on any workstation or server Use with Tripp Lite cabling and PowerAlert Software to monitor and manage network power and automatically save open files and shut down equipmen...

Page 8: ...ace it in the OFF mode by reversing the Connection procedure use the POWER button to place the UPS in STANDBY mode unplug the UPS set the double pole input breaker to the OFF position and disconnect t...

Page 9: ...o the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note T...

Page 10: ...10 1111 W 35th Street Chicago IL 60609 USA tripplite com support 21 10 009 932159_RevD...

Page 11: ...ter as AGBP4860Y3U No conveniente para los usos m viles 1111 W 35th Street Chicago IL 60609 USA tripplite com support 2021 Tripp Lite Todos los derechos reservados SmartPro es una marca registrada de...

Page 12: ...de su UPS Esto puede sobrecargar al UPS y anular las garant as del supresor de sobretensiones y del UPS Advertencias Sobre las Bater as Debido a que las bater as presentan un peligro de choque el ctr...

Page 13: ...ermanentemente los entrepa os B a los rieles de instalaci n usando los tornillos y las arandelas de copa C como se muestra Coloque 6 tornillos en total en el frente y 4 tornillos en total en la parte...

Page 14: ...DO hacia el lado izquierdo del panel trasero 3 Enchufe el cable del sistema UPS a una toma el ctrica Una vez conectado el sistema UPS ste se encuentra en modo STANDBY reserva Se activa el ventilador y...

Page 15: ...s Opcionales 1 2 3 2 Conexi n con un puerto USB Con ayuda del cable USB proporcionado conecte un puerto USB de una computadora a un puerto USB de su sistema UPS Instale en la computadora el software d...

Page 16: ...a emite sonidos r pidos y breves para avisarle de la necesidad de reducir la carga La tercera alarma es la de Low Battery bater a baja Cuando el sistema UPS est en modo INVERT y las bater as est n cas...

Page 17: ...exiones USB en su sistema UPS para reiniciar de manera remota el equipo conectado encienda y apague el sistema UPS con ayuda del software PowerAlert de Tripp Lite Para encender y apagar de manera remo...

Page 18: ...de onda presentes en la entrada de CA Cuando se producen dichas distorsiones el sistema UPS normalmente hace un cambio para entregar una alimentaci n sinusoidal pura mediante sus bater as y durante t...

Page 19: ...consecuencial del producto que ocurra durante el env o a Tripp Lite o a un centro de servicio t cnico de Tripp Lite autorizado Los productos enviados a Tripp Lite o a un centro de servicio t cnico de...

Page 20: ...junto con los s mbolos de aprobaci n e informaci n requeridos Al solicitar informaci n sobre el cumplimiento de las normas para este producto siempre mencione el n mero de serie El n mero de serie no...

Page 21: ...es AGBP4860Y3U Non appropri aux applications mobiles 1111 W 35th Street Chicago IL 60609 USA tripplite com support Tripp Lite 2021 Tous droits r serv s SmartPro est une marque d pos e de Tripp Lite Im...

Page 22: ...c de l air de l oxyg ne ou de l oxyde nitreux Ne pas brancher de parasurtenseurs ou de rallonges lectriques la sortie de l onduleur Cela risquerait de surcharger l onduleur et annulerait la garantie d...

Page 23: ...Le rebord du support de chaque tag re doit tre tourn vers l int rieur 2 Retenir les tag res B aux rails de montage de fa on permanente en utilisant les vis et les rondelles collerette incluses C tel...

Page 24: ...entation de votre syst me UPS dans une prise de secteur D s que votre syst me UPS est branch ce dernier se met en mode STANDBY attente Le ventilateur d marre et les voyants se mettent clignoter Les pr...

Page 25: ...2 Connexion du port USB En utilisant le c ble USB fourni reliez le port USB de l ordinateur celui de votre syst me UPS Installez dans l ordinateur le logiciel de protection de l alimentation lectrique...

Page 26: ...on totale du mat riel branch d passe la capacit de sortie de l unit La troisi me l alarme de batterie faible met un signal sonore en continu quand le syst me UPS est en mode INVERT et que ses batterie...

Page 27: ...s rie ou USB votre syst me UPS vous pouvez r initialiser distance le mat riel branch en utilisant le logiciel PowerAlert de Tripp Lite pour allumer ou teindre votre unit Vous pouvez m me s lectionner...

Page 28: ...d une montre pour prot ger le syst me UPS contre la distorsion de l onde d entr e c a Quand une telle distorsion se produit le syst me UPS basculera normalement vers l alimentation de batterie pour fo...

Page 29: ...uctions concernant le transport vous seront achemin es par courriel Tout dommage direct indirect sp cial ou fortuit survenu au produit pendant le transport Tripp Lite ou un centre de service autoris T...

Page 30: ...tion requises Lors d une demande d information de conformit pour ce produit utilisez toujours le num ro de s rie Il ne doit pas tre confondu avec le nom de la marque ou le num ro de mod le du produit...

Page 31: ...31...

Page 32: ...32 1111 W 35th Street Chicago IL 60609 USA tripplite com support 21 10 009 932159_RevD...

Reviews: