H

EXTENDED RUNTIME CHART

Runtime (minutes) with additional external battery packs

Load

Runtime (minutes) with 

Non-Expandable 

Expandable Battery Pack(s)**

(Watts)

included batteries*

Battery Pack

1

2

3

4  

SU750RTXL2U

BP24V28-2U

BP24V70-3U

300

11.0

88.0

224.4

461.7

699.1

933.8

600

4.0

44.1

117.1

249.9

386.3

523.3

SU1000RTXL2Ua BP24V28-2U

BP24V70-3U

400

17.4

77.6

199.6

413.3

628.1

841.1

800

6.0

32.4

87.3

189.1

295.2

402.5

SU1500RTXL2Ua

BP48V24-2U

BP48V60RT3U

600

17.0

80.3

164.6

334.2

506.1

677.5

1200

5.0

33.6

71.3

151.0

234.8

320.2

SU2200RTXL2Ua BP48V24-2U

BP48V60RT3U

800

14.0

56.2

117.0

241.9

370.3

499.3

1600

4.5

23.1

49.7

107.0

168.2

231.2

SU3000RTXL3U & SU3000RTXL3UHV

BP72V15-2U

BP72V28RT-3U

1200

17.0

40.9

77.6

157.8

241.9

327.3

2400

6.0

16.8

32.8

69.1

108.4

149.5

SU3000RTXR3U

BP72V15-2U

BP72V28RT-3U

1200

33.0

58.8

97.1

178.6

263.1

348.8

2400

14.0

24.6

41.5

78.7

118.6

159.9

SU5000RT3U & SU5000RT3UHV

BP240V10RT3U

1740

20.1

N/A

73.1

161.6

225.8

291.0

3500

8.0

N/A

30.6

70.2

100.0

130.9

SU5000RT4U

BP192V12-3U

1740

22.8

N/A

107.9

174.9

243.9

313.8

3750

8.0

N/A

42.5

70.7

100.7

131.7

SU6000RT3U & SU6000RT3UHV

BP240V10RT3U

2100

37.0

N/A

80.0

130.9

183.9

237.9

4200

15.0

N/A

33.4

55.9

80.0

105.1

SU6000RT4U

BP192V12-3U

2100

24.0

N/A

86.6

141.4

198.2

256.0

4200

9.0

N/A

36.8

61.5

87.8

115.2

SU8000RT4U

BP192V12-3U

2800

12.0

N/A

45.8

100.0

141.4

183.8

5600

5.0

N/A

19.0

42.8

61.5

81.1

SU8000RT3U, SU8000RT3U1TF & SU8000RT3UHW

BP240V10RT3U

3200

15.0

N/A

46.0

76.4

108.7

142.0

6400

6.0

N/A

18.6

31.6

45.6

60.4

SU10KRT3U, SU10KRT3UHV, SU10000RT3U & SU10000RT3U2TF

BP240V10RT3U

4000

10.0

N/A

35.1

58.6

83.8

110.0

8000

4.0

N/A

13.7

23.5

34.1

45.3

SU16000RT4U & SU16000RT4UHW

BP192V18-4U

5600

12.0

N/A

42.2

70.2

100.0

130.9

11200

5.0

N/A

17.1

29.2

42.2

55.9

* Included batteries are contained either internally within the UPS system or are offered as an external module, depending on model. ** Battery packs which are "expandable" can be
connected together for increased runtime. 

Fo

r

 additional extended 

r

untime 

solutions to fit you

r

 specific load

r

equi

r

ements, use T

r

ipp Lite's 

inte

r

active UPS Selecto

r

 Guide at

www.t

r

ipplite.com/selecto

r

/ups, 

o

r

 call T

r

ipp Lite's Application 

Specialists at (773) 869-1236.

Extend Runtime

All models accept external

battery packs to provide

extended runtime. Without

enough runtime, businesses

stand to lose up to $50,000 

per hour according to a recent

survey on the cost of lost

productivity for an hour of

network downtime.* Locate

your planned load and optimum

runtime on the chart to 

the right.

* Yankee Group.

Extending runtime is as simple 

as plugging in additional external 

battery packs.

Model

Description

External Battery Packs and Accessories

BP24V28-2U

24V external battery pack and cable, 2U. Not expandable. RED/BLACK 2-point connector.

BP24V70-3U

24V external battery pack and cable, 3U. Expandable. RED/BLACK 2-point connector.

BP48V24-2U

48V external battery pack and cable, 2U. Not expandable. BLUE 2-point connector.

BP48V60RT3U

48V external battery pack and cable, 3U. Expandable. BLUE 2-point connector.

BP72V15-2U

72V external battery pack and cable, 2U. Not expandable. BLACK 3-point connector.

BP72V28RT-3U

72V external battery pack and cable, 3U. Expandable. BLACK 3-point connector.

BP192V12-3U

192V external battery pack and cable, 3U. Expandable. BLACK 3-point connector.

BP192V18-4U

192V external battery pack and cable, 4U. Expandable. YELLOW INSULATED 2-point connector.

BP240V10RT3U

240V external battery pack and cable, 3U. Expandable. BLACK 3-point connector.

SU5000XFMRT2U

2U rack/tower mount isolation transformer. 208V input (L6-30P plug), 100/120V output. Outlets: 12 (5-15/20R) and 1 (L6-30R).

SUPDM56HW

Hardwire PDU. Replaces UPS system's detachable PDU. (for SU5000RT4U, SU6000RT4U models only).

SUPDMB710HW

Hardwire PDU. Replaces UPS system's detachable PDU. (for SU8000RT3U, SU10000RT3U models only). 

SUPDMB16KHW

Hardwire PDU. Replaces UPS system's detachable PDU. (for SU16000KRT4U model only).

SUPDM11

Converts hardwired to L6-30P plug/cord & two L6-30R outlets. 

200/208/240V

(for SU6000RT3UHV model only).

SUPDM12

Converts hardwired to L6-30P plug/cord & 13 outlets: ten 

120V

(5-15/20R), two 

208V

(L6-20R), one 

208V

(L6-30R) (for SU6000RT3U model only).

SUPDM13

Converts hardwired to L6-30P plug/cord & 13 outlets: ten 

120V

(5-15/20R), two 

240V

(L6-20R), one 

240V

(L6-30R) (for SU6000RT3U model only).

SNMPWEBCARD

Internal SNMP/Web management accessory card (connects compatible UPS systems to Ethernet).

ENVIROSENSE

Allows UPS to monitor external temperature/humidity & contact-closure inputs (requires SNMPWEBCARD).

2-9USTAND

Tower kit with 2 adjustable base stands—2U to 9U.  

2POSTRMKITWM

Horizontal mounting rails for 2-post rackmount installation. For all UPS and battery pack models.

Common specifications for all UPS systems: SNMP/Web accessory slot (for use with optional SNMPWEBCARD, sold separately). All models are designed with mounting hardware to fit standard 19 in. racks.

+ Backup times are

expandable using external battery packs. 

(A) 

Optional SU5000XFMRT2U isolation transformer is available to provide 100/120V output. 

(B)

Backup times will vary depending on battery condition and load. 

(C)

Auto-selecting frequency. 

(D)

Includes

customized load management receptacles. 

(E)

Includes phone/DSL/Ethernet surge protection. 

(F)

Includes a single combination RS-232 and contact-closure port. 

(G) 

This model includes an additional 5-15P plug which can be installed in place of the

existing plug. Installing the additional plug will change the output capacity. 

(H)

Converts to ten 5-15/20R, two L6-20R and one L6-30R outlets via optional SUPDM12 or SUPDM13. 

(I)

Converts to L6-30P plug via optional SUPDM12 or SUPDM13. 

(J)

Converts to two L6-30R outlets via optional SUPDM11. 

(K)

Converts to L6-30P plug via optional SUPDM11. 

(L)

Certifications vary by model. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change

without notice. Actual product may differ slightly from photos.

I

Complete, up-to-date specifications (including product weight and dimensions) available at www.tripplite.com

Also available: interactive UPS System selector guide, extended warranties, owner's manuals and more!

200701188-- UPS Brochure.qxd  12/21/2007  11:26 AM  Page 11

Reviews: