background image

UPS Input cord
length (m)

1.83

Recommended
Electrical Service

120V 15A

Maximum Input Amps
(A)

12

Input connection type

NEMA 5-15P

Voltage compatibility
(VAC)

120

BATTERY

DC system voltage
(VDC)

12

Replacement battery
cartridge (internal
UPS battery
replacement)

RBC51

Battery Access

Yes

Full load runtime

3 minutes (1000VA / 500W)

Half load runtime

10 minutes (500VA / 250W)

Typical battery
lifespan

4-6 years (depending on usage)

VOLTAGE REGULATION

Voltage regulation
description

Line-interactive voltage regulation corrects brownouts as low as 89V back to safe values

Brownout correction

Brownouts as low as 89V are boosted by 14%

LEDS ALARMS & SWITCHES

Alarms

Audible alarm indicates loss of utility power. Alarm can be silenced by pressing front panel mute button. Once
silenced, alarm will re-sound when approximately 2 minutes of runtime remain.

Switches

Includes 2 front panel buttons - one main on/off power switch and one dual function mute / self test button. Also
includes dimmer control to adjust the brightness of the LCD status screen.

Front panel LEDs

Front-panel LCD status screen with adjustable blue backlight offers continuous input voltage data, plus UPS status
information on power conditions, battery conditions, battery charge level and voltage regulation operation.

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

1038 joules

EMI / RFI AC noise
suppression

Yes

AC suppression
response time

Instantaneous

Dataline suppression

Phone (Tel/DSL) and Coaxial

PHYSICAL

Shipping Dimensions
(HWD/in)

10.43 x 15.55 x 4.84 (unit carton)

Shipping Dimensions
(HWD/cm)

26.49 x 39.50 x 12.29

Shipping weight (lbs)

15.75