12
Features
Outlets:
During normal operation, the outlets distribute AC power to
connected equipment.
Bank Status LED:
Once the unit is powered on, each Bank Status LED
will illuminate when the associated bank is ready to distribute live AC
power.
LED Color
Bank Status
Comments/Notes
Green
On
Normal operation.
Yellow
On
Bank’s current has exceeded 80% of its current
rating.
Red
Off
Bank’s voltage is below the Low Voltage
threshold.
Red Flashing
Off
Circuit breaker for this bank has tripped.
Off
Off
Bank is powered off.
Note: Colors noted here reflect standard LED configuration. See chart on page 9 for
full LED color definitions.
C13
C19
Circuit Breaker:
Each Load Bank is protected by a circuit breaker. If the
connected equipment load exceeds the Maximum Load Rating for those
banks of the PDU, the circuit breaker will trip. Disconnect excess load and
reset the breaker.
Note: Each breaker comes equipped with a
push-to-reset guard
to prevent
accidental breaker tripping. To turn off the breaker, insert a flathead screwdriver into
the reset slot.
Mounting Brackets:
Use these brackets as an alternate PDU mounting
method.
Mounting Buttons:
Come pre-installed on the back side of the PDU and
are used for toolless mounting.
Note: Four additional mounting buttons are included for alternate rack styles.
Bank Status LED
Push-to-Reset Guard
PDUMVROTATEBRKT Mounting Accessory:
Use these V-shaped
brackets to mount the PDU with its outlets facing the rear of the rack.
14-08-206-93338E.indb 12
10/9/2014 11:31:56 AM