background image

8

Specifications 

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.

Model:

SMART700

SMART750XL

SMART1050

Series:

AGSM1050PJR3

AGSM1500XPSR3

AGSM1050PJR3

Input Voltage/Frequency:

120V/60 Hz

120V/60 Hz

120V/60 Hz

Output Capacity (VA/Watts):

700/600

750/600

1050/800

Battery Runtime
(Half Load/Full Load) Minutes:

20/6

42/18*

23/8

Battery Recharge Time:

2-4 hrs.

2-4 hrs.*

2-4 hrs.

Approvals:

UL, cUL, NOM, FCC B

UL, cUL, NOM, FCC A

UL, cUL, NOM, FCC B

Model:

SMART1050XL

SMART1500

SMART1500XL

Series:

AGSM1500XPSR3

AGSM1500XPSR3

AGSM1500XPSR3

Input Voltage/Frequency:

120V/60 Hz

120V/60 Hz

120V/60 Hz

Output Capacity (VA/Watts):

1050/800

1500/980

1500/980

Battery Runtime
(Half Load/Full Load) Minutes:

26/6*

20/7

20/7*

Battery Recharge Time:

2-4 hrs.*

2-4 hrs.

2-4 hrs.*

Approvals:

UL, cUL, NOM, FCC A

UL, cUL, NOM, FCC A

UL, cUL, NOM, FCC A

*External battery packs can be connected to these models. External battery packs will increase both the battery runtime and

the battery recharge time.

ALL UNITS:

Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds
IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB at 1MHz); AC Protection Modes (H to N, H to G, N to G); Tripp Lite
External Battery Model (BP36V27).

FCC CLASS A RADIO/TV INTERFERENCE NOTICE:

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when operated in a com-
mercial environment. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in
accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must
use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the
party responsible for compliance could void the user's authority to operate the equipment.

FCC CLASS B RADIO/TV INTERFERENCE NOTICE:

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the
instruction manual, may cause interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference using one or more of the
following measures: reorient or relocate the receiving antenna; increase the separation between the equipment and the receiver;
connect the equipment into an outlet on a circuit different from that which the receiver is connected; consult the dealer or an expe-
rienced radio/television technician for help. The user must use shielded cables and connectors with this product. Any changes or
modifications to this product not expressly approved by the party responsible for compliance could void the user’s authority to
operate the equipment.

Storage

All connected equipment should be turned off, then disconnected from the UPS to avoid battery
drain. Unplug your UPS from its AC receptacle, then press and hold its ON/OFF button to deactivate
it. Your UPS is now ready for storage. If you plan on storing your UPS for an extended period
of time, fully recharge the UPS batteries once every three months by plugging the UPS into 
a live AC outlet and letting the UPS charge for 4 to 6 hours. If you leave your UPS batteries 
discharged for an extended period of time, they will suffer a permanent loss of capacity.

Service

If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will
refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING
MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem.
If the UPS is within the warranty period, enclose a copy of your sales receipt.

Storage & Service

200206186 SmartPro XL Owner’s Manual 93-2078.qxd  7/30/02  5:07 PM  Page 8

Summary of Contents for Power Suppy

Page 1: ...ns 2 Quick Installation 3 Basic Operation 5 Storage Service 8 Specifications 8 SmartPro 120V Input Output Line Interactive UPS Systems Copyright 2002 Tripp Lite All rights reserved SmartPro is a regis...

Page 2: ...ry Warnings Your UPS does not require routine maintenance Do not open your UPS for any reason except battery replacement There are no user serviceable parts inside Battery replacement must be performe...

Page 3: ...ors to its UPS Surge outlets Select UPS Operating Mode Press the ON OFF button to toggle your UPS between the UPS LED lit and the CHARGE ONLY LED flashing modes Choose the operating mode based on your...

Page 4: ...eded to extend runtime Adding external batteries will increase recharge time as well as runtime The illustration shows the location of your UPS s External Battery Connector where you will insert the b...

Page 5: ...until you hear a beep about 2 seconds then release it The indicator light will illuminate and AC power inverted from stored battery power will be provided at its receptacles Shut Down Your UPS Press a...

Page 6: ...d no action is required on your part BATTERY CHARGE This red light will turn ON continuously after the UPS runs a self test to indicate that the UPS s battery is weakly charged If it remains lit after...

Page 7: ...ominal 120V AC power before resetting the circuit breaker by pushing the breaker switch in to reset Charge Level Switch This switch should be set to the left unless you have connected multiple externa...

Page 8: ...FCC CLASS B RADIO TV INTERFERENCE NOTICE Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are desi...

Page 9: ...n r pida 11 Operaci n b sica 13 Almacenamiento y servicio 16 Ficha t cnica 17 SmartPro XL Sistemas UPS de 120V de entrada salida interactivos con tiempo de respaldo extendido 2002 Tripp Lite Todos los...

Page 10: ...dar sus garant as Advertencias sobre las bater as El sistema UPS no requiere mantenimiento rutinario alguno No abra el UPS por ning n motivo excepto para el reemplazo de las bater as No hay partes int...

Page 11: ...resores de sobretensiones Selecci n del modo de operaci n del UPS Oprima el bot n ON OFF encendido y apagado para alternar el sistema UPS entre los modos UPS LED encendido y CHARGE ONLY o carga s lo L...

Page 12: ...respaldo El agregar bater as externas incrementar el tiempo de recarga as como el tiempo de respaldo v La ilustraci n muestra la ubicaci n del conector de bater as externas del UPS en donde usted ins...

Page 13: ...os apagones si el equipo no se encuentra en uso Arrancar en fr o el sistema UPS Se puede arrancar en fr o la unidad UPS y utilizarla como fuente aut noma de energ a cuando la energ a el ctrica no est...

Page 14: ...a toma de CA LINE POWER energ a de l nea Esta luz de color verde se encender cada vez que el sistema UPS est recibiendo energ a de la l nea normal de CA La luz parpadear mientras el sistema UPS est en...

Page 15: ...S a cualquier estaci n de trabajo o servidor USB Al utilizar este puerto el UPS puede comunicar a la computadora el estado de falla de l nea y de nivel bajo de bater a Utilice el software Tripp Lite y...

Page 16: ...ichas distorsiones el sistema UPS normalmente hace un cambio para entregar una alimentaci n sinusoidal PWM mediante sus bater as y durante todo el tiempo que permanezca la distorsi n En el caso de reg...

Page 17: ...salida VA Vatios 1050 800 1500 980 1500 980 Tiempo de operaci n de la bater a Media carga Plena carga Minutos 26 6 20 7 20 7 Tiempo de recarga de la bater a 2 4 horas 2 4 horas 2 4 horas Certificacio...

Page 18: ...o existe garant a alguna de que estas interferencias no vayan a ocurrir en una instalaci n particular Si este equipo causa interferencias da inas a la recepci n de las se ales de radio o televisi n lo...

Page 19: ...ion rapide 21 Exploitation de base 23 Entreposage et entretien 26 Sp cifications 27 SmartPro XL Tension d entr e et de sortie de 120 V syst mes UPS Line Interactive Extended Run 2002 Tripp Lite Tous d...

Page 20: ...ntra ner une annulation de sa garantie tout comme celle couvrant le suppresseur de surtension Mises en garde relatives la batterie Votre syst me UPS n exige pas d entretien courant Ne l ouvrez pas que...

Page 21: ...ant lev e comme des appareils lectrom nagers des imprimantes laser et des suppresseurs de surtension Choix du mode d exploitation du syst me UPS Appuyez sur le commutateur ON OFF pour basculer entre l...

Page 22: ...externes allongera le temps de recharge ainsi que la dur e d ex cution Cette illustration pr sente l emplacement du connecteur de la batterie externe de votre syst me UPS au niveau d insertion du c bl...

Page 23: ...d sactivant l onduleur pour emp cher que la batterie ne se d charge durant les pannes secteur lorsque l quipement n est pas utilis D marrage froid de votre syst me UPS Si vos batteries sont charg es v...

Page 24: ...r judiciables Les descriptions des voyants lumineux ne sont applicables que si le syst me UPS est branch une prise de secteur et mis sous tension LINE POWER ALIMENTATION SECTEUR Ce voyant vert s allum...

Page 25: ...SB de votre syst me UPS se connecte tout poste de travail ou serveur muni d un port USB En utilisant ce port votre syst me UPS peut transmettre les tats de panne de secteur et de baisse de charge de l...

Page 26: ...pour prot ger le syst me UPS contre la distorsion de l onde d entr e c a Quand une telle distorsion se produit le syst me UPS basculera normalement vers l alimentation de batterie pour fournir une on...

Page 27: ...FCC Ces limites sont con ues pour fournir une installation commerciale une protection raisonnable contre les brouillages nuisibles Ce mat riel produit utilise et peut mettre de l nergie de fr quence...

Page 28: ...tallation particuli re Si ce mat riel cause un brouillage nuisible la r ception radio ou t l vision ce qui peut tre d termin en mettant le dispositif hors tension et puis de nouveau en marche l utilis...

Reviews: