Match Battery Amp-Hour Capacity to Your Application

Select a battery or system of batteries that will provide your Inverter/Charger with proper DC voltage
and an adequate amp-hour capacity to power your application. Even though Tripp Lite Inverter/Chargers
are highly efficient at DC-to-AC inversion, their rated output capacities are limited by the total amp-
hour capacity of connected batteries plus the output of an alternator when one is used.

• STEP 1) Determine Total Wattage Required

Add the wattage ratings of all equipment you will
connect to your Inverter/Charger. Wattage ratings
are usually listed in equipment manuals or on
nameplates. If your equipment is rated in amps,
multiply that number times AC utility voltage to
estimate watts. (Example: a ¼ in. drill requires
1.3 amps. 1.3 amps × 230 volts = 300 watts.) 

NOTE: Your Inverter/Charger will operate at higher efficiencies
at about 75% - 80% of nameplate rating.

• STEP 2) Determine DC Battery Amps Required

Divide the total wattage required (from step 1, above) by the battery
voltage to determine the DC amps required.

• STEP 3) Estimate Battery Amp-Hours Required

Multiply the DC amps required (from step 2, above) by the number of
hours you estimate you will operate your equipment exclusively from
battery power before you need to recharge your batteries with utility-
or generator-supplied AC power. Compensate for inefficiency by
multiplying this number by 1.2. This will give you a rough estimate of
how many amp-hours of battery power (from one or several batteries)
you should connect to your Inverter/Charger.

NOTE: Battery amp-hour ratings are usually given for a 20-hour discharge rate. Actual amp-
hour capacities are less when batteries are discharged at faster rates. For example, batteries
discharged in 55 minutes provide only 50% of their listed amp-hour ratings, while batteries
discharged in 9 minutes provide as little as 30% of their amp-hour ratings.

• STEP 4) Estimate Battery Recharge Required 

You must allow your batteries to recharge long enough to replace the
charge lost during inverter operation or else you will eventually
deplete your batteries. To estimate the minimum amount of time you
need to recharge your batteries given your application, divide your
required battery amp-hours (from step 3, above) by your Inverter/
Charger’s rated charging amps (see the 

Specifications

section).

NOTE: For Tripp Lite Inverter/Chargers providing 1000 watts or less of continuous AC power,
a full-size battery will normally allow sufficient power for many applications before
recharging is necessary. For mobile applications, if a single battery is continuously fed by an
alternator at high idle or faster, then recharging from utility or generator power may not be
necessary. Tripp Lite Inverter/Chargers will provide adequate power for ordinary usage
within limited times without the assistance of utility or generator power. However, when
operating extremely heavy electrical loads at their peak in the absence of utility power, you
may wish to “assist your batteries” by running an auxiliary generator or vehicle engine, and
doing so at faster than normal idling.

Battery Selection

Example

Tools

300W +  220W +  20W  = 

540W

¼" Drill

Orbital Sander

Cordless Tool

Charger

Appliances

300W + 140W +  100W = 

540W

Blender

Color TV

Laptop Computer

540 watts ÷ 12V = 

45 DC Amps

45 DC Amps ×

2 Hours Runtime ×

1.2 Inefficiency Rating =

108 Amp-Hours

108 Amp-Hours ÷

6 Amps 

Inverter/Charger Rating =

18 Hours Recharge

200705102 93-2678 APSX700HF OM.qxd  8/30/2007  12:34 PM  Page 4

Summary of Contents for PowerVerter DC-to-AC Inverter/Charger APSX700HF

Page 1: ...ing your connected battery bank Built in surge suppression provides connected equipment with additional protection The APSX700HF is the clean quiet emergency backup power alternative to gas generators...

Page 2: ...e would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC inpu...

Page 3: ...AC Connection section for instructions AC Output IEC 60320 C13 permits connection of equipment that would normally be plugged into a utility outlet Note The unit will always pass AC power to connected...

Page 4: ...r a 20 hour discharge rate Actual amp hour capacities are less when batteries are discharged at faster rates For example batteries discharged in 55 minutes provide only 50 of their listed amp hour rat...

Page 5: ...at the front and rear of the unit The user must supply mounting hardware and is responsible for determining if the hardware and mounting surface are adequate to support the weight of the unit Read the...

Page 6: ...ect Fuse NEC National Electrical Code article 551 requires that you connect all of your Inverter Charger s positive DC connectors directly to a UL listed fuse s and fuse block s within 18 inches 45 72...

Page 7: ...tching between operating modes as appropriate to your situation AUTO Switch to this mode when you need constant uninterrupted AC power for connected equipment The Inverter Charger will supply AC power...

Page 8: ...d alert you to fault conditions Battery Charge Level Indicator Illuminated Battery Capacity Charging Discharging Green 91 Full Green Yellow 81 90 Yellow 61 80 Yellow Red 41 60 Red 21 40 All three ligh...

Page 9: ...Service for assistance All Three Battery Indicator Battery is overcharged Unit will Disconnect any auxiliary chargers Lights Are Flashing shut down to prevent battery Reset by moving Operating Mode Se...

Page 10: ...Capacity DC 6 A Line VAC Operation Total Input AC Current Continuous Charger at Maximum 4 5 A Maximum Output Current Continuous 3 A Note on Labeling Two symbols are used on the APS labels V AC Voltag...

Page 11: ...ty does not apply to equipment which has been damaged by accident negligence or misapplication or has been altered or modified in any way including opening of the unit s casing for any reason This war...

Page 12: ...12 1111 W 35th Street Chicago IL 60609 USA 1 773 869 1234 www tripplite com 200705102 93 2678...

Reviews: