16
Battery information
Indicates the battery capacity by 0-25%, 26-50%, 51-75% and 76-100%.
Indicates the battery is not connected.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage, frequency or battery voltage.
VAC: Input Voltage, VDC: Battery Voltage, Hz: Input Frequency
4.3 Audible Alarm
Description
Alarm Status
Mutable
UPS Status
Bypass Mode
Beeps once every 2 minutes
Yes
Battery Mode
Beeps once every 4 seconds.
Fault Mode
Beeps continuously.
Warning
Overload
Beeps twice per second.
No
All other warnings
Beeps once per second.
Fault
All
Beeps continuously.
Yes
4.4 Single UPS Operation
4.4.1 Turning On the UPS (On-line Mode)
1) Make sure the power supply is correctly connected. If you have an external battery pack, set the breaker of the battery pack to the
“ON” position, then switch the UPS input breaker to the “ON” position. At this time, the fan will be running and the UPS will proceed to
power-on for initialization. Several seconds later, the UPS will operate in Bypass Mode and supply power to the connected loads via the
bypass.
Note:
In Bypass Mode, the load is not protected by the UPS. To protect connected devices, turn on the UPS as shown in Step 2.
2) Press and hold the “ON” button for 0.5 seconds to turn on the UPS. The alarm will beep once.
3) A few seconds later, the UPS will enter On-line Mode. If utility power is abnormal, the UPS will operate in Battery Mode without
interruption.
Note:
When the UPS is running low on battery power, it will automatically shut down in Battery Mode. The UPS will auto restart in On-line Mode once
utility power is restored.
4.4.2 Turning On the UPS without Utility Power (Battery Mode)
1) When using an external battery pack, make sure the two battery strings are correctly connected before switching the battery pack
breaker to the “ON” position.
2) Switch the battery pack breaker to the “ON” position.
3) Press the “ON” button to set up the power supply for the UPS. The UPS will enter Power-on Mode. After initialization, the UPS will enter
“No Output Mode”/Standby Mode. When this happens, press and hold the “ON” button for 0.5 seconds to turn on the UPS. The alarm
will beep once.
4) A few seconds later, the UPS will turn on and enter Battery Mode.
4. Operation
Summary of Contents for S3M30KX
Page 125: ...125 2 4 2 5 2 6 2 7 TN 4 2 EN IEC 62040 1...
Page 129: ...129 3 3 2 1 1 3 1 2 3 2 3 5 3 1 3 2...
Page 132: ...132 3 OFF R S T N 3 4 3 7 1 2 3 5 3 R S T N R S T N 4 5 6 7 8 S3M30KX S3M40KX 2 1...
Page 135: ...135 4 H M S Fault Warning 4 9 4 11 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO...
Page 147: ...147 4 2...
Page 148: ...148 ECO ECO 4...
Page 149: ...149 4 CVCF CF 50 60 4...
Page 150: ...150 2 CVCF Test 0 5 I P 4...
Page 151: ...151 4 3 4 11 4 9...
Page 155: ...155 6 EPO EPO OFF EPO 43 14 15 16 17 18 19 7 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Page 156: ...156 7 7 1 40 C 90 6 24 24 3 7 2 BUS 7 3 Tripp Lite S3MX 1 0 40 C 2 25 C 3 24 7 4 Tripp Lite...