26
4. Operation
20: Output-C Voltage Calibration
Interface
Setting
Parameter 2:
Always shows
OP.V
as output voltage.
Parameter 3:
Shows the internal measurement value of the output-C voltage. You can calibrate
it by pressing
Up
or
Down
according to the measurement from an external voltage meter. The
calibration result will be effective by pressing
Enter
. The calibration range is limited /-9V.
This function is normally used for parallel operation.
*It will display number 2 under
OP.U
to represent the output C voltage.
21: Current Charger Setting
Interface
Setting
Parameter 2:
CHG indicates adjust charger current function.
Parameter 3:
Set the charger current. The setting range is 1A to 4A. The default value is 2A for
30K/40K and 4A for 60K/80K.
• 30K-40K: Adjust the charger current function only for one charger board installed on UPS. This
feature will not work when more than one charger board is installed.
• 60K-80K: Adjust charger current function for only two charger boards installed on UPS. This
feature will not work when more than two charger boards are installed.
Note:
Once the charger board is extended, all installed charger boards will charge the battery at the maximum
power of 4A current. Extension board kits are available for the S3M30KX and S3M40KX models (CBKIT30-40)
and the S3M60KX and S3M80KX models (CBKIT30-80).
22: Charging Boards Number Setting
Interface
Setting
Parameter 2:
CHG indicates adjust charging boards quantity function.
Parameter 3:
Set the charging boards quantity. The setting range is from 1 to 3 and the default
value is 1.
• 60K-80K: Two charger boards are one group. If the UPS installs four charger boards, it needs to
be set to 2. If the UPS installs six charger boards, it needs set to 3.
Note:
Once the charger board is extended, this parameter has to be changed accordingly.
4.8 Operating Mode/Status Description
The following table shows the LCD screen for operating modes and status.
(1) If the UPS is in normal operation, it will show seven screens one-by-one, which represents 3-phase input voltages (An, bn, Cn), 3-line
input voltages (Ab, bC, CA) and frequency in turns.
(2) If parallel UPS systems are successfully set up, it will show one more screen with “
PAR
” in Parameter 2 and assigned number in
Parameter 3 (as shown in the below parallel screen illustration). The primary UPS will be assigned automatically as “
001
”. Secondary
UPS systems will be assigned as either “002” or “003”. The assigned numbers may be changed dynamically in the operation.
Parallel Screen
Summary of Contents for S3M30KX
Page 125: ...125 2 4 2 5 2 6 2 7 TN 4 2 EN IEC 62040 1...
Page 129: ...129 3 3 2 1 1 3 1 2 3 2 3 5 3 1 3 2...
Page 132: ...132 3 OFF R S T N 3 4 3 7 1 2 3 5 3 R S T N R S T N 4 5 6 7 8 S3M30KX S3M40KX 2 1...
Page 135: ...135 4 H M S Fault Warning 4 9 4 11 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO...
Page 147: ...147 4 2...
Page 148: ...148 ECO ECO 4...
Page 149: ...149 4 CVCF CF 50 60 4...
Page 150: ...150 2 CVCF Test 0 5 I P 4...
Page 151: ...151 4 3 4 11 4 9...
Page 155: ...155 6 EPO EPO OFF EPO 43 14 15 16 17 18 19 7 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Page 156: ...156 7 7 1 40 C 90 6 24 24 3 7 2 BUS 7 3 Tripp Lite S3MX 1 0 40 C 2 25 C 3 24 7 4 Tripp Lite...