UPS housing material
Steel
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature
Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
97.7
Battery mode BTU / hr.
(full load)
313.4
COMMUNICATIONS
Communications interface
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port
description
Supports detailed monitoring of UPS and site power conditions
LINE / BATTERY TRANSFER
Transfer time
2-4 milliseconds
Low voltage transfer to
battery power (setpoint)
83 (120v), 159 (230v)
High voltage transfer to
battery power (setpoint)
147 (120v), 282 (230v)
SPECIAL FEATURES
High availability UPS
features
Hot swappable batteries
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to CE (EU); Meets FCC Part 15 Category A (EMI)
WARRANTY
Product Warranty Period
(Worldwide)
2-year limited warranty
Connected Equipment
Insurance (U.S., Canada &
Puerto Rico)
$250,000
Ultimate Lifetime Insurance
Related Items
Optional Products
Product Type
Related Model
Description
Qty.
Extended Warranties
WEXT3-500-1500
3-Year Extended Warranty - For Smart Line-Interactive and Online
Tower or Rack models, 1500VA or less
1
Extended Warranties
WEXT5-500-1500
5-Year Extended Warranty - For Smart Line-Interactive and Online
Tower or Rack models, 1500VA or less
1
Power Distribution
PDU1215
Basic PDU / Power Distribution Unit - Safe, reliable power distribution
for critical networking equipment
1
SNMP Accessories
ENVIROSENSE
Monitors temperature, humidity and contact-closure inputs. (Requires
SNMPWEBCARD or switched PDU.)
1