background image

Owner’s Manual

1

SmartPro

®

 LCD UPS Systems

Models: 

SMART1200LCD 

(Series Number: AGOM5515)

Important Safety Instructions  2
Quick Installation  

4

Basic Operation  

5

UPS On/Off  

5

LCD  

5

LCD Features 

5

Display Power Conditions 

5

Enable/Disable Alarm 

5

LCD Brightness 

6

Self-test 6

Power Sensitivity 

6

Scroll Control 

7

External Battery Settings 

7

Error Messages 

7

Features  

8

Battery Replacement 

9

Storage and Service   

11

Product Registration   

11

Español 13 
Français 25

SMART1500LCD 

(Series Number: AG-8869) 

SMART1500LCDXL 

(Series Number: AGSM8191)

Not suitable for mobile applications

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

Copyright © 2017 Tripp Lite. All rights reserved.

PROTECT YOUR INVESTMENT!

Register your product for quicker service  

and ultimate peace of mind. 

You could also win an 

ISOBAR6ULTRA surge protector— 

a $100 value!

www.tripplite.com/warranty

17-02-143-9336B5.indb   1

3/14/2017   2:03:49 PM

Summary of Contents for SMART1200LCD

Page 1: ...Features 8 Battery Replacement 9 Storage and Service 11 Product Registration 11 Español 13 Français 25 SMART1500LCD Series Number AG 8869 SMART1500LCDXL Series Number AGSM8191 Not suitable for mobile applications 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2017 Tripp Lite All rights reserved PROTECT YOUR INVESTMENT Register your product for quicker service and ultim...

Page 2: ...d under warranty UPS Connection Warnings Connect your UPS directly to a properly grounded AC power outlet Do not plug the UPS into itself this will damage the UPS Do not modify the UPS s plug and do not use an adapter that would eliminate the UPS s ground connection Do not use extension cords to connect the UPS to an AC outlet If the UPS receives power from a motor powered AC generator the generat...

Page 3: ... Battery replacement should be performed only by authorized service personnel using the same number and type of batteries Sealed Lead Acid The batteries are recyclable Refer to your local codes for disposal requirements or visit http www tripplite com support recycling program for recycling information Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges R B C Visit Tripp...

Page 4: ...or the unit s battery will only be accessible after it has been charged for 24 hours STEP 3 Plug your equipment into the UPS Your UPS is designed to support electronic equipment only You will overload the UPS if the total VA ratings for all the equipment you connect to the outlets exceeds the UPS s Output Capacity To find your equipment s VA ratings look on their nameplates If the equipment is lis...

Page 5: ...all tool in the slots on the sides of the display to pop it out of the UPS housing rotate the display and snap it back into the UPS housing LCD Features Tap the MODE button to advance from one display to the next Use the MUTE button to toggle settings for Power Sensitivity Control External Battery Setting Control Scroll Control Alarm LCD Brightness and Self test functions The last option displayed...

Page 6: ...last option displayed before navigating away from this menu option will be the selected setting This setting is normally set to 100 which enables the UPS to protect against waveform distortions in its AC input When such distortion occurs the UPS will normally switch to providing PWM sine wave power from its battery reserves for as long as the distortion is present In some areas with poor utility p...

Page 7: ...XL model only Tap the MODE button repeatedly to advance to the External Battery screen as shown here Press the MUTE button to advance to the next available option The last option displayed before navigating away from this menu option will be the selected setting Note The Battery Runtime calculation is based on this setting This feature setting allows the user to configure the UPS for use with an E...

Page 8: ...REE download at www tripplite com and appropriate USB or DB9 cable Both a USB and a DB9 cable are included with your UPS Notes 1 This connection is optional The UPS will work properly without this connection 2 This UPS System provides basic communication compatibility with most integrated Windows Macintosh and Linux power management applications Battery Backup Protected Surge Protected Outlets Pro...

Page 9: ...tery cartridge For the SMART1500LCDXL model only Tripp Lite BP24V15RT2U external battery pack rated 24Vdc 14Ahr with overcurrent protection should be connected to the external battery pack connector For further information about replacement compatibility and ordering visit Tripp Lite on the Web at http www tripplite com products battery finder To Replace the Batteries 1 Remove the retaining screw ...

Page 10: ... place the new batteries into the UPS and connect the positive red connectors and negative black connectors 5 Reattach the bottom panel and secure using the retaining screw removed in step 1 17 02 143 9336B5 indb 10 3 14 2017 2 04 00 PM ...

Page 11: ...ducts shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid Mark the RMA number on the outside of the package If the product is within its warranty period enclose a copy of your sales receipt Return the product for service using an insured carrier to the address given to you when you request the RMA Visit www tripplite com warranty today to regis...

Page 12: ... Technical Requirements Document s The Department does not guarantee the equipment will operate to the user s satisfaction Before installing this equipment users should ensure that it is permissible to be connected to the facilities of the local telecommunications company The equipment must also be installed using an acceptable method of connection The customer should be aware that the compliance ...

Reviews: