background image

DC system voltage
(VDC)

24

Battery recharge rate
(included batteries)

Less than 8 hours from 10% to 90%

Replacement battery
cartridge (internal UPS
battery replacement)

RBC51

 (requires 2)

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 92 to 150

Overvoltage correction

Input voltages between 129 and 147 are reduced by 15%

Undervoltage
correction

Input voltages between 92 and 108 are boosted by 18%

LEDS ALARMS & SWITCHES

Front panel LCD
display

LCD screen with scroll buttons indicates Input voltage, Output voltage, Frequency (Hz), AVR boost / cut status,
Output load in watts, Output load percentage, Output load in watts, Battery voltage and Estimated runtime in
minutes

Alarms

Audible alarm indicates power-failure and low-battery conditions

Alarm cancel operation

Power-fail alarm can be silenced using alarm-cancel switch

Switches

Power switch offers whole UPS power control; Scroll/mute button enables LCD selection options and silences
audible alarm; Test button initiates self test

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

650

UPS AC suppression
response time

Instantaneous

UPS Dataline
suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet; Coax jacks (1 set)

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form
factors supported with
included accessories

Tower

Primary form factor

Tower

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)

8 x 5.75 x 15.4

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)

20.3 x 14.6 x 39.1

UPS / Power Module
weight (lbs)

27

UPS / Power Module
weight (kg)

12.3

Summary of Contents for SMART1500LCDT

Page 1: ...ures of Windows and Mac OS X Built in surge dataline surge suppression jacks protect equipment with single line dialup DSL or network Ethernet connection Built in audible alarm and large LCD front panel display offers easy to read icon based status indicators and detailed numeric data regarding input voltage output voltage frequency load percentage load watts battery voltage and runtime in minutes...

Page 2: ...put Voltage s Supported 120V Frequency compatibility 50 60 Hz Output voltage regulation line mode 10 6 Output voltage regulation Battery mode 5 Built in UPS output receptacles 10 5 15R outlet s Surge suppression only outlets 5 UPS outlets 5 surge only outlets Output AC waveform AC mode Sine wave Output AC waveform battery mode PWM sine wave INPUT Rated input current at maximum load 12A Nominal Inp...

Page 3: ...ted runtime in minutes Alarms Audible alarm indicates power failure and low battery conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch Switches Power switch offers whole UPS power control Scroll mute button enables LCD selection options and silences audible alarm Test button initiates self test SURGE NOISE SUPPRESSION UPS AC suppression joule rating 650 UP...

Page 4: ...m www tripplite com Communications cable USB and DB9 Serial cabling included WatchDog compatibility Supports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time 2 milliseconds AC to battery mode 6 milliseconds battery to AC mode Low voltage transfer to battery power setpoint 92 High voltage transfer to battery power setpoint 150 SPECI...

Page 5: ...For Smart Line Interactive and Online Tower or Rack models 1500VA or less 1 WATCHDOGSW WatchDog Service Monitoring Reboot Software 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 5325 Copyright 2013 Tripp Lite All rights reserved All trademarks are the sole property of th...

Reviews: