Recommended
Electrical Service
15A 120V
Phase
Single-Phase
BATTERY
Full load runtime
(minutes)
4 min. (900w)
Half load runtime
(minutes)
12 min. (450w)
External battery
pack compatibility
BP24V15RT2U
(limit 1)
DC system voltage
(VDC)
24
Battery recharge
rate (included
batteries)
Less than 4.5 hours from 10% to 90%
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage
correction
Input voltages between 128 and 147 are reduced by 12%
Undervoltage
correction
Input voltages between 93 and 107 are boosted by 14%
Severe
undervoltage
correction
Input voltages between 75 and 92 are boosted by 30%
LEDS ALARMS & SWITCHES
LED Indicators
Front panel LCD display
Front panel LCD
display
Numeric LCD interface reports Input Voltage, Output Voltage, Battery Charge Percentage, Estimated Runtime in
Minutes, Load Percentage, Load Watts; Additional LCD icons report battery charge level (5 "bars"), Line Power Mode,
Battery Mode, Replace Battery and Auto-Voltage Regulation / AVR status; LCD interface control options include Alarm
Disable, Display Scrolling, Initiate Self-test, LCD brightness, External Battery setting and line sensitivity
Alarms
Audible alarm indicates power-failure and low-battery conditions; Alarm can be permanently silenced via LCD interface
Alarm cancel
operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery
status
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; dimmer switch controls LCD brightness
SURGE / NOISE SUPPRESSION
UPS AC
suppression joule
rating
1038
UPS AC
suppression
response time
Instantaneous
UPS Dataline
suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC noise
suppression
Yes
PHYSICAL