Electrical Service

15A 120V

Phase

Single-Phase

BATTERY

Full load runtime
(minutes)

4 min. (900w)

Half load runtime
(minutes)

12 min. (450w)

External battery
pack compatibility

BP24V15RT2U

 (limit 1)

DC system voltage
(VDC)

24

Battery recharge
rate (included
batteries)

Less than 4.5 hours from 10% to 90%

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147

Overvoltage
correction

Input voltages between 128 and 147 are reduced by 12%

Undervoltage
correction

Input voltages between 93 and 107 are boosted by 14%

Severe
undervoltage
correction

Input voltages between 75 and 92 are boosted by 30%

LEDS ALARMS & SWITCHES

LED Indicators

Front panel LCD display

Front panel LCD
display

Numeric LCD interface reports Input Voltage, Output Voltage, Battery Charge Percentage, Estimated Runtime in
Minutes, Load Percentage, Load Watts; Additional LCD icons report battery charge level (5 "bars"), Line Power Mode,
Battery Mode, Replace Battery and Auto-Voltage Regulation / AVR status; LCD interface control options include Alarm
Disable, Display Scrolling, Initiate Self-test, LCD brightness, External Battery setting and line sensitivity

Alarms

Audible alarm indicates power-failure and low-battery conditions; Alarm can be permanently silenced via LCD interface

Alarm cancel
operation

Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery
status

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation; dimmer switch controls LCD brightness

SURGE / NOISE SUPPRESSION

UPS AC
suppression joule
rating

1038

UPS AC
suppression
response time

Instantaneous

UPS Dataline
suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC noise
suppression

Yes

PHYSICAL