32
2. Input / Output Values -
This screen reports UPS input and output values.
[0-MAIN MENU]
[2-INPUT/OUTPUT VALUES]
Input:-
Voltage
###.# Vac
Frequency
##.# Hz
Output:-
Voltage
###.# Vac
Frequency
##.# Hz
Power
#### Watt
VA
#### VA
Load Percent
### %
Battery:-
Temperature
## Deg C
Voltage
##.## Vdc
Event-Timer
INVERTER EVENTS
#####
INVERTER TIMER
####.# Hours
Boost EVENTS
#####
Boost TIMER
####.# Hours
Buck EVENTS
#####
Buck TIMER
####.# Hours
3. UPS Control Actions -
This screen offers control of UPS operation.
[0-MAIN MENU]
[3-Control]
30) Self Test
31) Dry Contact Test
32) External Fan Test
33) Ups Output
34) Event/Timer Reset
UPS Control Sub-Menu Options
Self Test (#30) -
Selecting the SELF TEST option will cause the UPS to switch to
battery mode for the duration selected in the SETTINGS/TEST TIME field (factory
default is one minute). The UPS must be in Normal, Boost or Buck mode before
a self-test will successfully be initiated. To initiate a SELF TEST, navigate to the
SELF TEST screen and select the START option. Once entered, the UPS will switch
to battery mode to test the battery, inverter and battery transfer circuits for proper
operation.
Self Test
0) Stop
1) Start
>
Operation