5. Line Conditioning Setup -
This option allows customization of the UPS system’s
line-interactive voltage regulation capabilities.
CAUTION: Improperly parameter
value setting can cause permanent damage to the unit. Changes should
only be made by qualified and trained personnel.
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
55) Buck Function
56) Boost Function
57) Sense Type
58) Line Qualify Time
59) High Limit [152] Vac
60) Low Limit [088] Vac
61) Boost Low [102] Vac
62) Buck High [128] Vac
63) High Gap [005] Vac
64) Low Gap [005] Vac
*) High back [147] Vac
*) Low back [093] Vac
*) Boost back [107] Vac
*) Buck back [123] Vac
>
Line Conditioning Sub-Menu Options
Buck Function (#55) -
Selecting this option allows users to enable or disable
line interactive UPS overvoltage (BUCK) correction. Select ENABLE to turn on
overvoltage regulation. Select DISABLE to turn off overvoltage regulation (default =
Enabled).
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
[55-Buck Function]
Current setting is [Enable]
0) Disable
1) Enable
>
Boost Function (#56) -
Selecting this option allows users to enable or disable
line interactive UPS undervoltage (BOOST) correction. Select ENABLE to turn on
undervoltage regulation. Select DISABLE to turn off undervoltage regulation (default
= Enabled).
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
[56-Boost Function]
Current setting is [Enable]
0) Disable
1) Enable
>