UPS Shipping
dimensions (height x
width x depth / inches)
22.2 x 12.8 x 16.5
UPS Shipping
dimensions (height x
width x depth / cm)
56.5 x 32.4 x 41.9
Shipping weight (lbs)
96
Shipping weight (kg)
43.6
UPS housing material
PVC
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature
Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
82.4
Battery mode BTU / hr.
(full load)
1219.3
COMMUNICATIONS
Communications
interface
DB9 Serial; Contact closure
Network monitoring
port description
Supports detailed monitoring of UPS and site power conditions; contact closure communications via two
additional DB9 ports (3 total)
PowerAlert software
Included
Communications cable
3 DB9 cables included
LINE / BATTERY TRANSFER
Transfer time
2-4 milliseconds
Low voltage transfer to
battery power (setpoint)
87
High voltage transfer to
battery power (setpoint)
140
SPECIAL FEATURES
Cold Start (startup in
battery mode during a
power failure)
Cold-start operation supported
Green & high efficiency
features
Individually controllable load banks
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A
(EMI)
WARRANTY
Product Warranty
Period (Worldwide)
2-year warranty, 3 year with
registration
. Note:
registration
is required for 3-year warranty.